Submittal Data

Versatec 300 & 500 Consoles | WaterFurnace

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 32 Pages, 2.90MB

Document DEVICE REPORTsd1010cnb
Console
FORMERLY ENVISION CONSOLE
R-410A Refrigerant 0.75-1.5 Tons
Submittal Data English Language/IP Units
SD1010CNB 01/22

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Model Nomenclature

1-2 3 4-5 6 7 8 9 10 11 12 13 14 15-16 17 NC S 09 L 0 1 1 C N N B 5 SS G
Model NC ­ Envision Series Console
Cabinet Configuration C ­ Chassis Only W ­ Chassis with Cabinet S ­ Chassis Slope Top E ­ Chassis with Extended Slope Top
Unit Capacity 09, 12, 15, 18
Piping Option L ­ Left R ­ Right
Voltage 0 ­ 208-230/60/1 2 ­ 265/60/1 9 ­ 115/60/1 (09 & 12)
Unit Control 1 ­ CCM A ­ AuroraTM Base Control (ABC) E ­ AuroraTM DDC UPC Controller F ­ AuroraTM DDC UPC Controller with LON
NOTES: Chassis only available with left piping option. UPC option is only available with remote wall-mounted thermostat control.

Vintage C ­ ECM Blower & Aluminum Air Coil G ­ Control Options "E" & "F"
Non-Standard Option Details SS ­ Standard Option
Air Coil/Insulation Option 5 ­ AlumiSealTM/Extended Range 6 ­ AlumiSealTM/Standard Range 7 ­ No Coating/Extended Range 8 ­ No Coating/Standard Range
Sound Kit A ­ None B ­ Blanket
Auxiliary Electric Heat N ­ None B ­ 1.0kW (09-12) C ­ 2.0kW (09-12) D ­ 3.0kW (15-18)
Motorized Outside Air Damper (Field Installed)
N ­ None M ­ Motorized Damper
Water Coil Option C ­ Copper N ­ CuproNickel
Thermostat Control 1 ­ Unit Mounted T-Stat 2 ­ Remote Wall-Mounted T-Stat

Voltage Availability

Voltage 09

115/60/1

·

208-230/60/1

·

265/60/1

·

Model

12

15

·

·

·

·

·

18
· ·
1/20/14

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

1

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

ARI/ISO 13256-1 Performance Ratings

ECM Motors
AHRI/ASHRAE/ISO 13256-1 English (IP) Units

Model

Flow Rate

Water Loop Heat Pump

Cooling EWT 86°F

Heating EWT 68°F

gpm

cfm

Capacity EER Capacity Btuh Btuh/W Btuh

COP

09

2.5 300 8,500

13.4

10,500

4.4

12

3.5 350 10,500 12.3

14,400

4.3

15

4.5 450 13,500 13.6

17,000 4.9

18

5.5 500 16,200 12.5

21,000

4.4

Ground Water Heat Pump

Cooling EWT 59°F

Heating EWT 50°F

Capacity EER Capacity Btuh Btuh/W Btuh

COP

10,200 22.5

8,700

3.8

12,400 19.5

11,800

3.7

16,200 22.0

14,000

4.1

19,000 19.6

17,000

3.7

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Heating capacities based upon 68°F DB, 59°F WB entering air temperature All ratings based upon operation at the lower voltage of dual voltage rated models.

