O3 Hub Application Guide

Delta Controls Inc.

Object Instance Numbers for Speaker, Bluetooth, and...

Sets the speaker volume in the range 0–10. value is 0 (Off). MV30s006. ... Setting Up the O3 Hub. Object Name Bluetooth Transmit Power Bluetooth Transmit Power MIC.

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 50 Pages, 1.20MB

Document DEVICE REPORTO3 Hub Application Guide
O3 Hub
Application Guide
Edition 1.0

© 2021 Delta Controls Inc. All rights reserved.
No part of this document may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language (natural or computer), in any form or by any means, without the prior written permission of Delta Controls Inc.
Limited permission is granted to reproduce documents released in Adobe® Portable Document Format (PDF) electronic format in paper format. Documents released in PDF electronic format may be printed by end-users for their own use using a printer such as an inkjet or laser device. Authorized distributors of Delta Controls Inc. products (Delta Partners) may print PDF documents for their own internal use or for use by their customers. Authorized Delta Partners may engage a printing or copying company to produce copies of released PDF documents with the prior written permission of Delta Controls Inc.
Information in this document is subject to change without notice and does not represent a commitment to past versions of this document on the part of Delta Controls Inc. Delta Controls Inc. may make improvements and/or changes to this document/the associated software/or associated hardware at any time.
BACstat, Earthright, enteliBRIDGE, enteliBUS, enteliCLOUD, enteliSTAT, enteliTOUCH, enteliVIZ, enteliVAULT, enteliWEB, enteliZONE, O3, ORCAview, and ORCAweb are registered trademarks of Delta Controls Inc.
All other trademarks are the property of their respective owners.
Document edition: 1.0

Contents

Introduction

5

About the O3 System and the O3 Hub

5

Setting Up the O3 Hub

7

Main Steps to Set Up the O3 Hub After Installation

7

Creating an Object Database

8

Object Instance Numbers for Input Sensors

8

Object Instance Numbers for Speaker, Bluetooth, and EnOcean

10

Object Instance Numbers for Light Ring Display

12

Object Instance Numbers for IR Blaster

15

Object Instance Number for Termination Switch

17

Object Instance Numbers for Universal I/O (O3-HUB-02 models)

17

Calibrating the Temperature

18

Creating a Custom Light Ring Color

18

Loading Custom Sounds

19

Configuring the IR Blaster

21

Troubleshooting the O3 Hub

22

The O3 Hub is offline

22

The O3 Hub has an error state

22

The O3 Hub no longer appears on the IOM object page

22

O3 App

23

Getting Started with the O3 App

26

Before you begin

26

Install an O3-DIN controller

27

Install and Set Up an O3 Hub

27

Create Rooms and Activities for the O3 App

28

Install and Log In to the O3 App

28

O3 Room Concept

28

What is an O3 Room?

28

Components of an O3 Room

28

What is an O3 Room Activity?

29

What is an Occupant?

29

Permissions

29

Room and O3 App

30

Creating O3 Rooms

30

Managing O3 Rooms

33

O3 Room Configuration Reference

35

Configuration

35

O3 Sensor Hubs

35

Room Controls

35

Activities

40

Principal Occupant

41

O3 Room Activity Concept

41

What is an O3 Room Activity?

41

Activities and the O3 App

41

Creating O3 Room Activities

42

Managing O3 Room Activities

42

O3 Room Activity Configuration Reference

44

Configuration

44

Activity Controls

44

Deploying the O3 App for Building Occupants

46

Users with a Google Account

46

Users with an enteliWEB Account

46

Document Revision History

48

Introduction
This guide describes how to set up and control the O3 Hub sensor hub using Delta Controls' O3DIN integrated room controller. These instructions apply to the following models:
l O3-HUB-00 (formerly O3-HUB) l O3-HUB-02 (formerly O3-HUB-2xP) l O3-HUB-02-E8 (formerly O3-HUB-En868-2xP) l O3-HUB-02-E9 (formerly O3-HUB-En902-2xP)
About the O3 System and the O3 Hub
The O3 integrated room control system is a flexible, modular room control system that integrates HVAC, dimmable lighting, door access, and motorized blind control in a single controller. As part of the O3 system, the O3 Hub combines temperature sensors, humidity sensors, occupancy detection, and wireless integration in a single device, providing occupant- and location-based control for the modern office or meeting space. Connected to an O3-DIN controller, the hub's sensor input values are mapped to BACnet objects on the controller, which can then be programmed in GCL+. O3-HUB-02 models, which require O3-DIN firmware 4.11 or later, come with two universal points that can be software-configured as inputs or outputs in enteliWEB. O3 Hubs equipped with EnOcean radios (O3-HUB-02-E8 and O3-HUB-02-E9) can receive wireless EnOcean data from up to 32 EnOcean devices. All O3 Hub devices come with an IR blaster for A/V remote control, as well as a Bluetooth beacon that enables users to control room comfort settings from their phones using the O3 mobile app.

© 2021 Delta Controls Inc.

5

Introduction
The following diagram depicts a typical O3 system:

6

O3 Hub Application Guide

Edition 1.0

Setting Up the O3 Hub
Main Steps to Set Up the O3 Hub After Installation
This section describes how to set up the O3 Hub sensor hub.
During an installation, it's assumed a unique address between 2 and 9 is assigned to the O3 Hub using the hub's rotary switch. The O3 Hub cannot be software addressed.
1. Enable CANbus protocol on the O3-DIN controller's NET3 port. When you connect the O3 Hub to the NET3 port of the controller, make sure the NP3 object on the controller is set to support CANbus protocol type. You also need to select Activate in the Command field in the same object. After a connection has been successfully established between the O3 Hub and the O3-DIN controller, the IOM object displays an online status for the sensor hub.
O3-HUB-02 models will show a second IOM entry with an address offset of +100 to represent the external I/O.
2. You can create the object database manually in enteliWEB, or you can auto-create the object database from an existing template using the Database Creation tool (enteliWEB 4.12 and later). The database includes BACnet objects that map to the sensor input values on the O3 Hub. Similar objects are also used to control the LED light ring and speaker. These objects follow a specific instance numbering format. A full list of BACnet objects for the hub can be found in Creating an Object Database.
3. Create GCL+ programs in enteliWEB for room control. These programs use the BACnet objects that you've created to execute control sequences.
4. (Optional) Configure the hub to receive EnOcean data from EnOcean devices. This step only applies to the O3-HUB-02-E8 and O3-HUB-02-E9 models. See the O3 EnOcean application guide.
5. (Optional) Configure room settings for the O3 mobile app. If you are employing the O3 mobile app on the same site, see Getting Started with the O3 App and Deploying the O3 App for Building Occupants for more information.

© 2021 Delta Controls Inc.

7

Setting Up the O3 Hub

Creating an Object Database
BACnet objects are used to map the O3 Hub input sensor values and configure light ring features. These are created in enteliWEB on the O3-DIN controller that controls the O3 Hub.
You can create objects manually or you can auto-create them from an existing template using the Database Creation tool.
The following tables list all the objects for the O3 Hub.

The letter "s" in the object instance numbers represents the O3 Hub's address switch setting (2­9).

Object Instance Numbers for Input Sensors

Object Name

Instance Number Description

Room Temperature

AI30s000

Calculated room temperature at 1 m (3 ft) above the floor. This is a composite value taken from the hub's internal temperature sensors (AI30s010 and AI30s012) and the infrared temperature sensor (AI30s011). Range -40°C to 125°C (­40°F to 257°F).

For optimal accuracy, the temperature can be calibrated to a specific reference point in the room. See Calibrating the Temperature for more details.

Estimate Occupant Humidity AI30s001

Calculated humidity (0­100%) at 1 m (3 ft) above the floor.

Occupancy

BI30s002

Active state = room occupied. Set the Binary Device Configuration property to Occupied/Unoccupied. See Occupancy States below for more details about how occupancy is determined.

Motion Sensor

BI30s003

Active state = motion detected. Set the Binary Device Configuration property to Motion/None.

