Partner Name | Tripp Lite, Div of Trippe MFG., Co. |
Model Name | AG-0644 |
Updated On | 2024-03-28 |
Last Update | 2024-03-29 |
Power Conversion Mechanism | Static |
Minimum Configuration Tested Model Number | SU3000RTXL2UA |
Active Output Power Rating Minimum Configuration (W) | 2740 |
Apparent Output Power Rating Minimum Configuration (VA) | 3000 |
Topology (ac) | Multi-Mode Double Conversion |
Topology and Product Type Combined | ac - Other |
Application | Data Center,Consumer,Commercial |
Rated Input Voltage (V rms) | 100-125 |
Rated Input Frequency (Hz) | 50-60 |
Rated Output Voltage (V) | 100-125 |
Rated Output Frequency (Hz) | 50-60 |
Rack Mountable | Yes |
Rack Mount Height (U) | 2 |
Height (mm) | 86 |
Width (mm) | 438 |
Depth (mm) | 630 |
Normal Mode(s) Input Dependency Characteristic (ac) | Voltage and Frequency Independent,Voltage and Frequency Dependent |
Modular UPS | No |
Number of Normal Modes | Multiple-normal-mode |
Default Normal Mode (ac) | Voltage and Frequency Independent |
Test Input Voltage (V rms) | 120 |
Test Input Frequency (Hz) | 60 |
Test Output Voltage (V) | 120 |
Test Output Frequency (Hz) | 60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) | 19.6 |
Total Input Power in W at 0% Load Min Config Highest Dependency (ac) | 15.2 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) | 89.9 |
Efficiency at 25% Load Min Config Highest Dependency (ac) | 96.4 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) | 91.8 |
Efficiency at 50% Load Min Config Highest Dependency (ac) | 97.6 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) | 91.7 |
Efficiency at 75% Load Min Config Highest Dependency (ac) | 97.7 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) | 91.2 |
Efficiency at 100% Load Min Config Highest Dependency (ac) | 97.6 |
Weighted Efficiency Calc Min Config Lowest Dependency | 91.6 |
Weighted Efficiency Calc Min Config Highest Dependency | 97.6 |
Minimum Configuration Input Power Factor Lowest-Input Dependency | 0.98 |
Minimum Configuration Input Power Factor Highest-Input Dependency | 1 |
Efficiency (%) | 93.1 |
Modular UPS Module Tested Model Number | N/A |
Energy Storage Mechanism | Battery |
Energy Storage System Technology | Valve Regulated Lead-acid Battery |
Energy Storage System Configuration | Integral |
Energy Storage System Removable to Another Room | No |
Energy Storage System Runtime at 100% Load (min.) | 3 |
Energy Storage System Runtime at 50% Load (min.) | 10 |
Energy Storage System Warranty (yrs) | 3 |
Energy Storage System Information URL | https://www.tripplite.com/ |
Battery Recycling URL | https://www.tripplite.com/support/recycling-program |
Network Connections Available | USB Port |
Communication Protocols | None |
Manufacturer Take Back Program | Yes |
Manufacturer Take Back Program URL | https://www.tripplite.com/support/recycling-program |
Model Web Page URL | https://www.tripplite.com/products/ups-battery-backup~11 |
Test Method Guidelines | N/A |
Date Available on Market | 03/01/2022 |
Date Certified | 12/05/2021 |
Markets | United States, Canada |
CB Model Identifier | ES_1097458_SU3000RTXL2UA_02182022065040_1417794 |