Ground Loop Heat Pump

Cooling EWT 77°F

Heating EWT 32°F

Capacity EER Capacity Btuh Btuh/W Btuh

COP

9,000 16.0

6,700

3.1

11,000 14.2

9,500

3.5

14,200 15.9

10,500

3.4

16,600 15.1

13,300

3.1

12/14/09

All Envision Series product is Safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

2

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Blower Performance Data

ECM Motors

Model
09 12 15 18

Low Speed 300 300 350 350

CFM Medium Speed
325 325 450 450

High Speed 400 400 600 600

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

3

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Electrical Data

ECM Motor

Model

Rated Voltage

115/60/1

09

208-230/60/1

265/60/1

115/60/1

12

208-230/60/1

265/60/1

208-230/60/1 15
265/60/1

208-230/60/1 18
265/60/1

HACR circuit breaker in USA only

Voltage Min/Max
104/127 187/253 238/292 104/127 187/253 238/292 187/253 238/292 187/253 238/292

Compressor

MCC

RLA

LRA

12.5

8.0

50.0

6.4

4.1

21.0

6.7

4.3

22.0

14.8

9.5

50.0

7.7

4.9

25.0

7.0

4.5

22.0

9.2

5.9

29.0

7.8

5.0

28.0

10.4

6.7

33.5

8.7

5.6

28.0

Fan Motor FLA 4.25
2.6 2.5 4.25 2.6 2.5 2.6 2.5 2.6 2.5

Total Unit FLA 12.3 6.7 6.8 13.8 7.5 7.0 8.5 7.5 9.3 8.1

Min Circ Amp 14.3 7.7 7.9 16.1 8.8 8.1 10.0 8.8 10.9 9.5

Max Fuse/ HACR
20 10/15 10/15
25 10/15 10/15
15 10/15
15 15
1/20/14

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

4

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Auxiliary Heat Ratings

ECM Motors

Model

Rated Voltage

Voltage Min./Max.

Heater Element
Watts

Fan Motor FLA

09-12 (1 kW)
09-12 (2 kW)
15-18 (3 kW)

208/60/1 230/60/1 265/60/1 208/60/1 230/60/1 265/60/1 208/60/1 230/60/1 265/60/1

197/254 197/254 239/291 197/254 197/254 239/292 197/254 197/254 239/292

818 1000 1000 1636 2000 2000 2454 3000 3000

2.45 2.60 2.50 2.45 2.60 2.50 2.45 2.60 2.50

Always refer to unit nameplate data prior to installation.

Heater Element
FLA
3.93 4.35 3.77 7.86 8.70 7.55 11.80 13.04 11.32

Total Unit FLA
6.4 7.0 6.3 10.3 11.3 10.1 14.3 15.6 13.8

Min. Circuit Amp.
8.0 8.7 7.8 12.9 14.1 12.6 17.8 19.6 17.3

Max. Fuse/ Brkr.
10 15 10 20 25 20 30 35 30 10/5/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

5

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Flat Top Cabinet
NCW09-18 RIGHT RETURN

LEFT RETURN

TOP

D
A
FILTER BRACKET

E A

F

B

G

B

FILTER BRACKET C

DETAIL B
TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF (ONLY BREAK-OFF TAB OPPOSITE AS GRILLE LID AS SHOWN)
REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE ON BROKEN EDGE OF LEG AS SHOWN

H
FRONT

J
I
DETAIL B
TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF (ONLY BREAK-OFF TAB OPPOSITE AS GRILLE LID AS SHOWN)
REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE ON BROKEN EDGE OF LEG AS SHOWN