Light Level

AI30s004

Intensity of light being measured (0­65535 lux).

Color Temperature

AI30s005

Color temperature of light being measured (0­65535 K).

8

O3 Hub Application Guide

Edition 1.0

Setting Up the O3 Hub

Object Name

Instance Number Description

Red Light Intensity

AI30s006

Red component of light being measured. No units but scaled from 0­65535.

Green Light Intensity

AI30s007

Green component of light being measured. No units but scaled from 0­65535.

Blue Light Intensity

AI30s008

Blue component of light being measured. No units but scaled from 0­65535.

Humidity at Ceiling

AI30s009

Humidity at ceiling height (0­100%), read from the hub's humidity sensor.

Internal Temperature

AI30s010

Temperature at ceiling height, read from the hub's humidity sensor. Range -40°C to 125°C (-40°F to 257°F).

IR Temperature

AI30s011

Average temperature of all room surfaces in the sensor's field of view, read from the hub's IR sensor. Range -40°C to 125°C (-40°F to 257°F).

Internal Temperature 2

AI30s012

Temperature at ceiling height, read from the hub's digital temperature sensor. Range -40°C to 125°C (-40°F to 257°F).

Sound Pressure Level

AI30s016

Unfiltered audio levels (0­120 dB) across the entire spectrum reported in dB SPL scale. Read-only.

Motion Sensitivity

AV30s033

PIR motion sensor sensitivity, expressed as a percentage (0­100%). 100% = maximum sensitivity, 0% = minimum sensitivity. Default value is 80%. May need adjusting based on room size and layout.

Occupancy Audio Sensitivity AV30s036

Sensitivity of the audio portion of the occupancy algorithm, expressed as a percentage (0­100%). 100% = maximum sensitivity, 0% = minimum sensitivity. Default value is 80%.

Occupancy Inactivity Period AV30s038

The amount of time (in seconds) it takes the hub to return to the unoccupied state when no motion and no audio activity is detected. Default value is 300 seconds (5 minutes).

© 2021 Delta Controls Inc.

9

Setting Up the O3 Hub

Object Name
Occupancy Audio Retrigger Period

Instance Number Description

AV30s039

The amount of time (in seconds) that activity sounds can cause the hub to remain in the occupied state after motion is detected. Default value is 1200 seconds (20 minutes). Measured from most recent motion detection event.

Occupancy States
A state change from unoccupied to occupied is triggered when motion is detected in the room, or by a combination of motion and sound. Sound alone does not trigger a state change.
The occupancy state is extended when either motion or sound is detected in the room. This sound level has to be above the baseline audio level that the O3 Hub has previously established. In addition, new sounds that fall outside of the Occupancy Audio Retrigger Period (set by the value of AV30s039) are not allowed to extend the occupancy state. This feature (available with firmware 4.6 and later) reduces artificial extension of the occupancy state by background noise.
If no motion or sound is detected after a set amount of time (the Occupancy Inactivity Period), the O3 Hub reports the room as unoccupied. This sound level has to be below the baseline audio level that the O3 Hub has previously established. You can change the Occupancy Inactivity Period using object AV30s038.

Object Instance Numbers for Speaker, Bluetooth, and EnOcean

Object Name Speaker Volume Play Sound
Sound List MIC
Sound Repeat

Instance Number Description

AV30s005

Sets the speaker volume in the range 0­10. Default value is 0 (Off).

MV30s006

Plays sounds defined by the associated MIC. Set to 1 (Idle/Off) for no sound. Values 2 to X are predefined sounds. Reverts to Idle after a sound is played. See Loading Custom Sounds.

MICx

Contains predefined stock sounds. Available through the Database Creation tool or via download from the O3 Hub product page on George Support (O3 HubScaleObjects.zip).

AV30s008

Sets how many times a sound should by played. 0 indicates indefinite repeats until changed.

10

O3 Hub Application Guide

Edition 1.0

Setting Up the O3 Hub

Object Name Bluetooth Transmit Power Bluetooth Transmit Power MIC
Enable BLE Enable EnOcean
Bluetooth Beacon MAC Address
EnOcean ID

Instance Number Description

MV30s024

Sets the strength (maximum transmit power) of the Bluetooth beacon. Default value is 4 dBM.

MICx

Contains the maximum transmit power states used by the MV30s024 object. There are 8 allowable states.

l -40 dBm l -20 dBm l -16 dBm l -12 dBm

l -8 dBm l -4 dBm l 0 dBm l 4 dBm

Available through the Database Creation tool or via download from the O3 Hub product page on George Support (O3 HubScaleObjects.zip).

BV30s026

When set to On, the Bluetooth Low Energy (BLE) beacon is enabled and broadcasting.

BV30s030

When set to On, EnOcean communication is enabled on O3-HUB-02-E8 and O3HUB-02-E9 models equipped with EnOcean antennae. Goes into fault if not an EnOcean hub. Default value is Off.

CSV30s040

Displays the MAC address of the Bluetooth beacon.
This object needs to be created so that the O3 app is aware of the room in which the O3 Hub is installed.

CSV30s044

Displays the EnOcean base ID of onboard chip. The EnOcean sending ID is determined by adding the base ID to the number of the sending device. For example, if a hub's EnOcean ID is ff9db180 and you are sending from EnOcean device 4, the sending ID would be ff9db184. If the EnOcean device being used were 12, the sending ID would be ff9db18c, since the value is in hexadecimal.

© 2021 Delta Controls Inc.

11

Setting Up the O3 Hub

Object Instance Numbers for Light Ring Display
These objects control the LED light ring's brightness and behaviors or patterns.

Object Name

Instance Numbers

Description

Light Ring Red Light Ring Green

AV30s000 AV30s001

Sets the red component of RGB value of light ring (0­255). See Creating a Custom Light Ring Color for more details.
Sets the green component of RGB value of light ring (0­255). See Creating a Custom Light Ring Color for more details.

Light Ring Blue

AV30s002

Sets the blue component of RGB value of light ring (0­255). See Creating a Custom Light Ring Color for more details.

Light Ring Brightness

AV30s004

Sets the overall brightness of the light ring (0­100%).

Light Ring Pattern

MV30s003

Sets the light ring pattern to one of 15 states defined by the Light Ring Patterns MIC. BV30s007 must be disabled for MV30s003 to work.
By default, the light patterns use the factory colors listed in the Light Ring Pattern States table below unless a custom color is defined by the RGB AVs (AV30s000, AV30s001, and AV30s002).

Light Ring Patterns MIC

MICx

Contains predefined light ring patterns used by the MV30s003 object. Available through the Database Creation tool or via download from the O3 Hub product page on George Support (O3 HubScaleObjects.zip).
See the Light Ring Pattern States table below for the complete list of light ring patterns.

12

O3 Hub Application Guide

Edition 1.0

Object Name Light Pattern Repeat Enable RGB Control
Enable Status Mode

Instance Numbers AV30s009
BV30s007
BV30s029

Setting Up the O3 Hub
Description
Sets how many times a light ring pattern should repeat. 0 indicates indefinite repeats until changed.
Sets the light ring to the custom color defined by AV30s000, AV30s001, and AV30s002. Overrides MV30s003 (light ring pattern).
When set to True/On, the light ring displays the hardware status of the major components of the O3 Hub. The light ring is divided into four quadrants, with each quadrant displaying the status of a specific component. Green indicates normal functioning, yellow indicates a component is disabled, and red indicates a failure or error.

© 2021 Delta Controls Inc.

For example, when the O3 Hub is powered on for the first time, it is normal to see green for all quadrants except the EnOcean quadrant. The EnOcean quadrant appears yellow because EnOcean is disabled by default. See the O3 Hub installation guide for more details.
13

Setting Up the O3 Hub

Light Ring Pattern States
This table lists the states defined by the Light Ring Patterns MIC object. These states are supplied to the MV30s003 object that issues a command to display a specific light ring pattern. The MIC object is part of the O3 HubScaleObjects.zip file available on the O3 Hub product page on George Support.

State Pattern Name Description

Suggested Factory

Use

Colors

1

Idle/Off

No ring pattern is displayed.

