SD1010CNB
jmondor
WaterFurnace
Submittal Data
Versatec 300 & 500 Consoles | WaterFurnace
Not Your Device? Search For Manuals or Datasheets below:
File Info : application/pdf, 32 Pages, 2.90MB
Document DEVICE REPORTsd1010cnbConsole FORMERLY ENVISION CONSOLE R-410A Refrigerant 0.75-1.5 Tons Submittal Data English Language/IP Units SD1010CNB 01/22 Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Model Nomenclature 1-2 3 4-5 6 7 8 9 10 11 12 13 14 15-16 17 NC S 09 L 0 1 1 C N N B 5 SS G Model NC Envision Series Console Cabinet Configuration C Chassis Only W Chassis with Cabinet S Chassis Slope Top E Chassis with Extended Slope Top Unit Capacity 09, 12, 15, 18 Piping Option L Left R Right Voltage 0 208-230/60/1 2 265/60/1 9 115/60/1 (09 & 12) Unit Control 1 CCM A AuroraTM Base Control (ABC) E AuroraTM DDC UPC Controller F AuroraTM DDC UPC Controller with LON NOTES: Chassis only available with left piping option. UPC option is only available with remote wall-mounted thermostat control. Vintage C ECM Blower & Aluminum Air Coil G Control Options "E" & "F" Non-Standard Option Details SS Standard Option Air Coil/Insulation Option 5 AlumiSealTM/Extended Range 6 AlumiSealTM/Standard Range 7 No Coating/Extended Range 8 No Coating/Standard Range Sound Kit A None B Blanket Auxiliary Electric Heat N None B 1.0kW (09-12) C 2.0kW (09-12) D 3.0kW (15-18) Motorized Outside Air Damper (Field Installed) N None M Motorized Damper Water Coil Option C Copper N CuproNickel Thermostat Control 1 Unit Mounted T-Stat 2 Remote Wall-Mounted T-Stat Voltage Availability Voltage 09 115/60/1 · 208-230/60/1 · 265/60/1 · Model 12 15 · · · · · 18 · · 1/20/14 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 1 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz ARI/ISO 13256-1 Performance Ratings ECM Motors AHRI/ASHRAE/ISO 13256-1 English (IP) Units Model Flow Rate Water Loop Heat Pump Cooling EWT 86°F Heating EWT 68°F gpm cfm Capacity EER Capacity Btuh Btuh/W Btuh COP 09 2.5 300 8,500 13.4 10,500 4.4 12 3.5 350 10,500 12.3 14,400 4.3 15 4.5 450 13,500 13.6 17,000 4.9 18 5.5 500 16,200 12.5 21,000 4.4 Ground Water Heat Pump Cooling EWT 59°F Heating EWT 50°F Capacity EER Capacity Btuh Btuh/W Btuh COP 10,200 22.5 8,700 3.8 12,400 19.5 11,800 3.7 16,200 22.0 14,000 4.1 19,000 19.6 17,000 3.7 Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Heating capacities based upon 68°F DB, 59°F WB entering air temperature All ratings based upon operation at the lower voltage of dual voltage rated models. Ground Loop Heat Pump Cooling EWT 77°F Heating EWT 32°F Capacity EER Capacity Btuh Btuh/W Btuh COP 9,000 16.0 6,700 3.1 11,000 14.2 9,500 3.5 14,200 15.9 10,500 3.4 16,600 15.1 13,300 3.1 12/14/09 All Envision Series product is Safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1. WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 2 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Blower Performance Data ECM Motors Model 09 12 15 18 Low Speed 300 300 350 350 CFM Medium Speed 325 325 450 450 High Speed 400 400 600 600 Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg. WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 3 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Electrical Data ECM Motor Model Rated Voltage 115/60/1 09 208-230/60/1 265/60/1 115/60/1 12 208-230/60/1 265/60/1 208-230/60/1 15 265/60/1 208-230/60/1 18 265/60/1 HACR circuit breaker in USA only Voltage Min/Max 104/127 187/253 238/292 104/127 187/253 238/292 187/253 238/292 187/253 238/292 Compressor MCC RLA LRA 12.5 8.0 50.0 6.4 4.1 21.0 6.7 4.3 22.0 14.8 9.5 50.0 7.7 4.9 25.0 7.0 4.5 22.0 9.2 5.9 29.0 7.8 5.0 28.0 10.4 6.7 33.5 8.7 5.6 28.0 Fan Motor FLA 4.25 2.6 2.5 4.25 2.6 2.5 2.6 2.5 2.6 2.5 Total Unit FLA 12.3 6.7 6.8 13.8 7.5 7.0 8.5 7.5 9.3 8.1 Min Circ Amp 14.3 7.7 7.9 16.1 8.8 8.1 10.0 8.8 10.9 9.5 Max Fuse/ HACR 20 10/15 10/15 25 10/15 10/15 15 10/15 15 15 1/20/14 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 4 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Auxiliary Heat Ratings ECM Motors Model Rated Voltage Voltage Min./Max. Heater Element Watts Fan Motor FLA 09-12 (1 kW) 09-12 (2 kW) 15-18 (3 kW) 208/60/1 230/60/1 265/60/1 208/60/1 230/60/1 265/60/1 208/60/1 230/60/1 265/60/1 197/254 197/254 239/291 197/254 197/254 239/292 197/254 197/254 239/292 818 1000 1000 1636 2000 2000 2454 3000 3000 2.45 2.60 2.50 2.45 2.60 2.50 2.45 2.60 2.50 Always refer to unit nameplate data prior to installation. Heater Element FLA 3.93 4.35 3.77 7.86 8.70 7.55 11.80 13.04 11.32 Total Unit FLA 6.4 7.0 6.3 10.3 11.3 10.1 14.3 15.6 13.8 Min. Circuit Amp. 8.0 8.7 7.8 12.9 14.1 12.6 17.8 19.6 17.3 Max. Fuse/ Brkr. 10 15 10 20 25 20 30 35 30 10/5/10 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 5 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Flat Top Cabinet NCW09-18 RIGHT RETURN LEFT RETURN TOP D A FILTER BRACKET E A F B G B FILTER BRACKET C DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF (ONLY BREAK-OFF TAB OPPOSITE AS GRILLE LID AS SHOWN) REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE ON BROKEN EDGE OF LEG AS SHOWN H FRONT J I DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF (ONLY BREAK-OFF TAB OPPOSITE AS GRILLE LID AS SHOWN) REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE ON BROKEN EDGE OF LEG AS SHOWN Overall Cabinet Flat Top A B C D E F GH I J Configuration Width Depth Height Grille Lid Grille Length Grille Width in. 45.0 10.8 25.7 9.2 35.0 6.1 2.3 44.1 10.3 4.3 09-12 cm. 114.3 27.3 65.2 23.4 88.9 15.6 5.8 112.0 26.0 10.9 in. 50.0 12.3 25.7 9.2 35.0 6.1 3.3 49.1 11.8 4.3 15-18 cm. 127.0 31.1 65.2 23.4 88.9 15.6 8.3 124.7 29.8 10.9 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 6 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Slope Top Cabinet NCS09-18 @756B@3BC@< B=> :34B@3BC@< 2 / 47:B3@0@/193B 3 / 4 0 5 0 47:B3@0@/193B 1 23B/7:/ BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E< @3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E< 6 4@=<B 8 7 23B/7:0 BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E< @3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E< Overall Cabinet Slope Top AB C D Configuration Width Depth Height Grille Lid in. 45.0 11.1 28.6 9.2 09-12 cm. 114.3 28.2 72.6 23.4 in. 50.0 12.6 29.1 9.2 15-18 cm. 127.0 32.0 73.9 23.4 E Grille Length 35.0 88.9 35.0 88.9 F Grille