Overall Cabinet

Flat Top A B C

D

E

F

GH I J

Configuration Width Depth Height Grille Lid

Grille Length

Grille Width

in. 45.0 10.8 25.7 9.2

35.0

6.1 2.3 44.1 10.3 4.3

09-12

cm. 114.3 27.3 65.2 23.4

88.9

15.6 5.8 112.0 26.0 10.9

in. 50.0 12.3 25.7 9.2

35.0

6.1 3.3 49.1 11.8 4.3

15-18

cm. 127.0 31.1 65.2 23.4

88.9

15.6 8.3 124.7 29.8 10.9

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

6

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Slope Top Cabinet

NCS09-18

@756B@3BC@<

B=>

:34B@3BC@<

2
/
47:B3@0@/193B

3 /

4

0

5

0

47:B3@0@/193B

1

23B/7:/
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<

6
4@=<B

8 7

23B/7:0
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<

Overall Cabinet

Slope Top

AB C

D

Configuration Width Depth Height Grille Lid

in. 45.0 11.1 28.6 9.2

09-12

cm. 114.3 28.2 72.6 23.4

in. 50.0 12.6 29.1 9.2

15-18

cm. 127.0 32.0 73.9 23.4

E Grille Length
35.0 88.9
35.0 88.9

F Grille Width
6.1 15.6
6.1 15.6

GH I J
2.8 44.1 10.3 4.3 7.2 112.0 26.0 10.9 2.5 49.1 11.8 4.3 6.4 124.7 29.8 10.9

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

7

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Extended Slope Top Cabinet
NCE09-18

@756B@3BC@<

B=>

:34B@3BC@<

2

3

/

4
0 5

/

47:B3@0@/193B

23B/7:/
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<

6
4@=<B

1

47:B3@0@/193B

0

8
7
23B/7:0
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<

Overall Cabinet

Ext. Slope Top

Configuration

AB Width Depth

C H eight

D Grille Lid

E Grille Length

F Grille Width

G

H

I

J

in. 50.0 12.6 29.1 9.2

35.0

6.1 2.4 49.1 12.0 4.3

09-12

cm. 127.0 32.0 73.9 23.4

88.9

15.6 6.1 124.7 30.5 10.9

in. 55.0 12.6 29.1 9.2

35.0

6.1 2.5 54.1 11.8 4.3

15-18

cm. 139.7 32.0 73.9 23.4

88.9

15.6 6.4 137.4 29.8 10.9

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

8

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Right Return Controls Detail

1=<B@=:>/<3: @3;=D34=@/113AA B=1=<B@=:0=F
4/<=>B7=<AE7B16 3:31B@7163/B;=23 <=@;/:0=7:3@:3AA AE7B16=>B7=</: 2/;>3@=<=44AE7B16
1=;>@3AA=@ /113AA>/<3: @3;=D324=@ 1:/@7BG 0=B6A723A

47:B3@

6/<2G0=F
=>B7=</: 4CA32 <=<4CA32 27A1=<<31B
:=ED=:B/53 B3@;7</:A 4F@3;=B3E/:: AB/B=>B7=<A=<:G 1=<23<A/B3 2@/7<1=<<31B7=<
=>B7=</: 0/::D/:D3A =>B7=</: 6=A397BA

=>B7=</:0/19>:/B3 @3?C7@324=@ 2/;>3@7<AB/::/B7=<

=CBA723/7@ 2/;>3@=>B7=< 473:27<AB/::32

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

9

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Right Return Chassis

Data = inches (cm)

9.38 (23.8)

Models 09-12

37.88 (96.2) CONTROL PANEL

28.5 (72.4)

8.88 (22.6)

Models 15-18

42.88 (108.9) CONTROL PANEL

34.0 (86.4)

COMPRESSOR ACCESS PANEL

BLOWER ACCESS PANEL

1.5 (3.8) 1.5 (3.8)

FILTER

4.37 (11.1)

WATER OUT 1/2 FPT WATER IN 1/2 FPT

10.31 (26.2)
4.5 (11.4)

1.0 (2.5)

COMPRESSOR ACCESS PANEL

BLOWER ACCESS PANEL

WATER OUT 1/2 FPT WATER IN 1/2 FPT

FILTER
11.75 (29.8)
4.5 (11.4)

1.0 (2.5)

1.5 (3.8) 1.5 (3.8) 4.32 (11.0)

0.86 (2.2)
2.0 (5.1) 25.25 (64.1) 21.4 (54.4) 20.0 (50.8)

1.78 (4.5) 11.0 (27.9)

CONDENSATE DRAIN CONNECTION
43.37 (110.2) 28.0 (71.1)

OPTIONAL BACK PLATE

9.25 (23.5)