None

2

Swirl

Single spot of light spins around the ring once before the ring flashes twice. Ends with a prolonged flash that lasts for 2 seconds.

Blue

3

Fast Swirl

A faster version of the Swirl sequence.

Blue

4

Power On

Spins a single spot of light around the ring 3 times.

When the O3 Hub powers on.

Green

5

Occupancy

Triggered

Spins a single spot of light around the ring 3 times.

When

White

occupancy

is detected

in the room.

6

Request

Received

The ring flashes 3 times in a sequence that lasts for 2 seconds.

To confirm receipt of a room command.

Green

7

Heating Active The entire ring fades in and out.

When the Red room is heating.

8

Cooling Active The entire ring fades in and out.

When the room is cooling.

Blue

9

Request Not

The ring flashes 4 times followed by a

Understood

prolonged light flash that lasts for 2

seconds.

Yellow

10

Error Condition The entire ring flashes 8 times.

Red

11

Alarm Condition Flashes alternate between both halves of

Red

the ring, for a total of 16 flashes.

14

O3 Hub Application Guide

Edition 1.0

Setting Up the O3 Hub

State Pattern Name

12

Christmas

13

Awake

14

Power On

(Alternate)

15

Occupancy

Triggered

(Alternate)

Description

Suggested Factory

Use

Colors

The entire ring flashes and alternates between 2 colors. This sequence is repeated 8 times.

Red and Green

The entire ring lights up and stays lit while a spot of more intense light in the same color travels around the ring twice.

Blue

3 spots of light spin around once before the ring flashes twice. The entire ring then lights up and stays lit for 2 seconds.

When the O3 Hub powers on.

Violet, Blue and Yellow

3 spots of light spin around once, followed When

Violet

by a sequence where a light spot travels occupancy and Cyan

down each half of the ring to the point

is detected

where the 2 ring halves meet before

in the room.

moving back to their point of origin.

Object Instance Numbers for IR Blaster

The IR blaster feature is available in firmware 4.6 and later.

Using the following objects, you can set up the O3 Hub's IR blaster to transmit infrared signals to control room appliances. Remote control codes using Pronto hex format are saved in CSV objects as string values. See Configuring the IR Blaster for more details.

Object Name

Instance Number Description

Send IR Blaster Code

MV30s010

Sends an IR code from CSV30s011 to CSV30s022. When set to Idle/Off (state 1), no code is sent. Reverts to Idle/Off after a code is sent.

IR Transmitter MIC

MICx

Contains Pronto IR codes for the IR blaster. Available through the Database Creation tool or via download from the O3 Hub product page on George Support (O3 HubScaleObjects.zip).

© 2021 Delta Controls Inc.

15

Setting Up the O3 Hub
Object Name IR Repeat IR Code 1 IR Code 2 IR Code 3 IR Code 4 IR Code 5 IR Code 6 IR Code 7 IR Code 8 IR Code 9 IR Code 10 IR Code 11
16

Instance Number AV30s023 CSV30s011 CSV30s012 CSV30s013 CSV30s014 CSV30s015 CSV30s016 CSV30s017 CSV30s018 CSV30s019 CSV30s020 CSV30s021

Description
Sets how many times an IR code should be sent per transmission. By default, a code is sent once per transmission.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 2.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 3.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 4.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 5.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 6.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 7.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 8.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 9.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 10.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 11.
Data in this object is sent out through the IR blaster when MV30s010 is set to state 12.

O3 Hub Application Guide Edition 1.0

Setting Up the O3 Hub

Object Name IR Code 12

Instance Number CSV30s022

Description
Data in this object is sent out through the IR blaster when MV30s010 is set to state 13.

When programming the O3 Hub to transmit multiple infrared signals at the same time, allow a one second interval between signals to allow each signal to complete its transmission.

Object Instance Number for Termination Switch
The O3 Hub includes built-in network termination through a manual switch setting. The switch is factory set to no termination (OFF). To enable termination, move the switch from OFF to TERM.

Object Name

Instance Number

Description

CAN Termination Status

BV30s043

Read-only value that indicates whether termination is on or off.

Object Instance Numbers for Universal I/O (O3-HUB-02 models)

O3-HUB-02 models require firmware 4.11 or later.

Object Name 2xP universal I/O 1
2xP universal I/O 2

Instance Number
AI/BI/MI/AO/BO/MO 30s101
AI/BI/MI/AO/BO/MO 30s102

Description
Used to configure an O3-HUB-02. Universal I/O 1.
Used to configure an O3-HUB-02. Universal I/O 2.

© 2021 Delta Controls Inc.

17

Setting Up the O3 Hub
Calibrating the Temperature
The O3 Hub temperature reading needs to be calibrated to match a reference room temperature. After calibration, the accuracy of the hub's temperature sensor is ± 0.5 degrees when measured within a band ± 5 degrees from the calibrated temperature.

To calibrate the temperature: l In enteliWEB, enter a correction factor in the AI30s000 object's Calibration property (where "s" represents the hub's address switch setting). The correction factor is the difference between the reference temperature and the AI30s000 object's present temperature value. For example, if the reference temperature is 21°C and the AI30s000 temperature value is 22°C, the correction factor that should be recorded is -1°C.
Creating a Custom Light Ring Color
The light ring color represented by the RGB triplet does not exactly match the same RGB color displayed on computer monitors. When setting a custom light ring color, use the O3 Hub to preview the color.
To create a new light ring color and display it on the O3 Hub:

18

O3 Hub Application Guide

Edition 1.0

Setting Up the O3 Hub

1. Create the following AV objects to set the red, green and blue values of the custom color ("s" represents the O3 Hub's address switch setting).

Object Name

Instance Number

Description

Red value AV30s000

Sets the red value for the light ring RGB, 0 (Off) to 255 (max).

Green value AV30s001

Sets the green value for the light ring, 0 (Off) to 255 (max).

Blue value AV30s002

Sets the blue value for the light ring, 0 (Off) to 255 (max).

2. To display the new custom color, create object BV30s007. Set this object value to True or On. The light ring displays the color until you set the object value to False or Off.

In firmware 4.6 and later, you can also apply custom colors to light ring patterns.

Examples of light ring colors and their associated RGB triplets: green (0,255,0), white (84,84,84), blue (0,0,255), red (255,0,0).

Light Ring Display Command Prioritization
All commands interrupt other commands in progress, and are processed in the following priority: hub status display (highest priority) > Brightness AV > Custom RGB color BV > Light ring patterns (lowest priority). For example, if a command to play a ring pattern and a status request were sent together, both commands would be accepted without error but only the status is displayed on the light ring.

Loading Custom Sounds
O3 firmware version 4.9 and later supports loading custom audio files to the O3 Hub. The audio files are represented in BACnet as FIL objects. To load custom sounds to the hub:
1. Create up to 12 audio files with the following specifications: l File format: WAV l Bit resolution: 16 bit l Sampling rate: 16 kHz l Audio channel: Mono

© 2021 Delta Controls Inc.