Width 6.1 15.6 6.1 15.6 GH I J 2.8 44.1 10.3 4.3 7.2 112.0 26.0 10.9 2.5 49.1 11.8 4.3 6.4 124.7 29.8 10.9 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 7 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Extended Slope Top Cabinet NCE09-18 @756B@3BC@< B=> :34B@3BC@< 2 3 / 4 0 5 / 47:B3@0@/193B 23B/7:/ BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E< @3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E< 6 4@=<B 1 47:B3@0@/193B 0 8 7 23B/7:0 BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E< @3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E< Overall Cabinet Ext. Slope Top Configuration AB Width Depth C H eight D Grille Lid E Grille Length F Grille Width G H I J in. 50.0 12.6 29.1 9.2 35.0 6.1 2.4 49.1 12.0 4.3 09-12 cm. 127.0 32.0 73.9 23.4 88.9 15.6 6.1 124.7 30.5 10.9 in. 55.0 12.6 29.1 9.2 35.0 6.1 2.5 54.1 11.8 4.3 15-18 cm. 139.7 32.0 73.9 23.4 88.9 15.6 6.4 137.4 29.8 10.9 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 8 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Right Return Controls Detail 1=<B@=:>/<3: @3;=D34=@/113AA B=1=<B@=:0=F 4/<=>B7=<AE7B16 3:31B@7163/B;=23 <=@;/:0=7:3@:3AA AE7B16=>B7=</: 2/;>3@=<=44AE7B16 1=;>@3AA=@ /113AA>/<3: @3;=D324=@ 1:/@7BG 0=B6A723A 47:B3@ 6/<2G0=F =>B7=</: 4CA32 <=<4CA32 27A1=<<31B :=ED=:B/53 B3@;7</:A 4F@3;=B3E/:: AB/B=>B7=<A=<:G 1=<23<A/B3 2@/7<1=<<31B7=< =>B7=</: 0/::D/:D3A =>B7=</: 6=A397BA =>B7=</:0/19>:/B3 @3?C7@324=@ 2/;>3@7<AB/::/B7=< =CBA723/7@ 2/;>3@=>B7=< 473:27<AB/::32 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 9 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Right Return Chassis Data = inches (cm) 9.38 (23.8) Models 09-12 37.88 (96.2) CONTROL PANEL 28.5 (72.4) 8.88 (22.6) Models 15-18 42.88 (108.9) CONTROL PANEL 34.0 (86.4) COMPRESSOR ACCESS PANEL BLOWER ACCESS PANEL 1.5 (3.8) 1.5 (3.8) FILTER 4.37 (11.1) WATER OUT 1/2 FPT WATER IN 1/2 FPT 10.31 (26.2) 4.5 (11.4) 1.0 (2.5) COMPRESSOR ACCESS PANEL BLOWER ACCESS PANEL WATER OUT 1/2 FPT WATER IN 1/2 FPT FILTER 11.75 (29.8) 4.5 (11.4) 1.0 (2.5) 1.5 (3.8) 1.5 (3.8) 4.32 (11.0) 0.86 (2.2) 2.0 (5.1) 25.25 (64.1) 21.4 (54.4) 20.0 (50.8) 1.78 (4.5) 11.0 (27.9) CONDENSATE DRAIN CONNECTION 43.37 (110.2) 28.0 (71.1) OPTIONAL BACK PLATE 9.25 (23.5) 13.9 (35.3) 1.64 (4.2) 25.65 (65.2) 19.83 (50.4) 12.03 (30.6) 5.5 (14.0) 2.75 (7.0) 0.66 (1.7) DAMPER OPENING COMPRESSOR ACCESS PANEL 0.86 (2.2) 2.0 (5.1) 25.25 (64.1) 20.6 (52.3) 19.5 (49.5) CONDENSATE DRAIN CONNECTION 48.25 (122.6) 33.0 (83.8) 12.0 (30.5) OPTIONAL BACK PLATE 11.78 (29.9) 13.9 (35.3) 1.62 (4.1) 25.80 (65.5) 20.0 (50.8) 12.18 (30.9) 5.4 (13.7) 2.75 (7.0) 0.83 (2.1) DAMPER OPENING COMPRESSOR ACCESS PANEL WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 10 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Left Return Controls Detail 1=;>@3AA=@ /113AA>/<3: @3;=D324=@ 1:/@7BG 0=B6A723A 1=<B@=:>/<3: @3;=D34=@/113AA B=1=<B@=:0=F :=ED=:B/53 B3@;7</:A 4F@3;=B3E/:: AB/B=>B7=<A=<:G 2/;>3@=<=44AE7B16 3:31B@7163/B;=23 <=@;/:0=7:3@:3AA AE7B16=>B7=</: 4/<=>B7=<AE7B16 =>B7=</: 4CA32 <=<4CA32 27A1=<<31B =>B7=</: 0/::D/:D3A =>B7=</: 6=A397BA =>B7=</: 3:31B@7163/B 6/<2G0=F 47:B3@ 1=<23<A/B3 2@/7<1=<<31B7=< =>B7=</:0/19>:/B3 @3?C7@324=@ 2/;>3@7<AB/::/B7=< =CBA723/7@ 2/;>3@=>B7=< 473:27<AB/::32 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 11 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Dimensional Data - Left Return Chassis Data = inches (cm) Models 09-12 28.5 (72.4) 37.88 (96.2) CONTROL PANEL 9.38 (23.8) Models 15-18 34.0 (86.4) 42.88 (108.9) CONTROL PANEL 8.88 (22.6) 1.50 (3.8) 1.50 (3.8) BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 4.37 (11.1) FILTER WATER OUT 1/2 FPT WATER IN 1/2 FPT 10.31 (26.2) 4.5 (11.4) 1.00 (2.5) 1.50 (3.8) 1.50 (3.8) BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 4.32 (11.0) FILTER WATER OUT 1/2 FPT WATER IN 1/2 FPT 11.75 (26.2) 4.5 (11.4) 1.00 (2.5) 0.86 (2.2) 2.0 (5.1) 25.25 (64.1) 21.4 (54.4) 20.0 (50.8) 1.78 (4.5) 11.0 (27.9) 1.62 (4.1) 25.65 (65.1) 19.83 (50.4) 12.03 (30.5) CONDENSATE DRAIN CONNECTION 43.37 (110.2) 28.00 (71.1) OPTIONAL BACK PLATE 2.75 (7.0) 13.90 (35.3) 9.25 (23.5) COMPRESSOR ACCESS PANEL 0.66 (1.7) DAMPER OPENING 5.50 (14.0) 0.86 (2.2) 2.0 (5.1) 25.25 (64.1) 20.6 (52.3) 19.5 (49.5) 12.0 (30.5) 1.62 (4.1) 25.80 (65.5) 20.0 (50.8) 12.18 (30.9) COMPRESSOR ACCESS PANEL CONDENSATE DRAIN CONNECTION 48.25 (122.6) 33.0 (83.8) OPTIONAL BACK PLATE 2.75 (7.0) 0.83 (2.1) 13.90 (35.3) 11.78 (29.9) DAMPER OPENING 5.50 (14.0) WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 12 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Physical Data Model Compressor (1 each) Factory Charge R410A, oz [kg] Fan Motor & Blower Fan Motor Type/Speeds Fan Motor- hp [W] ECM ECM Blower Wheel Size (Dia x W), in. [mm] ECM Coax and Water Piping Water Connections Size - FPT - in [mm] Coax & Piping Water Volume - gal [l] Consoles Air Coil Dimensions (H x W), in. [mm] Air Coil Total Face Area, ft2 [m2] Air Coil Tube Size, in [mm] Air Coil Number of rows Filter Standard - 1" [25.44mm] Weight - Operating, lb [kg] Weight - Packaged, lb [kg] 09 27 [0.77] Consoles 12 15 LG Rotary 27 [0.77] 36 [1.02] 18 34 [0.96] 0.25 [186] 5.75 x 5.5 [146 x 140] 3 Speeds 0.25 [186] 0.25 [186] 5.75 x 5.5 [146 x 140] 6.0 x 6.5 [152 x 165] 0.25 [186] 6.0 x 6.5 [152 x 165] 1/2" [12.7] 0.15 [0.6] 1/2" [12.7] 0.18 [0.7] 1/2" [12.7] 0.35 [1.3] 1/2" [12.7] 0.35 [1.3] 8 x 22 [203 x 559] 1.2 [0.114] 3/8 [9.5] 3 1 - 10 x 28 [254 x 711] 210 [91] 220 [100] 8 x 22 [203 x 559] 1.2 [0.114] 3/8 [9.5] 3 1 - 10 x 28 [254 x 711] 210 [95] 220 [100] 8 x 30 [203 x 762] 1.7 [0.155] 3/8 [9.5] 4 1 - 12 x 33 [305 x 838] 230 [102] 240 [109] 8 x 30 [203 x 762] 1.7 [0.155] 3/8 [9.5] 4 1 - 12 x 33 [305 x 838] 235 [107] 245 [111] 1/20/14 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 13 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Reference Calculations Heating Calculations: LWT = EWT - HE GPM x 500 Cooling Calculations: HR LWT = EWT + GPM x 500 HC LAT = EAT + CFM x 1.08 TH = HC + HWC LAT(DB) = EAT(DB) - SC CFM x 1.08 LC = TC - SC SC S/T = TC Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Definitions ABBREVIATIONS AND DEFINITIONS: CFM = airflow, cubic feet/minute EWT = entering water temperature, Fahrenheit GPM = water flow in gallons/minute WPD = water pressure drop, PSI and feet of water EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) HC = air heating capacity, MBTUH TC = total cooling capacity, MBTUH SC = sensible cooling capacity, MBTUH KW = total power unit input, kilowatts HR = total heat of rejection, MBTUH HE = total heat of extraction, MBTUH HW = desuperheater capacity, MBTUH EER = Energy Efficient Ratio = BTU output/Watt input COP = Coefficient of Performance = BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBTUH LC = latent cooling capacity, MBTUH S/T = sensible to total cooling ratio Operating Limits Operating Limits Air Limits Min. Ambient Air Rated Ambient Air Max. Ambient Air Min. Entering Air Rated Entering Air db/wb Max. Entering Air db/wb Water Limits Min. Entering Water Normal Entering Water Max. Entering Water Cooling (°F) (°C) 45 80 100 50 80.6/66.2 110/83 7.2 26.7 37.8 10.0 27/19 43/28.3 30 50-110 120 -1.1 10-43.3 48.9 Heating (°F) (°C) 45 7.2 70 21.1 85 29.4 40 4.4 68 20.0 80 26.7 20 30-70 90 -6.7 -1.1 32.2 NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation. WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 14 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Correction Factor Tables EA Corrections Cooling Capacity Corrections Entering Total Air WB ºF Clg Cap 55 60 65 66.2 67 70 75 0.898 0.912 0.967 0.983 1.000 1.053 1.168 60 0.723 Sensible Cooling Capacity Multipliers - Entering DB ºF 65 70 75 80 80.6 85 90 95 0.866 1.048 1.185 * * * * * 0.632 0.880 1.078 1.244 1.260 * * * 0.694 0.881 1.079 1.085 1.270 * * 0.655 0.842 1.040 1.060 1.232 * * 0.616 0.806 1.000 1.023 1.193 1.330 * 0.693 0.879 0.900 1.075 1.250 1.404 0.687 0.715 0.875 1.040 1.261 Note: * Sensible capacity equals total capacity at conditions shown. 100 * * * * * * 1.476 Power Heat of Input Rejection 0.985 0.994 0.997 0.999 1.000 1.003 1.007 0.913 0.927 0.972 0.986 1.000 1.044 1.141 11/10/09 Heating Capacity Corrections Ent Air DB °F Heating Corrections Htg Cap Power Heat of Ext 45 1.062 0.739 1.158 50 1.050 0.790 1.130 55 1.037 0.842 1.096 60 1.025 0.893 1.064 65 1.012 0.945 1.030 68 1.005 0.976 1.012 70 1.000 1.000 1.000 75 0.987 1.048 0.970 80 0.975 1.099 0.930 11/10/09 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 15 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Antifreeze Corrections Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given. Antifreeze Type Antifreeze % by wt Cooling Capacity Heating Capacity Pressure Drop EWT - degF [DegC] 90 [32.2] 30 [-1.1] 30 [-1.1] Water Ethylene Glycol Propylene Glycol Ethanol Methanol 0 1.000 10 0.991 20 0.979 30 0.965 40 0.955 50 0.943 10 0.981 20 0.969 30 0.950 40 0.937 50 0.922 10 0.991 20 0.972 30 0.947 40 0.930 50 0.911 10 0.986 20 0.970 30 0.951 40 0.936 50 0.920 1.000 0.973 0.943 0.917 0.890 0.865 0.958 0.913 0.854 0.813 0.770 0.927 0.887 0.856 0.815 0.779 0.957 0.924 0.895 0.863 0.833 1.000 1.075 1.163 1.225 1.324 1.419 1.130 1.270 1.433 1.614 1.816 1.242 1.343 1.383 1.523 1.639 1.127 1.197 1.235 1.323 1.399 Warning: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent. Antifreeze Correction Example Antifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F and 90°F respectively as well as pressure drop at 30°F for an Envision Console Series NC*18. The corrected cooling capacity at 90°F would be: 17,100 MBtuh x 0.969 = 16,569 MBtuh The corrected heating capacity at 30°F would be: 14,300 MBtuh x 0.913 = 13,056 MBtuh The corrected pressure drop at 30°F and 5.5 GPM would be: 18.2 feet of head x 1.270 = 23.1 feet of head WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 16 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz NC09 !@ObSR14;6SObW\U1]]ZW\U 3EB 4 4Z]e @ObS 5>; EObS` >`Saac`S2`]^ >A7 4B62 61 Y0bcV 63/B7<53/B%4 >]eS` 63 :/B YE Y0bcV 4 # & " #$ =^S`ObW]\\]b`SQ][[S\RSR # !& && $& $ "& &' ! =^S`ObW]\\]b`SQ][[S\RSR ! & ! #" $' $ "& &'! # !& && %! $! # '# %$ $ ## '# " & ! # %' $ #& ' " # !& &% &! $" $ '!% ' && $# $$ '# # & # ' $# $' '$ # !% &# '" $$ % '% ' ! $& & ''& $ & "' # $& & # # !$ &! & $' &# ! & & & % '" "# % & "% % '$ # # !# & % '& #% & % % %! %! & & "$ ' %" " %' # !" %' ! %# # &" % $ !$ %$ ' & ' "" !& %% $ # !! %$ " %& ! % # & & "! # ! %" $ # & & " =^S`ObW]\\]b`SQ][[S\RSR # ! % $ " & % " # ! $' 1=> !!# !!& !" !$! !% !& " "& "% ""$ "#! "$ "&& "'! "'' # # #! # " # # # $ >S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV 1==:7<53/B&$%4 B1 Y0bcV A1 Y0bcV AB @ObW] >]eS` 6@ YE Y0bcV 33@ =^S`ObW]\\]b`SQ][[S\RSR =^S`ObW]\\]b`SQ][[S\RSR %! $ !& !" !& %" $ !$ !" !!' =^S`ObW]\\]b`SQ][[S\RSR # % $ " ' & $ % $ !' ' ! % $& $! "# ! !$ ' $' $! "" ! "' % $" " " $$ " $% $" # '' # $% $" # % $' $" "% ! " $# $# #' % $$ $# #$ & ! $% $# #" ' '# $! $% $# % "# '$ $# $% $ % ## '' $# $$ $ ' $" ' $ $% % $ % '! $ $% $' % !# '" $! $% $% % " =^S`ObW]\\]b`SQ][[S\RSR ' $ $% %$ $ & ' $ $% %" $ ! =^S`ObW]\\]b`SQ][[S\RSR &$ #& $% &! # " &% #' $& & # % =^S`ObW]\\]b`SQ][[S\RSR & ## $% ' ! ' &! #$ $& && ! '# WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 17 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz NC12 !#@ObSR14;6SObW\U1]]ZW\U 3EB 4 4Z]e @ObS 5>; EObS` >`Saac`S2`]^ >A7 4B62 61 Y0bcV 63/B7<53/B%4 >]eS` 63 :/B YE Y0bcV 4 # ! ! % " =^S`ObW]\\]b`SQ][[S\RSR !# ! %" &$ & #' '& # ' =^S`ObW]\\]b`SQ][[S\RSR ! ! % !& &# % '"! !# ! $' &$ %! '# # ' & && %& '$% " ! $ !% && & '% !# ' $$ ! &' & '%& # & & ' ' && ''$ # ! # !# ' ' !# % $ ! ' ' $ # & % ! '" ! $ ! " !! !" '" !" !# $ $ !% '$ " " # % $ "# '% $" % ! " ! "% '& " $' !# # #& # $ %% # % # #$ ! '" & ! ! ! #' " ! !# # #% $ # # $ # $ " $% % ! ' ! ! ' $' ' ! & !# " ## % !" !# # $ ! ! & !# ! #! # # ! $ =^S`ObW]\\]b`SQ][[S\RSR !# # # # ! # !# "' 1=> !# !"" !"& !$ !$$ !% !&$ !&' !'" "" "$ "' "!' "" "" ""# ""& "# "## "#$ "#% >S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV 1==:7<53/B&$%4 B1 Y0bcV A1 Y0bcV AB @ObW] >]eS` 6@ YE Y0bcV 33@ =^S`ObW]\\]b`SQ][[S\RSR " "" !% !' ! ! !! " ! # $ ' " # '% '& &' ' &# &% =^S`ObW]\\]b`SQ][[S\RSR '& $' "# #& $' " #' =^S`ObW]\\]b`SQ][[S\RSR '# % #" ## '% % # #$ ' % $" # ' % $ # '" % #& #! &$ % % "# &% % $& "# &' % $# "$ & % %% !& & % %# !& &! % % !' %& %! &" !# %' %! & !$ & %! %& !% %# %! ' !" %$ %" && !" %% %! &# !" =^S`ObW]\\]b`SQ][[S\RSR %! %# ! %" %# '% ! =^S`ObW]\\]b`SQ][[S\RSR $' %% % % %% & & =^S`ObW]\\]b`SQ][[S\RSR $% %' $ $& %& & % !$ !" ## %$ & % %& ' "" # $! $ !