13.9 (35.3)

1.64 (4.2)
25.65 (65.2) 19.83 (50.4) 12.03 (30.6)

5.5 (14.0)

2.75 (7.0)

0.66 (1.7)

DAMPER OPENING

COMPRESSOR ACCESS PANEL

0.86 (2.2) 2.0 (5.1) 25.25 (64.1) 20.6 (52.3) 19.5 (49.5)
CONDENSATE DRAIN CONNECTION
48.25 (122.6) 33.0 (83.8)

12.0 (30.5)

OPTIONAL BACK PLATE

11.78 (29.9)

13.9 (35.3)

1.62 (4.1)
25.80 (65.5) 20.0 (50.8) 12.18 (30.9)

5.4 (13.7)

2.75 (7.0)

0.83 (2.1)

DAMPER OPENING

COMPRESSOR ACCESS PANEL

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

10

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Left Return Controls Detail

1=;>@3AA=@ /113AA>/<3: @3;=D324=@ 1:/@7BG 0=B6A723A

1=<B@=:>/<3: @3;=D34=@/113AA B=1=<B@=:0=F

:=ED=:B/53 B3@;7</:A 4F@3;=B3E/:: AB/B=>B7=<A=<:G

2/;>3@=<=44AE7B16
3:31B@7163/B;=23 <=@;/:0=7:3@:3AA AE7B16=>B7=</:
4/<=>B7=<AE7B16

=>B7=</: 4CA32 <=<4CA32 27A1=<<31B
=>B7=</: 0/::D/:D3A

=>B7=</: 6=A397BA

=>B7=</: 3:31B@7163/B
6/<2G0=F 47:B3@ 1=<23<A/B3 2@/7<1=<<31B7=<

=>B7=</:0/19>:/B3 @3?C7@324=@ 2/;>3@7<AB/::/B7=<

=CBA723/7@ 2/;>3@=>B7=< 473:27<AB/::32

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

11

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Dimensional Data - Left Return Chassis

Data = inches (cm)

Models 09-12

28.5 (72.4)

37.88 (96.2) CONTROL PANEL

9.38 (23.8)

Models 15-18

34.0 (86.4)

42.88 (108.9) CONTROL PANEL

8.88 (22.6)

1.50 (3.8) 1.50 (3.8)

BLOWER ACCESS PANEL

COMPRESSOR ACCESS PANEL

4.37 (11.1)

FILTER

WATER OUT 1/2 FPT WATER IN 1/2 FPT

10.31 (26.2)
4.5 (11.4)

1.00 (2.5)

1.50 (3.8) 1.50 (3.8)

BLOWER ACCESS PANEL

COMPRESSOR ACCESS PANEL

4.32 (11.0)

FILTER

WATER OUT 1/2 FPT WATER IN 1/2 FPT

11.75 (26.2)
4.5 (11.4)

1.00 (2.5)

0.86 (2.2)
2.0 (5.1) 25.25 (64.1) 21.4 (54.4) 20.0 (50.8)

1.78 (4.5) 11.0 (27.9)

1.62 (4.1)
25.65 (65.1)
19.83 (50.4)
12.03 (30.5)

CONDENSATE DRAIN CONNECTION
43.37 (110.2)
28.00 (71.1)

OPTIONAL BACK PLATE

2.75 (7.0)

13.90 (35.3)

9.25 (23.5)

COMPRESSOR ACCESS PANEL

0.66 (1.7)

DAMPER OPENING

5.50 (14.0)

0.86 (2.2)
2.0 (5.1) 25.25 (64.1) 20.6 (52.3) 19.5 (49.5)

12.0 (30.5)

1.62 (4.1)
25.80 (65.5)
20.0 (50.8)
12.18 (30.9)
COMPRESSOR ACCESS PANEL

CONDENSATE DRAIN CONNECTION
48.25 (122.6)
33.0 (83.8)