19

Setting Up the O3 Hub
The total size of the audio files must not exceed 1.8 Mb. So, for example, you could create 12 short sounds (approximately 5 seconds each), a single long sound (approximately 1 minute), or some combination of short and medium-length sounds. 2. In enteliWEB, on the O3-DIN controller that controls the O3 Hub, create an FIL object for each audio file that you have created.
l To load the files to a specific hub, create FIL objects in the range 30s101 to 30s112 (where "s" represents the hub's address switch setting).
l To load the files to all the connected hubs, create FIL objects in the range 310101 to 310112.
If there are FIL objects created in the global range (310101­310112) and also FIL objects created in the range of a specific O3 Hub (30s101­30s112), the firmware driver will transmit the global files to all hubs except the hub with its own specific files. Global files cannot overwrite hub-specific files. If the files for a specific hub are invalid, the audio loading for that hub will end in error; it will not attempt to use any global files.
3. Open each FIL object and upload the audio file that you want to associate with that FIL. a. In the Configuration section, click Upload File. b. In the Load File to Object dialog, click Browse, navigate to the location of the file, select it, click Open, and then click OK. c. Click Save to save your changes.
If you would like to load custom sounds but you also want to keep using some of the stock sounds, reload the stock sounds you want using the same method as the custom sounds. The stock sound files can be downloaded from the O3 Hub product page on George Support. Every time new audio is loaded, the audio files are rewritten. Therefore, every time you do an audio load you must provide every file to be loaded, even if it already exists in memory.
4. If you are loading less than 12 sounds, modify the default Sound List MIC to match the number of sounds that you have loaded or, alternatively, create a new MIC. If you are modifying the default MIC, rename the sounds as needed and delete any states that are not used. For example, if you are loading 6 sounds, the MIC should only have 7 states (state 1 as Idle/Off and states 2 to 7 as sounds). FIL30s101 corresponds to state 2, FIL30s102 corresponds to state 3, and so on.
5. Reset the O3-DIN controller or, alternatively, command BV30s099 to On. If the FIL objects are valid, the audio files are transmitted to the hub and saved to its data flash. Depending on the size of the transfer, this can take up to 5 minutes. The light ring displays solid blue while the audio is loading.

20

O3 Hub Application Guide

Edition 1.0

Setting Up the O3 Hub
6. If one or more of the files are not in the proper format, or if the total size of the audio is larger than the 1.8 Mb of space reserved for audio, no transfer will take place. Only if all files are valid and can be contained within the data space of the O3 Hub will the O3-DIN controller update the hub(s).
7. To verify that the audio transfer was successful, create and/or open object CSV30s099 (read-only).
Once the audio transfer is complete, the files can be played back using MV30s006.
If the MV30s006 object is commanded to a non-existent sound file, all sounds will play consecutively in an infinite loop until the O3 Hub is power cycled. Make sure the audio MIC does not have any unused states.
Configuring the IR Blaster
The IR blaster feature is available in firmware 4.6 and later.
To set up the O3 Hub to transmit infrared remote control signals: 1. Obtain the remote control codes specific to your appliance brand and model in Pronto hex format. Remote control codes are available online on websites such as www.remotecentral.com/cgi-bin/codes. 2. Create the CSV object or objects with specific instances as listed in the Object Instance Numbers for IR Blaster table. You can create up to 12 CSV objects per O3 Hub. 3. In the CSV object, copy and paste the remote control code into the Default Value property field. Make sure your text editor tool does not introduce any extra characters or spaces in the code. 4. Create an MIC object to store the states associated with specific CSV objects in the exact order shown in the Object Instance Numbers for IR Blaster table. 5. Create object MV30s010 (where "s" represents the O3 Hub's address switch setting). To transmit a remote control signal, command the MV object value to the correct state.

© 2021 Delta Controls Inc.

21

Troubleshooting the O3 Hub
The IOM object page displays the working status of the O3 Hubs on the O3BUS network. In general, the status reflects the health of the connection between the O3 Hub and the O3-DIN controller. This topic describes three possible statuses and how to interpret them. If the O3 Hub is still powered, the light ring displays the hardware status until the issue is resolved.
The O3 Hub is offline
This could be due to one of the following reasons: l Faulty network or power wiring between the O3-DIN controller and the O3 Hub. l The NP object on the O3-DIN controller is set to a protocol type other than CANbus. l The O3 Hub has been assigned the same address as a O3-DIN-PWRINJ module on the O3BUS network. Both the O3 Hub and power injector module remain offline until the duplicate addressing is resolved. l You are using the switched PWR OUT 1 port on the O3-DIN-CPU controller to power the O3 Hub and the BO1 object set to OFF. Manually command BO1 to ON to turn on power to the hub.
The O3 Hub has an error state
This could be due to the NET3 port being disabled. Verify that the Out of Service box on the NP3 object is not selected.
The O3 Hub no longer appears on the IOM object page
This could be due to one of the following reasons: l The O3 Hub was offline before the O3-DIN controller was reset. When the controller comes back online after a reset, the O3 Hub no longer appears on the IOM object page. l The O3 Hub shares the same address as another sensor hub on the O3BUS network. Give each O3 Hub on the network a unique address. l You are using the switched PWR OUT 1 port on the O3-DIN-CPU controller to power the O3 Hub and the BO1 object set to OFF. Manually command BO1 to ON to turn on power to the hub.

22

O3 Hub Application Guide

Edition 1.0

O3 App
The O3 app is a room control application for mobile devices. The app communicates with the O3-DIN room controller and enteliWEB to execute a preset comfort setting in a room. These comfort settings are previously configured by the enteliWEB administrator to match what the occupants intend to do in the room, for example, a meeting or presentation.
The O3 app relies on the Bluetooth beacon in the O3 Hub for room location information, and therefore is designed to work only with rooms or spaces that have O3 Hub devices. enteliWEB determines the room permission level of each O3 app user on the site.

© 2021 Delta Controls Inc.

23

O3 App
The O3 app displays a list of rooms closest to the O3 app user. In general, the room with the strongest Bluetooth beacon signal appears at the top of this list.

For more information about O3 rooms, see O3 Room Concept.

24

O3 Hub Application Guide

Edition 1.0

O3 App
Each room or space is associated with one or more activities, each with their own preset comfort values. The O3 app user selects an activity option on the app to apply the new comfort values.

(1) Displays the current activity in use. Also displays the current values from the sensors in the room. (2) Other Activities: List the activities available for selection. (3) Control: Select Control to change the preset comfort values. (4) Use the menu icon to go back to the room list. For more information about O3 room activities, see O3 Room Activity Concept.

© 2021 Delta Controls Inc.

25

O3 App
The O3 app user can change the preset comfort values using the Control section of the app.

The control tiles display the comfort values of the selected activity. Each control is represented by an image that changes color and form to reflect its current comfort value. To change these comfort values, touch to open the control tile and tap or drag to adjust the setting.
Getting Started with the O3 App
Before you begin
l You must have enteliWEB version 4.8 or later installed, with the Web Services and Interface API license add-on activated. You can check the status of the add-on by going to > Configuration > Support.
l A wireless access point must be installed to allow Wi-Fi connections to enteliWEB.

26

O3 Hub Application Guide

Edition 1.0

O3 App
l The enteliWEB server must be set up for HTTPS connections, which requires installing an SSL certificate from a trusted certificate authority (Let's Encrypt is a popular free option). The O3 app will not connect to the server if a self-signed certificate is used. To obtain an SSL certificate, the server must have a DNS-resolvable hostname and access to the internet. Internal server names and IP addresses are not supported. For more information, see KBA 2037.
Install an O3-DIN controller
Install an O3-DIN-CPU device running firmware version 4.6 or later (or an O3-DIN-SRC device running firmware version 4.7 or later) on a BACnet network. For more information, refer to the O3-DIN-CPU Installation Guide.
Install and Set Up an O3 Hub
1. Install an O3 Hub and connect it to the O3-DIN controller. Connect the hub's O3BUS port to the controller's NET3 port and connect the hub's power to the controller's PWR OUT port. For more information, refer to the O3-HUB Installation Guide.
2. To enable the PWR OUT port on the O3-DIN controller, select the controller in enteliWEB, create object BO1, command it to ON, then click Save.
3. In the NP3 object, set Protocol Type to CANbus, set Command to Activate, then click Save. 4. Open the IOM1 object and verify that the O3 Hub is online. 5. Create the object database for the O3 Hub. You can create objects manually in enteliWEB
or you can auto-create them from an existing template using the Database Creation tool (in enteliWEB 4.12 and higher).
In the following object names, "s" is a placeholder for the O3 Hub's rotary switch position (2­9).
a. Create object BV30s026 and set it to On to enable the Bluetooth beacon on the hub. b. Create object CSV30s040 to hold the MAC address of the Bluetooth beacon on the hub
so that the O3 app can distinguish it from other beacons within range. c. Create object AI30s000 for the room temperature. d. Create object AI30s009 for the room humidity. e. Create AV and BV objects to hold room setpoints. f. Create other objects as needed (for occupancy, motion, LED light ring, speaker
settings, etc.). For a full list of BACnet objects for the hub, see Creating an Object Database. g. Download the scale range objects, load them into the controller database, and apply them to the inputs as needed. 6. Create GCL+ programs in enteliWEB for room control. These programs use the objects that you've created to execute control sequences.