# " & " '% & &" % %" WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 18 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz NC15 "#@ObSR14;6SObW\U1]]ZW\U 3EB 4 4Z]e @ObS 5>; EObS` >`Saac`S2`]^ >A7 4B62 61 Y0bcV 63/B7<53/B%4 >]eS` 63 :/B YE Y0bcV 4 & " ! !" %& =^S`ObW]\\]b`SQ][[S\RSR "# #' !$ % '! %# ' % !' =^S`ObW]\\]b`SQ][[S\RSR ! ! !! %$ & '# &# ' "# #% ! ! '% ' '!! % !& % '# '" '" " ! ! %# ' '$ '$ '"$ "# #$ ' !" '& '#$ $ !% !' '# $ '$# # ! ! %! " '% & '% "# ## % "$ '' '%' $ !$ # '$ ''" $ ! ! % #$ '% "# #" # $ % # !# $$ '$ !! % ! ! % % '& !% ! "# #! %$ " " # !" &! ! "& #% & ! ! $& &$ " # $! "# # &' # #! $& " ! '$ % #' &! ' ! ' $% '' ' $ &' "# # & $" '# " ! ! & $# "# # $ ! ! ! & $" =^S`ObW]\\]b`SQ][[S\RSR "# "' ! ! ' ! % $ "# "& 1=> !!% !$ !% !'! !'" " " % " & "! "$$ "$' "% ## #& # # # " # $ #!# #!$ #!& >S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV 1==:7<53/B&$%4 B1 A1 Y0bcV Y0bcV AB >]eS` 6@ @ObW] YE Y0bcV 33@ =^S`ObW]\\]b`SQ][[S\RSR =^S`ObW]\\]b`SQ][[S\RSR % % "& &% !#$ %! " % "# &' !&" =^S`ObW]\\]b`SQ][[S\RSR $% % $ && %& % % #% &' ! $ % % %# && # $" & % % && $ $$ % $& &' "" ## " %" &" &! &! #$ # %" & &" ' #' & %" %% &# % "% %$ '" %' #% "' ! %$ ' & $# # # %$ &$ & %& " ' %% %$ " "# %% '$ %% # "% %$ '! %& #& !% $ %% & %" % !' & %& ! %" !# " ' %% %# " =^S`ObW]\\]b`SQ][[S\RSR !" # %& " %! & !$ $ %& %! ! =^S`ObW]\\]b`SQ][[S\RSR & %' ! % " ! ! %' % & =^S`ObW]\\]b`SQ][[S\RSR ! ' & !' $ & # '! & !# $ &# WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 19 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz NC18 #@ObSR14;6SObW\U1]]ZW\U 3EB 4 4Z]e @ObS 5>; EObS` >`Saac`S2`]^ >A7 4B62 61 Y0bcV 63/B7<53/B%4 >]eS` 63 :/B YE Y0bcV 4 ! & " " " '% =^S`ObW]\\]b`SQ][[S\RSR ## & &# ! &' ' ! % !' =^S`ObW]\\]b`SQ][[S\RSR ! " " '$ " " '"! ## %' & "! # '"# ! % !& ## $ '$% " " " '" #& % # '%! ## %& %' $ & & '& ! $ !% % & & ''' # " " ' %$ ' ! # ## %$ %$ & ! !$ # ! $ !$ ' ! "& !$ $ " !' ' '% ! # "" ## %# %! ! !" #% #$ ! # !# ! ! $& %" % " !' &' & !" % &! ## %" % # !% %& '% ! # !" !! " &$ & " !& && !% " &' ' ## %! $' " "! ' " ! " ! "% "" '& !& ' " !% &$ # "$ "# ## % $$ ## "& # # ! " ! " !% &# ## % $! ! ! ! " !$ &! =^S`ObW]\\]b`SQ][[S\RSR ## $' #' ! ! ' " !# & ## $& #% 1=> !$ !!# !!$ !$ !$# !% !'! !'& "# "!! "!% ""! "% "%# "& "&& "' "'! #! #" #$ >S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV 1==:7<53/B&$%4 B1 Y0bcV A1 Y0bcV AB @ObW] >]eS` 6@ YE Y0bcV 33@ =^S`ObW]\\]b`SQ][[S\RSR # ! % ! # & ' ' '# %$ %& & % %" %% $$ $' % $" $$ #& $ "% # =^S`ObW]\\]b`SQ][[S\RSR $ % $' "$ $! % $# "% =^S`ObW]\\]b`SQ][[S\RSR ## % %' " #& %! %# " "& %! '! !# "' %! &' !# # %! &" !% !' %! " " %! '% # "" %" ' $ ! %" ' ! ! %" $ # !# %" $ ' %# # ! ! %# ' # ! %# # $ $ %$ " " & %$ !" # ' %# ! # =^S`ObW]\\]b`SQ][[S\RSR # %$ "' # $ %$ "" # =^S`ObW]\\]b`SQ][[S\RSR %% $ ! ! %% #& " =^S`ObW]\\]b`SQ][[S\RSR % & %% & ' %' % ' ! !"$ $' ' ' ! "& &% '% $ $' & !% "% #! & $ ! # '% &! &% WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 20 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Wiring Schematics CCM - with ECM Motor and Electronic Stat 208-230-265/60/1 ECM Motor Compressor Green/Yellow ECM Motor Module Note 4 Red Black Blue S C R Red Blk Tan (33) Ground Lug Handi - Box T2 T1 CC L2 L1 Brown (26) Black (31) Red (32) Unit Power Supply 208-230/60/1 or 265-277/60/1 G White Yellow Blue Y LP LP HP HP CC CG LO R C Y LP LP HP HP CC CG LO R C Fan Switch High Low 4 Black (25) RB 2 Black (27) 5 Brown (26) Red (19) Black NOTE 1 Red Blue 208V 230V 265V Transformer PB 24V 1 Yellow Black/White Yellow (13) Electronic THERMOSTAT IN PUT Mode Switch Red (19) 4 5 6 1 Auto 2 3 Fan White (18) Red (17) Red (11) Ther Black ST mistor Black T Yellow (10) Black (12) Black (22) 2 NOTE 2 3 Green (00) HP LP FS NOTE 3 Black/White (1) Red (2) Brown (3) Violet (4) Violet (5) Black (6) Black (7) Blue (8) Blue (9) Yellow (10) TEST PIN COMPRESSOR CONTROL MODULE A Heat T1 T2 T3 T4 T5 T6 B Cool Red 24 V AC Black (12) T3 Red (11) Red T1 Orange T2 T4 T6 T5 SHUT DOWN Red (15) Red (16) Red (17) Fan Mode Sw Continuous White (18) Black (22) 1 3 White (20) RB Yellow (13) Orange (14) Cycled RV Orange (21) Violet (5) Violet (4) Damper Switch ON CC White (34) Blk/Wht (23) Blk/Wht (24) OFF Blue (T6) 24VAC Shutdown Yellow (13) Not Used NC*09 NC*12 NC*15 NC*18 CHART 1 Blower Sengs High Low Yellow White Blue Yellow Yellow White Blue Yellow Blue/Wht (36) 24 V Accessory Damper Motor D Blue/Wht (35) DT 1 3 2 J1 Overide Shut down Legend Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring Quick connect terminal Wire nut CC - Compressor Contactor DT - Damper Terminal Block FS - Freeze Sensing Device HP - High Pressure Switch LP - Low Pressure Switch PB - Power Block RB - Blower Relay RV - Reversing Valve Coil ST - Entering Air Temperature Sensor L1 P Field wire lug Earth Ground Relay Contacts N.O., N.C. Polarized connector HP Switch - High Pressure LP Switch - Low Pressure Relay coil Capacitor T Thermistor Temperature Switch Notes: 1. Switch Red and Blue wires for 208 volt operation 2. Terminal C of 24 V PB is used as "L" output for Brown wire 3 for Lockout. 3. Optional field installed freeze sensing device. 4. Factory wired. Refer to blower table settings. Page 1 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 21 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Wiring Schematics cont. CCM - with ECM, Electronic Heat and Electronic Stat 208-230-265/60/1 ECM Motor Green/Yellow ECM Motor Module Note 5 Blue White White T2 T1 EH L2 L1 Blue (40) Tan (41) Compressor Blue S C R Red Blk Tan (33) Ground Lug Handi - Box Blue (40) T2 T1 CC L2 L1 Brown (26) Black (31) Unit Power Supply 208-230/60/1 or 265-277/60/1 G White Yellow Blue Y LP LP HP HP CC CG LO R C Y LP LP HP HP CC CG LO R C Fan Switch High Black (25) Red Black 4 RB 2 Black (27) 5 Brown (26) Tan (41) Red (32) Black Blue 230V 265V NOTE 1 Red 208V Transformer Low Yellow (44) Yellow (13) Electronic THERMOSTAT IN PUT A Heat T1 T2 T3 T4 T5 T6 B Cool Red (19) Mode Switch Red (19) 4 5 1 3 E1 Black (12) Black (22) Gray (42) 6 1 Auto 2 3 Fan AQ NOTE 4 Normal White (18) Red (17) Red (11) Ther Black ST mistor Black T Red 24 V AC Black (12) T3 Red (11) Red T1 Orange T2 T4 T6 Brown (43) EHS Blue (T6) Red Fan Mode Sw (17) Continuous White (18) 1 3 White (20) RB Yellow (13) Orange (14) Blue (T6) Cycled RV Yellow (44) Orange (21) PB 24V 1 Yellow 2 NOTE 2 3 Black/White Green (00) HP LP FS NOTE 3 Black/White (1) Red (2) Brown (3) Violet (4) Violet (5) Black (6) Black (7) Blue (8) Blue (9) Yellow (10) TEST PIN COMPRESSOR CONTROL MODULE Violet (4) Red (39) Violet (5) EH Blue (38) 2 4 E1 5 Black (37) CC Blk/Wht (23) White (34) Damper Switch Blk/Wht (24) ON T5 SHUT DOWN Red (15) 24VAC Shutdown Red (16) Blue/Wht (36) NC*09 NC*12 NC*15 NC*18 CHART 1 Blower Sengs High Low Yellow White Blue Yellow Yellow White Blue Yellow 24 V Accessory Damper Motor D OFF Blue/Wht (35) DT 1 3 2 J1 Overide Shut down LegLeegnednd Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring Quick connect terminal Wire nut AQ - Aquastat CC - Compressor Contactor DT - Damper Terminal Block E1 - Electric Heat Relay EH - Electric Heat Contactor EHS Electric Heat Switch FS - Freeze Sensing Device HP - High Pressure Switch LP - Low Pressure Switch PB - Power Block RB - Blower Relay RV - Reversing Valve Coil ST - Entering Air Temperature Sensor L1 P Field wire lug Earth Ground Relay Contacts N.O., N.C. Polarized connector HP Switch - High Pressure LP Switch - Low Pressure Relay coil Capacitor T Thermistor Temperature Switch Notes: 1. Switch Red and Blue wires for 208 volt operation 2. Terminal C of 24 V PB is used as "L" output for Brown wire 3 for Lockout. 3. Optional field installed freeze sensing device. 4. Optional field installed aquastat. 5. Factory wired. Refer to blower table settings. Page 1 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 22 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Wiring Schematics cont. ABC and UPC - ECM with Remote Stat Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz 208-230-265/60/1 ECM Motor Module Grn ECM Motor Compressor S C Blue R Red Tan Black Handi - Box Ground Lug Unit Power Supply 208-230/60/1 or 265/60/1 G White Yellow Blue Note 2 Fan Speed Switch High Low Gray/White Damper Switch Off White (34) On Blue /Wht (35) DT D Damper Motor Blue /Wht (36) RB 42 Red Black Black Black (13) RB White (12) Violet (14) CC Black (15) Orange (01) Orange (02) RV Yellow T Yellow Gray T Gray Blue (07) Blue (08) Black (09) T2 T1 CC L2 L1 Black White Black Blue 230V/265V Note 1 Red 208V RV FD LAT LP HP Transformer Black (10) Black/White P9 EH1 CC2 CC F C P2 ES LS ALM ALG ACC COM K5-Alarm Relay ACC NO ACC NC K6-Acc Relay LO R C O/B G Y1 Y2 W DH P1 R Com2 LED5 G RS485 NET C P8 K1-RV Relay K3-CC2 Relay K2-CC Relay K4-Fan Relay JW2 R F FG CC CCGCHCI2 CC2 LO CC2 G P5 REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS P4 C R F1-3A F Aurora Base Control (ABC) SW1 Test Mode Com1 LED5 G RS485 NET C R - + P7 RS485 EXP C R - + P6 CO C EH1 C EH2 P3 Status LED3 G PWM CFM Fault C LED1 P13 R Off On FP1 15°F/30°F 1 FP2 15°F/30°F 2 RV B/O 3 Acc Dip 4 4 Acc Dip 5 5 CC Dual/Single 6 L Output Type 7 Future Use 8 SW2 Config LED2 Y Y1 G CC Green (00) Red Black/White MV Note 3 Black/White From UPC Brown (23) Condensate ES Yellow Yellow ES Red Red 24V Emergency Shutdown WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 23 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Wiring Schematics cont. ABC and UPC - ECM with Remote Stat Notes: 1 Swap blue and red leads for 208V operation. 2 Factory wired. Refer to blower table settings. 3 - When field installed 24VAC motorized valve is used, connect to C and Y. NC*09 NC*12 NC*15 NC*18 CHART 1 Blower Sengs High Low Yellow White Blue Yellow Yellow White Blue Yellow Legend Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal T Thermistor Relay Coil Switch - Condensate Overflow Switch - High pressure Switch - Low pressure 1 2 3 L1 Field Wiring Lug Polarized connector Ground Relay Contacts N.O., N.C. Capacitor Fuse G Light Emitting Diode - Green Y Light Emitting Diode - Yellow Temperature Switch R Light Emitting Diode - Red Wire nut CC Compressor Contactor CO Condensate Overflow Sensor ES Emergency Shutdown HP High Pressure Switch LP Low Pressure Switch FD Freeze Detection Sensor F1 Fuse SW1 Push button SW2 DIP package 8 position PB Power Block RB Blower Relay RV Reversing Valve Coil 208-230-265/60/1 Accessory Relay Operation SW2-4 SW2-5 Cycle with Blower On On Cycle with Compressor Off Off Water Valve Slow Open On Off Outdoor Air Damper Off On Aurora Timing Events Event Normal Mode Random Start Delay 5 to 80 seconds Compressor On Delay 5 seconds Compressor Minimum On Time 2 minutes Compressor Short Cycle Delay 4 minutes Blower Off Delay 30 seconds Fault Recognition Delay High Pressure Less than 1 second Start-Up Bypass Low Pressure 2 minutes Fault Recognition Delay Low Pressure 30 seconds Start-Up Bypass Low Water/Air Coil Limit 2 minutes Fault Recognition Delay Low Water/Air Coil Limit 30 seconds Fault Recognition Delay Condensate Overflow 30 seconds Thermostat Call Recognition Time 2 seconds Auxiliary Heat Staging Delay 5 minutes Emergency Heat Staging Delay 2 minutes Water Valve Slow Open Delay 90 seconds Reheat Delay 30 seconds Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds Aurora LED Flash Codes Slow Flash 1 second on and 1 second off Fast Flash 100 milliseconds on and 100 milliseconds off Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Random Start Delay Status LED (LED1, Green) Fast Flash Configuration LED (LED2, Yellow) Fast Flash Fault LED (LED3, Red) Fast Flash Status LED (LED1, Green) Configuration LED (LED2, Yellow) Fault LED (LED3, Red) Normal Mode ON No Software Overide Flash ECM Setting Normal Mode OFF Control is Non-Functional OFF DIP Switch Overide Slow Flash Input Fault Lockout Flash Code 1 Test Mode Slow Flash ECM Configure Mode Fast Flash High Pressure Lockout Flash Code 2 Lockout Active Fast Flash Reset Configure Mode Off Low Pressure Lockout Flash Code 3 Dehumidification Mode Flash Code 2 Low Air Coil Limit Lockout - FP2 Flash Code 4 Reserved Flash Code 3 Low Water Coil Limit Lockout - FP1 Flash Code 5 Reserved Flash Code 4 Reserved Flash Code 6 Load Shed Flash Code 5 Condensate Overflow Lockout Flash Code 7 ESD Flash Code 6 Over/Under Voltage Shutdown Flash Code 8 Reserved Flash Code 7 Reserved Flash Code 9 Reserved Flash Code 10 Air/Water Coil Limit Sensor Error Flash Code 11 PWM CFM C CC2 Factory Factory Use HP P4 ECM PWM HP P13 LP LP FP2 Factory FP2 FP1 FP1 SW1 Test REV REV RV K1 CC2 CC K2 G P5 LO HI CCG CC FG F R F CC Hi K3 Fan K4 Alarm K5 CC Acc K6 G Y1 JW2 Alarm P2 Field Connections Off LED1 FP1 15oF/30oF On 1 LED2 R FP2 15oF/30oF 2Y Fault RV B/O ACC Dip 4 LED3 