OPTIONAL BACK PLATE

2.75 (7.0)
0.83 (2.1)

13.90 (35.3)

11.78 (29.9)

DAMPER OPENING

5.50 (14.0)

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

12

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Physical Data

Model

Compressor (1 each) Factory Charge R410A, oz [kg]
Fan Motor & Blower Fan Motor Type/Speeds
Fan Motor- hp [W]

ECM ECM

Blower Wheel Size (Dia x W), in. [mm] ECM

Coax and Water Piping Water Connections Size - FPT - in [mm]
Coax & Piping Water Volume - gal [l] Consoles

Air Coil Dimensions (H x W), in. [mm]
Air Coil Total Face Area, ft2 [m2] Air Coil Tube Size, in [mm] Air Coil Number of rows
Filter Standard - 1" [25.44mm] Weight - Operating, lb [kg] Weight - Packaged, lb [kg]

09 27 [0.77]

Consoles

12

15

LG Rotary

27 [0.77]

36 [1.02]

18 34 [0.96]

0.25 [186]
5.75 x 5.5 [146 x 140]

3 Speeds

0.25 [186] 0.25 [186]

5.75 x 5.5 [146 x 140]

6.0 x 6.5 [152 x 165]

0.25 [186]
6.0 x 6.5 [152 x 165]

1/2" [12.7] 0.15 [0.6]

1/2" [12.7] 0.18 [0.7]

1/2" [12.7] 0.35 [1.3]

1/2" [12.7] 0.35 [1.3]

8 x 22 [203 x 559]
1.2 [0.114] 3/8 [9.5]
3 1 - 10 x 28 [254 x 711] 210 [91] 220 [100]

8 x 22 [203 x 559]
1.2 [0.114] 3/8 [9.5]
3 1 - 10 x 28 [254 x 711] 210 [95] 220 [100]

8 x 30 [203 x 762]
1.7 [0.155] 3/8 [9.5]
4 1 - 12 x 33 [305 x 838] 230 [102] 240 [109]

8 x 30 [203 x 762]
1.7 [0.155] 3/8 [9.5]
4 1 - 12 x 33 [305 x 838] 235 [107] 245 [111]
1/20/14

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

13

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Reference Calculations

Heating Calculations:

LWT = EWT -

HE

GPM x 500

Cooling Calculations:
HR LWT = EWT +
GPM x 500

HC LAT = EAT +
CFM x 1.08 TH = HC + HWC

LAT(DB) = EAT(DB) - SC CFM x 1.08
LC = TC - SC
SC S/T =
TC

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Definitions
ABBREVIATIONS AND DEFINITIONS:
CFM = airflow, cubic feet/minute EWT = entering water temperature, Fahrenheit GPM = water flow in gallons/minute WPD = water pressure drop, PSI and feet of water EAT = entering air temperature, Fahrenheit
(dry bulb/wet bulb) HC = air heating capacity, MBTUH TC = total cooling capacity, MBTUH SC = sensible cooling capacity, MBTUH KW = total power unit input, kilowatts HR = total heat of rejection, MBTUH

HE = total heat of extraction, MBTUH HW = desuperheater capacity, MBTUH EER = Energy Efficient Ratio
= BTU output/Watt input COP = Coefficient of Performance
= BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBTUH LC = latent cooling capacity, MBTUH S/T = sensible to total cooling ratio

Operating Limits

Operating Limits
Air Limits Min. Ambient Air Rated Ambient Air Max. Ambient Air Min. Entering Air Rated Entering Air db/wb Max. Entering Air db/wb
Water Limits Min. Entering Water Normal Entering Water Max. Entering Water

Cooling

(°F)

(°C)

45 80 100 50 80.6/66.2 110/83

7.2 26.7 37.8 10.0 27/19 43/28.3

30 50-110
120

-1.1 10-43.3
48.9

Heating

(°F)

(°C)