© 2021 Delta Controls Inc.

27

O3 App
Create Rooms and Activities for the O3 App
1. Go to > Systems and Dashboards > Create O3 Room to create one or more rooms. For more information, see Creating O3 Rooms. A room must have at least one control set up (for temperature, lights, blinds, or fans) before it will appear in the rooms list in the O3 app.
2. Go to > Systems and Dashboards > Rooms > Create O3 Room Activity to create one or more room activities. For more information, see Creating O3 Room Activities.
Install and Log In to the O3 App
1. Download and install the O3 app to your mobile device. The app is available from Google Play or Apple's App Store.
2. Enable Bluetooth on your device. 3. Position yourself within range of the O3 Hub and the Wi-Fi network. 4. Open the O3 app and enter your enteliWEB server address and login credentials.
O3 Room Concept
What is an O3 Room?
We define an O3 room as an area of a building where occupant comfort is controlled by a Delta Controls O3-DIN controller and one or more O3 Hub sensor hubs and where the occupants use the Delta Controls O3 app to manage their comfort.
Components of an O3 Room

Devices

O3 Hub

O3-DIN-CPU or O3-DIN- Mobile device with O3

SRC

app

Sensors in room
Temperature at hub

Humidity at hub

CO2 on room wall

28

O3 Hub Application Guide

Edition 1.0

O3 App

Controls via O3 app

Temperature setpoint

Lights

Blinds

Fans

What is an O3 Room Activity?
See What is an O3 Room Activity?

What is an Occupant?
An occupant is a person who is in a room and can use the O3 app. An occupant with the proper permissions uses the O3 app to choose an activity for the room. The activity defines the comfort settings for the room. See Permissions below to understand what a principal occupant is.

Permissions
Each setpoint and other comfort setting for a room is assigned one of the following permission levels: principal occupant, everyone in room, no permission.

Principal Occupant
Principal Occupant permission allows the named user(s) to adjust the setpoint or other comfort setting for the room.
When the permissions for all setpoints and comfort settings for a room are set to Principal Occupant, then the room is displayed on the O3 app room list for the room's principal occupant users only.
A principal occupant can be either an enteliWEB user or an O3 app user.

Everyone in Room
Everyone in Room permission allows any enteliWEB user or O3 app user to adjust the setpoint or other comfort setting for the room. The room is displayed on the O3 app room list for all occupants.

No Permission
No Permission does not allow any enteliWEB user or O3 app user to adjust the setpoint or other comfort setting for the room. When the permission for all room comfort settings is set to No Permission, then the room is not displayed on the O3 app room list for any occupant.

© 2021 Delta Controls Inc.

29

O3 App
Room and O3 App
The O3 app displays a room on its room list when all of the following rules are true:
l The app user is a member of the O3 Room Guests group or another group with the same object, service, and device permissions.
l The room has at least one of the following controls configured: temperature, lights, blinds, or fans.
l The control permissions are set to Everyone in Room or Principal Occupant. If the permission is set to Principal Occupant, the app user must be designated as a principal occupant or belong to a group that is designated as a principal occupant.
The O3 Room page does not support the nameFormat feature in config.xml.
Creating O3 Rooms
An O3 room is an area of a building where occupant comfort is controlled by an O3-DIN controller and one or more O3 Hub sensor hubs and is managed through the O3 app.
O3 rooms are created on the Create O3 Room page ( > Systems and Dashboards > Create O3 Room).
To create a room:
1. Enter the Room Name (for example, "Conference Room"). 2. Optional: Select a Room Photo to identify the room in the app. 3. Optional: Enter a Description for the room. The description is not visible to the app user. 4. In the O3 Sensor Hubs area, do the following:
a. Click Add to add a new row. b. In the Device Reference field, start typing the name of the O3-DIN controller that
controls the O3 Hub. Select the controller from the list of results. c. Ensure that the Hub Address is correct. By default, the value is set to 2. To edit the
address, double-click in the Hub Address field to make it active, then select a new address from the list. d. The hub address is displayed in the IOM object (IOM1) of the controller. The hub address is the third digit from the left in the hub's IOM address. For example, 302000 indicates a hub address of 2, 303000 indicates a hub address of 3, 304000 indicates a hub address of 4, and so on. 5. In the Room Controls area, do the following: a. On the Sensors tab:
i. In the Temperature Reference field, enter the AI object that holds the temperature of the room (AI30s000, where s is the hub address).
ii. In the CO2 Reference field, enter the object that holds the CO2 level of the room (this reading is not provided by the O3 Hub; a separate CO2 wall sensor must be installed).

30

O3 Hub Application Guide

Edition 1.0

O3 App
iii. In the Humidity Reference field, enter the AI object that holds the humidity level of the room (AI30s009, where s is the hub address).
b. On the Temperature tab: i. Set Allow Control by to Everyone in Room (recommended), Principal Occupant (see step 8), or No Permission (no one in the room is allowed to adjust the temperature). ii. Set the Setpoint Type to Absolute or Offset. Absolute means that an O3 app user selects the setpoint temperature within a range set by Minimum Value and Maximum Value. Offset means an O3 app user selects an offset as an increase or decrease to the base setpoint temperature. l If Absolute is selected, configure the following settings: Setpoint Reference, Minimum Value Type, Minimum Value, Maximum Value Type, Maximum Value. l If Offset is selected, configure the following settings: Offset Adjustment Type, Offset Adjustment (+/-), Base Setpoint Reference, User Offset Setpoint.
c. On the Lights tab: i. Set Allow Control by to Everyone in Room (recommended), Principal Occupant (see step 8), or No Permission (no one in the room is allowed to adjust the lights). ii. Click Add to add a new row.
iii. Enter a Name for the light(s) (for example, "Front Lights"). This is the name that the app user sees.
iv. Set the Control Type to Dimmer, On/Off, or Dimmer - On/Off. l If Dimmer is selected, configure the following setting: Dimmer Reference. l If On/Off is selected, configure the following settings: Lights On Reference, Lights Off Reference, State Reference. l If Dimmer - On/Off is selected, configure the following settings: Dimmer Reference, Lights On Reference, Lights Off Reference, State Reference.
v. Write a GCL+ program to allow the O3 app to control the lights using the objects from the previous step. For example:
// On/Off light switch controlled by O3 app
IfOnce ('ON/OFF - ON' = 'On') Then 'ON/OFF - StateRef' = 'On' 'ON/OFF - ON' = 'Off' EndIf
IfOnce ('ON/OFF - OFF' = 'On') Then 'ON/OFF - StateRef' = 'Off' 'ON/OFF - OFF' = 'Off'

© 2021 Delta Controls Inc.

31

O3 App
EndIf
In this example, 'ON/OFF - ON' is the Lights On Reference BV object, 'ON/OFF OFF' is the Lights Off Reference BV object, and 'ON/OFF - StateRef' is the State Reference BV object.
vi. Optional: Enter an internal Key Name for the light(s) that can be applied to similar lights in other rooms (for example, "Main Lights" or "Perimeter Lights"). This allows activities to control these devices in a consistent way across multiple rooms.
vii. Add additional lights as needed. d. On the Blinds tab:
i. Set Allow Control by to Everyone in Room (recommended), Principal Occupant (see step 8), or No Permission (no one in the room is allowed to adjust the blinds).
i. Click Add to add a new row. ii. Enter a Name for the blinds (for example, "West Window"). This is the name that
the app user sees. iii. In the Position Reference field, enter the AV object that holds the vertical
position of the blinds. iv. In the Angle Reference field, enter the AV object that holds the angle of the
blinds. v. Optional: Enter an internal Key Name for the blinds that can be applied to similar
blinds in other rooms. This allows activities to control these devices in a consistent way across multiple rooms. vi. Add additional blinds as needed. e. On the Fans tab: i. Set Allow Control by to Everyone in Room (recommended), Principal Occupant (see step 8), or No Permission (no one in the room is allowed to adjust the fans). ii. Click Add to add a new row. iii. Enter a Name for the fans (for example, "Ventilation"). This is the name that the app user sees. iv. In the Fan Reference field, enter the MV object that holds the fan state. v. Optional: Enter an internal Key Name for the fans that can be applied to similar fans in other rooms. This allows activities to control these devices in a consistent way across multiple rooms. vi. Add additional fans as needed.