G ACC Dip 5 CC Dual/Single L Pulse/Continuous Status Reheat/Normal 3 Config 4 5 6 7 8 SW2 AURORA BASE CONTROLTM Com1 G EH1 P3 EH2 C EH1 C CO N/A Factory RS485 Exp P6 (+) (-) R C P7 (+) RS 485 (-) R C P11 P8 Com2 G P9 Factory Fan Connection DH W Y2 Y1 G O/B C R LO P1 Field Connections 3A-Fuse DH W Y2 Y1 G O/B C R LO ES LS ALM ALG ACC c ACC no ACC nc RR RS485 NET CC C WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 24 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Wiring Schematics cont. ABC - ECM with Electric Heat and Remote Stat Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz 208-230-265/60/1 ECM Blue ECM Motor Module Motor Grn Note 2 Fan Speed Switch High White Yellow Blue Low Black (25) White White T2 T1 EH L2 L1 RB 42 Black (27) Tan (41) Blue (40) Red Black Damper Switch Off Blue /Wht (35) DT D Damper On Motor Blue /Wht (36) White (34) Compressor S C Blu R Red Blk Tan Handi - Box Ground Lug T2 T1 CC L2 L1 Black (31) Red (32) Black Blue 230V/265V Unit Power Supply 208-230/60/1 or 265/60/1 G Red 208V Note 1 Transformer Yellow 24V Emergency Shutdown Black/White Red ES Red ES Yellow TB Emerg Shutdown ES Load Shed LS Lockout Circuit A LO1 24VAC R 24VAC Common C Reversing Valve O Fan G Compressor A Y1 Electric Heat W Dehumidification DH Lockout Circuit B LO2 Compressor B Y2 Class 2 Note 3 AQ Black/ White Black/ White 4 5 Red (39) E1 2 Blue (38) EH CC Yellow (44) Black (15) Black (13) RB White (12) 470 T RV 470 Resistor RV FD LP HP Black (10) Black (09) Blue (08) Blue (07) Yellow Yellow Orange (02) Orange (01) Violet (14) P9 EH1 CC2 CC F C P2 ES LS ALM ALG ACC COM K5-Alarm Relay ACC NO ACC NC K6-Acc Relay LO R C O/B G Y1 Y2 W DH P1 R Com2 LED5 G RS485 NET C P8 JW2 K1-RV Relay R F FG CC CCGCHCI2 CC2 LO CC2 G P5 REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS P4 C R F1-3A F K3-CC2 Relay K2-CC Relay K4-Fan Relay Aurora Base Control (ABC) SW1 Test Mode Com1 LED5 G RS485 NET C R - + P7 RS485 EXP C R - + P6 CO C EH1 C EH2 P3 Status LED3 G PWM CFM Fault C LED1 P13 R Off On FP1 15°F/30°F 1 FP2 15°F/30°F 2 RV B/O 3 Acc Dip 4 4 Acc Dip 5 5 CC Dual/Single 6 L Output Type 7 Future Use 8 SW2 Config LED2 Y Y1 G CC 1 3 E1 Green (00) Brown (23) Condensate WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 25 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Wiring Schematics cont. ABC - ECM with Electric Heat and Remote Stat Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Notes: 208-230-265/60/1 05 1 Swap blue and red leads for 208V operation. 2 Factory wired. Refer to blower table settings. 3 Optional field installed Aquastat for use with single heat. Accessory Relay Operation Cycle with Blower SW2-4 SW2-5 On On Cycle with Compressor Off Off Water Valve Slow Open On Off Outdoor Air Damper Off On Aurora Timing Events Event Normal Mode Random Start Delay 5 to 80 seconds Compressor On Delay 5 seconds Compressor Minimum On Time 2 minutes Compressor Short Cycle Delay 4 minutes Blower Off Delay 30 seconds Fault Recognition Delay High Pressure Less than 1 second Start-Up Bypass Low Pressure 2 minutes Fault Recognition Delay Low Pressure 30 seconds Start-Up Bypass Low Water/Air Coil Limit 2 minutes Fault Recognition Delay Low Water/Air Coil Limit 30 seconds Fault Recognition Delay Condensate Overflow 30 seconds Thermostat Call Recognition Time 2 seconds Auxiliary Heat Staging Delay 5 minutes Emergency Heat Staging Delay 2 minutes Water Valve Slow Open Delay 90 seconds Reheat Delay 30 seconds Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds NC*09 NC*12 NC*15 NC*18 CHART 1 Blower Sengs High Low Yellow White Blue Yellow Yellow White Blue Yellow Legend Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal T Thermistor Relay Coil Switch - Condensate Overflow Switch - High pressure Switch - Low pressure 1 2 3 L1 Field Wiring Lug Polarized connector Ground Relay Contacts N.O., N.C. Capacitor Fuse G Light Emitting Diode - Green Y Light Emitting Diode - Yellow Temperature Switch R Light Emitting Diode - Red AQ Aquastat CC Compressor Contactor CO Condensate Overflow Sensor ES Emergency Shutdown HP High Pressure Switch LP Low Pressure Switch FD Freeze Detection Sensor F1 Fuse Wire nut SW1 Push button SW2 DIP package 8 position PB Power Block RB Blower Relay RV Reversing Valve Coil Aurora LED Flash Codes Slow Flash 1 second on and 1 second off Fast Flash 100 milliseconds on and 100 milliseconds off Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Random Start Delay Status LED (LED1, Green) Fast Flash Configuration LED (LED2, Yellow) Fast Flash Fault LED (LED3, Red) Fast Flash Status LED (LED1, Green) Configuration LED (LED2, Yellow) Fault LED (LED3, Red) Normal Mode ON No Software Overide Flash ECM Setting Normal Mode OFF Control is Non-Functional OFF DIP Switch Overide Slow Flash Input Fault Lockout Flash Code 1 Test Mode Slow Flash ECM Configure Mode Fast Flash High Pressure Lockout Flash Code 2 Lockout Active Fast Flash Reset Configure Mode Off Low Pressure Lockout Flash Code 3 Dehumidification Mode Flash Code 2 Low Air Coil Limit Lockout - FP2 Flash Code 4 Reserved Flash Code 3 Low Water Coil Limit Lockout - FP1 Flash Code 5 Reserved Flash Code 4 Reserved Flash Code 6 Load Shed Flash Code 5 Condensate Overflow Lockout Flash Code 7 ESD Flash Code 6 Over/Under Voltage Shutdown Flash Code 8 Reserved Flash Code 7 Reserved Flash Code 9 Reserved Flash Code 10 Air/Water Coil Limit Sensor Error Flash Code 11 PWM CFM C CC2 Factory Factory Use Factory Factory HP P4 ECM PWM HP P13 LP LP FP2 FP2 FP1 FP1 SW1 Test REV REV RV K1 CC2 CC K2 G P5 LO HI CCG CC FG F R F CC Hi K3 Fan K4 Alarm K5 CC Acc K6 G Y1 JW2 Alarm P2 Field Connections Off LED1 FP1 15oF/30oF On 1 LED2 R FP2 15oF/30oF 2Y Fault RV B/O ACC Dip 4 LED3 G ACC Dip 5 CC Dual/Single L Pulse/Continuous Status Reheat/Normal 3 Config 4 5 6 7 8 SW2 AURORA BASE CONTROLTM Com1 G EH1 P3 EH2 C EH1 C CO N/A RS485 Exp P6 (+) (-) R C P7 (+) RS 485 (-) R C P11 P8 Com2 G P9 Factory Fan Connection DH W Y2 Y1 G O/B C R LO P1 Field Connections 3A-Fuse DH W Y2 Y1 G O/B C R LO ES LS ALM ALG ACC c ACC no ACC nc RR RS485 NET CC C P WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 26 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Wiring Schematics cont. Aurora UPC Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz To ABC - P8 12345678 BACnet or N2 Network Connections Devices Must Be Wired in Daisy Chain Configuration Orange Red White Black Blue Green Brown Yellow NET+ NETCOM NET+ NETCOM Optional LON Add-On Module LON OC LON Network Connections Devices Must Be Wired in Daisy Chain Configuration Service LED1 21 LED2 Tx LED3 Rx LED4 Net ECHELON 12 12 GND ZS Sensor 1 RNET+ Addr: 0 RNET- +12V ZS Sensor 2 Addr: 1 GND RNET+ RNET- +12V ZS Sensor 3 Addr: 2 GND RNET+ RNET- +12V NET+ NETCOM NET+ NETN N/C Signal LED1 TX LED2 RX LON DAPTER PORT LED6 TX LED7 2W RX 4W GND RNET+ RNET+12V RNET GND LN+ LN+12 /S LOCAL ACCESS POWER GND 24 VAC LED3 POWER FORMAT BATT Communication Options NOTE 1 12345678 LED4 RUN LED5 ERR ON TEN'S 89 0 12 73 654 89 0 12 73 654 ONE'S MAC Address Setting ZS Sensor Information Notes Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations. 