32

O3 Hub Application Guide

Edition 1.0

O3 App

For a room to appear in the rooms list in the O3 app, it must have at least one of the following controls configured: temperature, lights, blinds, or fans.

6. The Activities area shows any room activities that have been created. To associate an activity with the room, select the Enabled check box. To create a new activity, see Creating O3 Room Activities.
7. In the Principal Occupant area, you can designate specific users and/or groups as the principal room occupant. When room controls permissions are set to Principal Occupant, only these users and groups will be able to view and manage the room comfort settings in the app.
a. To add users to the Principal Occupant list, on the Users tab, click Add, select the users that you want to add, then click OK. To create new users, see Creating a User help topic.
b. To add groups to the Principal Occupant list, on the Groups tab, click Add, select the groups that you want to add, then click OK. To create new groups, see Creating a Group help topic.
8. Click Create . The room is added to the O3 Rooms list.

Managing O3 Rooms
An O3 room is an area of a building where occupant comfort is controlled by an O3-DIN controller and one or more O3 Hub sensor hubs and is managed through the O3 app.
O3 rooms are managed on the O3 Rooms page ( > Systems and Dashboards > Rooms), which lists rooms for all sites known to enteliWEB.

Searching the Rooms List To search the rooms list, start typing a room name in the Search Room field. The list is filtered as you type. To see everything in the rooms list, clear the Search Room field.

Sorting the Rooms List To sort the rooms list, click the column heading that you want to sort by.

Opening an Existing Room To open a room, click its name.

Adding a Room
To add a new room, click Rooms.

Add. The Create O3 Room page opens. For details, see Creating O3

© 2021 Delta Controls Inc.

33

O3 App
Copying a Room to a Single Controller
When a room is copied, its configuration--its specific objects and instances--is replicated in the copy. The object database is not copied. The copy process assumes that an identical object database exists in the destination device.
1. From the rooms list, select the room that you want to copy. 2. Click Copy . The Copy Room dialog opens. 3. Edit the Room Name as needed. Each room name must be unique. 4. Optional: If you want to copy the room to a different controller, double-click in the
Destination Device field to make it active, then start typing the name of the destination O3DIN controller. Select the controller from the list of results. 5. Optional: Edit the Destination Hub Address if needed. If you are copying to the same device, the hub address must be different. To edit the address, double-click in the Destination Hub Address field to make it active, then select a new address from the list. 6. Click Copy. The room list is updated to include the copied room.
Copying a Room to Multiple Controllers
When a room is copied, its configuration--its specific objects and instances--is replicated in the copy. The object database is not copied. The copy process assumes that an identical object database exists in the destination device.
1. From the rooms list, select the room that you want to copy. 2. Click Copy to Many . The Copy Room dialog opens. 3. In the Destination area, configure the Site, Device Range, Device Increment, and Hub
Address. 4. Click Generate . The Generated Rooms list is updated with the copied rooms.
Deleting a Room 1. From the rooms list, select the room or rooms that you want to delete. 2. Click Delete. A confirmation dialog opens. 3. Click Yes to delete the rooms.

34

O3 Hub Application Guide

Edition 1.0

O3 App
O3 Room Configuration Reference
Configuration
Room Name Room Name specifies the name used in enteliWEB and in the O3 app for this room.
Room Photo Room Photo specifies the image displayed for this room in the O3 app.
Description Description contains a brief description of the room to help you identify it. This description is not visible to O3 app users.
O3 Sensor Hubs
Device Reference Device Reference specifies the O3-DIN controller that is controlling the room.
Hub Address Hub Address specifies the address of the O3 Hub in the room in the range 2 through 9. The hub address is set by a rotary dial on the hub. The factory default setting is 2. The hub's current address setting can be confirmed by opening the O3-DIN controller's IOM object (IOM1). The hub address is the third digit from the left in the O3 Hub's IOM address in the Hardware Devices table. For example, 302000 indicates a hub address of 2, 303000 indicates a hub address of 3, 304000 indicates a hub address of 4, and so on.
Room Controls
Sensors
Temperature Reference
Temperature Reference specifies the AI object of the O3 Hub that holds the composite temperature value for the room (AI30s000). For details, see Object Instance Numbers for Input Sensors.
CO2 Reference
CO2 Reference specifies an AI or AV object reference for the CO2 sensor. The O3-HUB does not include a CO2 sensor. A wall-mounted CO2 sensor must be used.

© 2021 Delta Controls Inc.

35

O3 App
Humidity Reference
Humidity Reference specifies the AI object of the O3 Hub that holds the relative humidity value for the room (AI30s009). For details, see Object Instance Numbers for Input Sensors.
Temperature
Allow Control by
Allow Control by specifies which O3 app users are allowed to adjust the temperature setpoint for the room. Everyone in Room, Principal Occupant, No Permission
Setpoint Type
Setpoint Type specifies how the O3 app user is allowed to adjust the temperature setpoint for the room.
l Absolute means that an O3 app user selects the setpoint temperature within a range set by Minimum Value and Maximum Value.
l Offset means an O3 app user selects an offset as an increase or decrease to the base setpoint temperature.
Setpoint Type affects the Setpoint Value setting for activities that you assign to the room.
Minimum Value Type
When Setpoint Type is set to Absolute, Minimum Value Type specifies how Minimum Value is specified.
l Absolute means that Minimum Value specifies a temperature value. l Object Reference means that Minimum Value specifies an object reference for the AV
object that holds a temperature value.
Maximum Value Type
When Setpoint Type is set to Absolute, Maximum Value Type specifies how Maximum Value is specified.
l Absolute means that Maximum Value specifies a temperature value. l Object Reference means that Maximum Value specifies an object reference for the
AV object that holds a temperature value.
Setpoint Reference
When Setpoint Type is set to Absolute, Setpoint Reference specifies an object reference for the AV object that holds the desired setpoint that is requested by an O3 app user. The O3 app updates this object when the user adjusts the desired temperature.

36

O3 Hub Application Guide

Edition 1.0

O3 App
Minimum Value
When Setpoint Type is set to Absolute, Minimum Value specifies the lowest temperature that an O3 app user can request. Setpoint Reference holds the requested temperature value. The Minimum Value Type setting determines how Minimum Value is specified.
Maximum Value
When Setpoint Type is set to Absolute, Maximum Value specifies the highest temperature value that an O3 app user can request. Setpoint Reference holds the requested temperature value. The Maximum Value Type setting determines how Maximum Value is specified.
Offset Adjustment Type
When Setpoint Type is set to Offset, Offset Adjustment Type specifies how Offset Adjustment(+/-) specifies the maximum offset.
l Absolute means that Offset Adjustment (+/-) specifies an offset value. l Object Reference means that Offset Adjustment (+/-) specifies an object reference for the
AV object that holds an offset value.
Offset Adjustment (+/-)
When Setpoint Type is set to Offset, Offset Adjustment (+/-) specifies the maximum temperature offset that an O3 app user can request. The O3 app limits a user to adjust the room temperature to this range. Setting Offset Adjustment (+/-) to zero is not recommended; the temperature control in the O3 app may not be able to function properly. The offset that is requested by an O3 app user is held in the object specified by User Offset Setpoint.
Base Setpoint Reference
When Setpoint Type is set to Offset, Base Setpoint Reference specifies an object reference for the AV object that holds the temperature setpoint to which the offset is applied. The temperature setpoint held in the AV object is set by a GCL+ program. The temperature setpoint is not changed by enteliWEB. A GCL+ program adds the offset requested by the O3 app user to the temperature setpoint to calculate the desired temperature setpoint for the room.
User Offset Setpoint
When Setpoint Type is set to Offset, User Offset Setpoint specifies an object reference for the AV object that holds the desired offset that is requested by an O3 app user. That is, the O3 app updates enteliWEB with the desired offset and enteliWEB writes the value to User Offset Setpoint on the O3-DIN controller.

© 2021 Delta Controls Inc.

37

O3 App
Lights
Allow Control by
Allow Control by specifies which O3 app users are allowed to adjust the lights. Everyone in Room, Principal Occupant, No Permission
Name
Name specifies a unique name for the lights. This name is visible to O3 app users.
Key Name
Key Name is optional and can be left blank. It is not visible to O3 app users. The key name specifies an internal name for the lights that allows them to be controlled independently of other lights in an activity. If no key names are specified, all lights in a room will be controlled together. Also, when an activity is applied to multiple rooms, key names can be used to control similar devices the same way in each room. For example, suppose you want a Presentation activity that turns off a meeting room's main fluorescent lights and dims a set of downlights. You would assign a key name to the fluorescent lights (such as "Main Lights") and another key name to the downlights (such as "Perimeter Lights"). The Presentation activity will then be able to separately turn off the fluorescent lights and dim the downlights. Now, suppose you want to apply the activity to other meeting rooms. The downlights in each room might have different names specific to each space--they might be called "Front Lights" in one room and "Side Lights" in another. Give both sets of lights a consistent key name, such as "Perimeter Lights." This will allow the activity to control the downlights the same way in both rooms.
Control Type
Control Type specifies how the O3 app allows a user to control the lights. l Dimmer means the O3 app presents a dimmer to allows a user to control the lights. l On/Off means the O3 app presents an on/off switch to allows a user to control the lights. l Dimmer - On/Off means the O3 app presents both a dimmer and an on/off switch to allows a user to control the lights.
Dimmer Reference
When Control Type is set to Dimmer or to Dimmer - On/Off , Dimmer Reference specifies an object reference for the AV object that holds the dimmer setting.
Lights On Reference
When Control Type is set to On/Off or to Dimmer - On/Off , Lights On Reference specifies an object reference for the BV object that causes the lights to be turned on.

38

O3 Hub Application Guide

Edition 1.0

O3 App
By design, Lights On Reference is always Off except momentarily when the lights are turned on. For the current state of the lights, see State Reference.
The BV object used for Lights On Reference should be different from the one used for Lights Off Reference.
Lights Off Reference
When Control Type is set to On/Off or to Dimmer - On/Off , Lights Off Reference specifies an object reference for the BV object that causes the lights to be turned off. By design, Lights Off Reference is always Off except momentarily when the lights are turned off. For the current state of the lights, see State Reference.
The BV object used for Lights Off Reference should be different from the one used for Lights On Reference.
State Reference
When Control Type is set to On/Off or to Dimmer - On/Off , State Reference specifies an object reference for the BV object that holds the current state, On or Off, of the lights.
The BV object used for State Reference should be different from the ones used for Lights On Reference and Lights Off Reference.
For an on/off light switch, the Lights On Reference and Lights Off Reference BV objects are always Off except momentarily when the lights are turned on or off. State Reference remembers the lights on and off events to allow the O3 app to display the current state of the lights.
Blinds
Allow Control by
Allow Control by specifies the permission required for an O3 app user to adjust the blinds. Everyone in Room, Principal Occupant, No Permission
Name
Name specifies a unique name for the blinds. This name is visible to O3 app users.
Key Name
Key Name is optional and can be left blank. It is not visible to O3 app users.

© 2021 Delta Controls Inc.

39

O3 App
The key name specifies an internal name for the blinds that allows them to be controlled independently of other blinds in an activity. If no key names are specified, all blinds in a room will be controlled together. Also, when an activity is applied to multiple rooms, key names can be used to control similar devices the same way in each room.
Position Reference
Position Reference specifies an object reference for the AV object that holds the position of the blinds.
Angle Reference
Angle Reference specifies an object reference for the AV object that holds the angle of the blinds.
Fans
Allow Control by
Allow Control by specifies which O3 app users are allowed to adjust the fans. Everyone in Room, Principal Occupant, No Permission
Name
Name specifies a unique name for the fan settings. This name is visible to O3 app users.
Key Name
Key Name is optional and can be left blank. It is not visible to O3 app users. The key name specifies an internal name for the fan setting that allows it to be controlled independently of other fan settings in an activity. If no key names are specified, all fans in a room will be controlled together. Also, when an activity is applied to multiple rooms, key names can be used to control similar devices the same way in each room.
Fan Reference
Fan Reference specifies an object reference for the MV object that holds the fan state.
Activities
Activity Name Activity Name lists the names of activities known to enteliWEB.
Enabled When Enabled is selected, the corresponding activity is allowed in the room. When Enabled is not selected, the corresponding activity is not allowed in the room.

40

O3 Hub Application Guide

Edition 1.0

O3 App
Principal Occupant
Users Users lists the user names of users who are principal occupants of the room.
Groups Groups lists the group names of groups whose members are principal occupants of the room.
O3 Room Activity Concept
What is an O3 Room Activity?
An O3 room activity consists of a collection of comfort settings for an O3 room based on what the occupants will be doing in the room: attending a meeting, attending a presentation, doing desk work, etc. You can create multiple activities and associate an activity with multiple rooms. An activity must include one or more of the following controls (depending on the options available in the O3-DIN controller and the O3 Hub sensor hub).
l Temperature setpoint l Lights l Blinds l Fans
Activities and the O3 App
Using Delta Controls' O3 app, a room occupant with the proper permissions can choose an activity for the room. When the occupant chooses an activity, the app sends a request to enteliWEB and the activity's definition is written to corresponding BACnet objects in the O3-DIN controller that controls the room. The control sequence (implemented in GCL+ in the controller) adjusts the room's comfort settings accordingly. When the occupant adjusts a setpoint, such as raising or lowering the room temperature, the app sends the change to enteliWEB and enteliWEB writes the change to the appropriate BACnet object in the controller. The control sequence (implemented in GCL+ in the controller) adjusts the room's temperature setting accordingly.
When an O3 app user selects an activity, all activity values are applied regardless of the permission that the user has on each control.

© 2021 Delta Controls Inc.

41

O3 App
Creating O3 Room Activities
An O3 room activity is a collection of comfort settings for an O3 room based around one or more setpoints (temperature, lights, blinds, etc.). An activity can be applied to multiple rooms.
O3 room activities are created on the Create O3 Room Activity page ( > Systems and Dashboards > Rooms > Create O3 Room Activity).
To create an activity:
1. Enter the Activity Name (for example, "Presentation"). This name identifies the activity in enteliWEB. If Activity Label in App is left blank, it is also the name that is displayed in the app.
2. Optional: Enter the Activity Label in App (if you want it to be different from the Activity Name).
3. Select a Color to identify the activity in the app. 4. Optional: Enter a Description for the activity. The description is not visible to the app user. 5. In the Activity Controls area:
a. On the Temperature tab, enter the Setpoint Value for the activity. This value is determined by the Setpoint Type (Absolute or Offset) of the O3 room in which the activity takes place.
b. On the Lights tab, click Add, enter the desired light level for the activity in the Dimmer field, then select the default On/Off setting (Lights On, Lights Off, Not In Use). If applicable, enter its Key Name.
c. On the Blinds tab, click Add, enter the desired blind position for the activity in the Position field (0% is fully retracted; 100% is fully deployed), then enter the desired blind angle for the activity in the Angle field (0° means slats pointed down; 90° means slats are horizontal; and 180° means slats point up). If applicable, enter its Key Name.
d. On the Fans tab, click Add, then select the desired fan state for the activity from the Fans list. This list of allowable fan states is determined by the fan's MIC object. If applicable, enter its Key Name.
6. In the Rooms area, associate one or more rooms with the activity. Click Add, select a room from the list, then click OK. If the list is blank, then no rooms have been created yet. To create new rooms, see Creating O3 Rooms.
7. Click Create. The activity is added to the O3 Room Activities list.
Managing O3 Room Activities
An O3 room activity is a collection of comfort settings for an O3 room based around one or more setpoints (temperature, lights, blinds, etc.). An activity can be applied to multiple rooms.
O3room activities are managed on the O3 Room Activities page ( > Systems and Dashboards > Rooms > O3 Room Activities), which lists room activities for all sites known to enteliWEB.