1. Use DIP Switches 5 8 to change communication protocol and DIP switches 1 2 to change BACnet baud rate DIP Switch Value 1 2 4 8 ON 1 2 34 Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address. Legend Factory Low Voltage Wiring Field Low Voltage Wiring 12345678 RJ45 Connector Page 1 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 27 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Engineering Guide Specifications General Furnish and install WaterFurnace Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Chassis shall be installed with factory built cabinet or other custom cabinet approved by WaterFurnace engineering. Chassis SHALL NOT be installed without an approved cabinet enclosure. Capacities and characteristics as listed in the schedule and the specifications that follow. The reverse cycle heating/ cooling units shall be floor mounted console type with horizontal air inlet and up-flow air discharge. Units shall be AHRI/ISO 13256-1 certified and listed by a nationally recognized safety-testing laboratory or agency, such as ETL Testing Laboratory. Each unit shall be computer runtested at the factory with conditioned water and operation verified to catalog data. Each unit shall be mounted on a pallet and shipped in a corrugated box or stretch-wrapped. The units shall be designed to operate with entering liquid temperature between 20°F and 120°F [-6.7°C and 48.9°C]. The drain pan shall be of stainless steel construction to inhibit corrosion and bacterial growth. Drain outlet shall be located on pan as to allow complete and unobstructed drainage of condensate. The unit as standard will be supplied with solid-state electronic condensate overflow protection with Aurora Base Control. Mechanical float switches WILL NOT be accepted. Condensate tube shall be constructed of stainless steel and have an internal factory installed condensate trap. Refrigerant Circuit All units shall utilize the non-ozone depleting and low global warming potential refrigerant R410A. All units shall contain a sealed refrigerant circuit including a hermetic motorcompressor, bi-directional thermostatic expansion valve, finned tube air-to-refrigerant heat exchanger, reversing valve, coaxial tube water-to-refrigerant heat exchanger, and service ports. Chassis & Cabinet The cabinet shall be fabricated from heavy-gauge galvanized steel and finished with a beige textured epoxy powder coating on both sides for added protection. This corrosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117. The cabinet shall be easily removable to allow for ease of service to the controls compartment, chassis, and piping. The top of the cabinet and grille is a horizontally flat (optional sloped) surface with a hinged control door cover. The return air filter shall be 1 in. (25.4 mm) fiberglass disposable type media. The return and supply air sections are insulated with a 1/4 in. (6.4 mm) thick, dual density, 2 lb/ft3 (32 kg/m3) coated mat glass fiber with edges sealed or tucked under flanges to prevent the introduction of glass fibers into the discharge supply air through the aluminum grille. Standard cabinet panel insulation must meet NFPA 90A requirements, air erosion and mold growth limits of UL-181, stringent fungal resistance test per ASTM-C1071 and ASTM G21, and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not be accepted. Option: A Super Quiet Sound package shall include multidensity full coverage compressor blanket. Option: Shipped with motorized outside air damper and damper assembly for 25% make-up air. Compressors shall be high-efficiency single speed rotary type designed for heat pump duty and mounted on durometer grommets to provide vibration free compressor mounting. Compressor motors shall be single-phase ECM with internal overload protection. Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled aluminum tube construction rated to withstand 600 psig (4135 kPa) refrigerant working pressure. Option: AlumiSeal electro-coated air coil. The coaxial water-to-refrigerant heat exchanger shall be designed for low water pressure drop and constructed of a convoluted copper (cupronickel option) inner tube and a steel outer tube. Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled copper tube construction rated to withstand 600 PSIG (4135 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG (4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure. The thermostatic expansion valve shall provide proper superheat over the entire liquid temperature range with minimal "hunting." The valve shall operate bi-directionally without the use of check valves. Option: Cupro-nickel refrigerant to water heat exchanger shall be of copper-nickel inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 28 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Engineering Guide Specifications cont. (4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure. Water lines shall also be of cupronickel construction. Option: ThermaShield coated water-to-refrigerant heat exchanger, water lines and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures below 50°F. Blower Motor and Assembly The blower shall be a direct drive centrifugal type with a twin dynamically balanced wheel. The housing and wheel shall be designed for quiet, low outlet velocity operation. The blower housing shall be constructed of galvanized steel and shall be removable from the unit for servicing of the blower motor. The blower motor shall be 3-speed highefficiency electrically commutated motor (ECM) and shall be isolated from the housing by rubber grommets. The motor shall be permanently lubricated and have thermal overload protection. Electrical A control box shall be located within the unit compressor compartment and shall contain a 75VA transformer, 24 Volt activated, 2 pole compressor contactor, and solidstate controller for complete unit operation. Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be 24 Volt and provide heating or cooling as required by the remote thermostat/sensor. Unit mounted controls shall consist of switches for "OFF", "FAN", and "AUTO" or "HEAT/COOL". An additional switch is provided for blower speed setting of "HI" or "LO". The unit shall be equipped with a blower switch on the side of the control to provide "CONTINUOUS" or "CYCLED" blower operation. "CYCLED" blower will turn the blower on with the compressor. A unit-mounted electronic thermostat with a remote electronic thermistor located in the return air will control compressor operation in heating and cooling modes. Unit mounted thermostat shall be the standard thermostat option. All unit mounted thermostats shall be auto changeover. Manual changeover WILL NOT be accepted. Electromechanical operation WILL NOT be accepted. Controls Standard: A compressor control module (CCM) shall be included to disable compressor operation in the event of a trip of any of the safety switches and to send a signal to activate a fault indicator light at the thermostat. The CCM shall be capable of being reset from the thermostat or from the unit main disconnect switch. A terminal block with screw terminals shall be provided for field connection of all low-voltage wiring. An Aurora microprocessor-based controller that interfaces with a multi-stage electronic thermostat to monitor and control unit operation shall be provided. The control shall provide operational sequencing, blower speed control, high and low pressure switch monitoring, freeze detection, condensate overflow sensing, lockout mode control, LED status and fault indicators, fault memory, field selectable options and accessory output. The control shall provide fault retry three times before locking out to limit nuisance trips. A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal. Option: An Aurora Unitary Protocol Converter (UPC) shall be included that communicates directly with the Aurora Heat Pump Controls and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC shall convert the internal Aurora Modbus protocol to BACnet MS/TP, or N2 protocols for communication over a BAS system. Additional individual unit configuration items such freeze protection settings shall be directly available over the BAS without the need for access to the actual heat pump. Option: Aurora UPC DDC communication protocols: LonWorks Option: Remote mounted thermostat is available for CCM and Aurora Base Control. A terminal block with screw terminals will be provided for field control wiring. Piping Supply and return water connections shall be 1/2 in. [12.7 mm] FPT copper threaded fittings. All water piping shall be insulated to prevent condensation at low liquid temperatures. A stainless steel tube stubbed out from the chassis is provided for condensate drain attachment. A short piece of polyvinyl hose is supplied to assist in adapting to drain. WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 29 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Engineering Guide Specifications cont. Accessories Hose Kits Ball Valves (field-installed) A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A full port ball valve shall be provided with integral P/T (pressure/ temperature) port on supply hose. Specifications: Temperature range of 35°F [2°C] to 180°F [82°C]. Max. working pressure of 400 psi [2757 kPa] for 1/2 in. and 3/4 in. hose kits; max. working pressure of 350 psi [kPa] for 1 in. and 1-1/4 in. hose kits. Hose Kits Automatic Balancing and Ball Valves (field-installed) A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A full port ball valve shall be provided with integral P/T (pressure/ temperature) port on supply hose and automatic balancing valve with integral P/T ports and full port ball valve on return hose. and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A "y" strainer is provided on one end for fluid straining and integral "blowdown" valve.. A full port ball valve shall be provided with integral P/T (pressure/temperature) port on supply hose and automatic balancing valve with integral P/T ports and full port ball valve on return hose. Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C]. · Max. working pressure of 400 psi [2757 kPa] for 1/2 in. and 3/4 in. hose kits; max. working pressure of 350 psi [2413 kPa] for 1 and 1-1/4 in. hose kits. · Minimum burst pressure of four times working pressure. Auxiliary Heater (field-installed 208-230V units only) An electric resistance heater shall provide supplemental and/or emergency heating capability. A manual switch shall be mounted on the side of the control compartment with "NORMAL" or "BOILERLESS" mode. "NORMAL" will run the compressor when there is a call for heating or cooling. "BOILERLESS" mode operation will run electric heat whenever there is a call for heating and run the compressor for a cooling call. Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C]. · Max. working pressure of 400 psi [2757 kPa] for 1/2 in. and 3/4 in. hose kits; max. working pressure of 350 psi [2413 kPa] for 1 in. and 1-1/4 in. hose kits. · Minimum burst pressure of four times working pressure. Hose Kits Automatic Balancing and Ball Valves with `Y' strainer (field-installed) A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 30 Page _____ of _____ Contractor: Engineer: Project Name: P.O.: Unit Tag: Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz Revision Guide Pages: Cover 6 All All All 30 Description: Naming Update Updated Flat Top Dimensional Data Updated Nomenclature and Wiring Schematics (ABC and UPC Controls) Obsoleted PSC Option, Updated Nomenclature, Updated Wiring Schematics Updated With Aluminum Air Coils Added Revision Guide Date: By: 30 Jan 2022 JM 03 May 2016 MA 1 Sept 2015 MA 04 Mar 2015 MA 02 Mar 2014 DS 02 Mar 2014 DS WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com. SD1010CNB 01/22 31 Page _____ of _____Acrobat Distiller 21.0 (Macintosh)