42

O3 Hub Application Guide

Edition 1.0

O3 App

Searching the Room Activities List To search the room activities list, start typing a room activity name in the Search Room Activity field. The list is filtered as you type. To see everything in the room activities list, clear the Search Room Activity field.

Sorting the Room Activities List To sort the room activities list, click the column heading that you want to sort by.

Opening an Existing Room Activity To open a room activity, click its name.

Adding a Room Activity
To add a new room activity, click see Creating O3 Room Activities.

Add. The Create O3 Room Activity page opens. For details,

Copying a Room Activity
1. From the room activities list, select the activity that you want to copy. 2. Click Copy . The Copy Room Activity dialog opens. 3. Edit the Activity Name as needed. Each activity name must be unique. 4. If you don't want to keep the associated rooms with the new activity, clear the Copy Room
Mapping checkbox. 5. Click Copy. The room activity list is updated to include the copied activity.

Setting the Units for Room Activities

Changes to the room activity unit settings apply to all room activities.

1. Click Settings. The Activity Unit Settings dialog opens. 2. To set the temperature unit, select °C or °F from the Temperature list. 3. To set the fan unit, in the Fan field, enter the MIC object that holds the list of allowed fan
states. The MIC object must be from version 4 firmware. 4. To set the blind angle unit, select % or ° from the Blind Angle list. 5. Click Save to apply the settings.
Deleting a Room Activity 1. From the room activities list, select the activity or activities that you want to delete. 2. Click Delete. A confirmation dialog opens. 3. Click Yes to delete the activities.

© 2021 Delta Controls Inc.

43

O3 App
O3 Room Activity Configuration Reference
Configuration
Activity Name Activity Name specifies the name used in enteliWEB for this activity. When Activity Label in App is blank, then Activity Name is displayed in the O3 app.
Activity Label in App Activity Label in App specifies the name used in the O3 app for this activity. When Activity Label in App is blank, then Activity Name is displayed in the O3 app.
Color Color specifies the color that you want to associate with the activity to help users identify it in the O3 app.
Description Description contains a brief description of the activity to help you identify it. The description is not visible to O3 app users.
Activity Controls
Temperature
Setpoint Value
The setpoint value is determined by the setpoint type (absolute or offset) that has been configured for the room in which the activity takes place.
Setpoint Type = Absolute
When the setpoint type is absolute, the setpoint value specifies the temperature setpoint for the room when the activity is selected by an O3 app user (for example, 19°C). The setpoint value must be in the range for the absolute temperature configured for the room by the Minimum Value and Maximum Value settings. The temperature setpoint is written to the object specified by the Setpoint Reference.
Setpoint Type = Offset
When the setpoint type is offset, the setpoint value specifies the temperature offset for the room that is applied when the activity is selected by an O3 app user (for example, -1 or +2). The setpoint value must be in the range for the offset that is configured for the room by the Offset Adjustment (+/-) setting. The offset is applied to the value held by the Base Setpoint Reference.

44

O3 Hub Application Guide

Edition 1.0

O3 App
Lights
Key Name
Key Name is optional and can be left blank. It is not visible to O3 app users. The key name specifies an internal name for the lights that allows them to be controlled independently of other lights in an activity. If no key names are specified, all lights in a room will be controlled together. When an activity is applied to multiple rooms, key names can be used to control similar devices the same way in each room.
Dimmer
Dimmer specifies the desired light level (as a percentage) when this activity is selected by an O3 app user.
On/Off
On/Off specifies whether the room lights are on or off by default, when this activity is selected by an O3 app user.
l Lights On specifies that the lights are on. l Lights Off specifies that the lights are off. l Not In Use specifies that the activity does not include light control.
Blinds
Key Name
Key Name is optional and can be left blank. It is not visible to O3 app users. The key name specifies an internal name for the blinds that allows them to be controlled independently of other blinds in an activity. If no key names are specified, all blinds in a room will be controlled together. When an activity is applied to multiple rooms, key names can be used to control similar devices the same way in each room.
Position
Position specifies the desired height of the blinds when this activity is selected by an O3 app user.
l 0% specifies that the blinds are fully retracted or rolled up. l 100% specifies that the blinds are fully deployed or rolled down.
Angle
Angle specifies the desired angle of the slats when this activity is selected by an O3 app user. l 0° specifies that the blinds are fully closed with the slats pointing down. l 90° specifies that the blinds are fully open with the slats horizontal. l 180° specifies that the blinds are fully closed with the slats pointing up.

© 2021 Delta Controls Inc.

45

O3 App
Fans
Key Name
Key Name is optional and can be left blank. It is not visible to O3 app users. The key name specifies an internal name for the fan setting that allows it to be controlled independently of other fan settings in an activity. If no key names are specified, all fans in a room will be controlled together. When an activity is applied to multiple rooms, key names can be used to control similar devices the same way in each room.
Fans
Fans specifies the state of the fan operation. The list of allowed states is taken from the MIC object specified for Fan in the Activity Unit Settings dialog on the O3 Room Activities page. See Selecting the Units for Room Activities.
Deploying the O3 App for Building Occupants
The O3 app allows occupants with the proper permissions to control the comfort settings of a room by interacting with enteliWEB, an O3-DIN controller, and an O3 Hub sensor hub. To use the O3 app, occupants must log in with either an enteliWEB account or a Google Account (Gmail address). Both login methods are valid on Android and iOS mobile devices.
Users with a Google Account
When a user logs in to the O3 app for the first time with a Google Account, enteliWEB creates a guest account for the user and assigns them to the O3 Room Guests group--provided the automatic guest user creation function is enabled. To enable this function, go to > Configuration > Global Settings and select the Enable Automatic Creation of Guest User Account checkbox. The O3 Room Guests group is created automatically in enteliWEB and includes the necessary object, service, and device permissions to use the O3 app. To view or edit the group's settings, go to > Sites and Users > Groups and click O3 Room Guests. As long as the O3 room control permissions are set to Everyone in Room, users with Google Accounts should be able to see rooms and control setpoints and comfort settings when they log in to the app.
Users with an enteliWEB Account
Users with non-administrator enteliWEB accounts can log in to the O3 app with their enteliWEB account credentials but they will not be able to see rooms and control setpoints and comfort settings unless they are assigned to the O3 Room Guests group or to another group with the same object, service, and device permissions. To add an enteliWEB user to the O3 Room Guests group:

46

O3 Hub Application Guide

Edition 1.0

O3 App
1. Go to > Sites and Users > Groups and click O3 Room Guests. 2. In the Members area, click Edit. The Edit Membership dialog opens and lists the
usernames of all users. 3. In the Search field, enter the username of the user you want to add and press Enter. The
username is shown in the list of users. 4. Select the user and click Save. To create a group based on the O3 Room Guests group:
1. Go to > Sites and Users > Groups and click O3 Room Guests. 2. Scroll to the bottom of the page and click Copy Group. The Copy Group dialog opens. 3. Enter a new name for the group and click Create. The new group will have the same
permissions as the O3 Room Guests group. 4. Configure other settings for the group as needed. 5. Add members to the group. As long as the O3 room control permissions are set to Everyone in Room, users with enteliWEB accounts that are members of the O3 Room Guests group (or another group with the same permissions as the O3 Room Guests group) should be able to see rooms and control setpoints and comfort settings when they log in to the app.

© 2021 Delta Controls Inc.

47

Document Revision History

Edition 1.0

Date

Change Description

April 2021 New document based on O3-HUB Application Guide, edition 2.1.

48

O3 Hub Application Guide

Edition 1.0

www.deltacontrols.com