45

7.2

70

21.1

85

29.4

40

4.4

68

20.0

80

26.7

20 30-70
90

-6.7 -1.1 32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

14

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Correction Factor Tables

EA Corrections Cooling Capacity Corrections

Entering

Total

Air WB ºF Clg Cap

55 60 65 66.2 67 70 75

0.898 0.912 0.967 0.983 1.000 1.053 1.168

60 0.723

Sensible Cooling Capacity Multipliers - Entering DB ºF

65

70

75

80 80.6 85

90

95

0.866 1.048 1.185

*

*

*

*

*

0.632 0.880 1.078 1.244 1.260

*

*

*

0.694 0.881 1.079 1.085 1.270

*

*

0.655 0.842 1.040 1.060 1.232

*

*

0.616 0.806 1.000 1.023 1.193 1.330

*

0.693 0.879 0.900 1.075 1.250 1.404

0.687 0.715 0.875 1.040 1.261

Note: * Sensible capacity equals total capacity at conditions shown.

100 * * * * * *
1.476

Power Heat of Input Rejection

0.985 0.994 0.997 0.999 1.000 1.003 1.007

0.913 0.927 0.972 0.986 1.000 1.044 1.141 11/10/09

Heating Capacity Corrections

Ent Air DB °F

Heating Corrections

Htg Cap

Power Heat of Ext

45

1.062

0.739

1.158

50

1.050

0.790

1.130

55

1.037

0.842

1.096

60

1.025

0.893

1.064

65

1.012

0.945

1.030

68

1.005

0.976

1.012

70

1.000

1.000

1.000

75

0.987

1.048

0.970

80

0.975

1.099

0.930

11/10/09

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

15

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Antifreeze Corrections
Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.

Antifreeze Type

Antifreeze % by wt

Cooling Capacity

Heating Capacity

Pressure Drop

EWT - degF [DegC]

90 [32.2]

30 [-1.1]

30 [-1.1]

Water Ethylene Glycol Propylene Glycol Ethanol Methanol

0

1.000

10

0.991

20

0.979

30

0.965

40

0.955

50

0.943

10

0.981

20

0.969

30

0.950

40

0.937

50

0.922

10

0.991

20

0.972

30

0.947

40

0.930

50

0.911

10

0.986

20

0.970

30

0.951

40

0.936

50

0.920

1.000
0.973 0.943 0.917 0.890 0.865 0.958 0.913 0.854 0.813 0.770 0.927 0.887 0.856 0.815 0.779 0.957 0.924 0.895 0.863 0.833

1.000
1.075 1.163 1.225 1.324 1.419 1.130 1.270 1.433 1.614 1.816 1.242 1.343 1.383 1.523 1.639 1.127 1.197 1.235 1.323 1.399

Warning: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent.

Antifreeze Correction Example
Antifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F and 90°F respectively as well as pressure drop at 30°F for an Envision Console Series NC*18.
The corrected cooling capacity at 90°F would be: 17,100 MBtuh x 0.969 = 16,569 MBtuh
The corrected heating capacity at 30°F would be: 14,300 MBtuh x 0.913 = 13,056 MBtuh
The corrected pressure drop at 30°F and 5.5 GPM would be: 18.2 feet of head x 1.270 = 23.1 feet of head

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

16

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

NC09

!@ObSR14;6SObW\U1]]ZW\U

3EB 4

4Z]e @ObS 5>;

EObS` >`Saac`S2`]^
>A7 4B62

61 Y0bcV

63/B7<53/B%4

>]eS`

63

:/B

YE Y0bcV

4





#



&

"

#$

=^S`ObW]\\]b`SQ][[S\RSR

#

!&

&&

$&

$

"&

&'





!

=^S`ObW]\\]b`SQ][[S\RSR

!

&

!

#"

$'

$

"&

&'!

#

!&

&&

%!

$!

#

'#







%$

$

##

'#

"

&

!

#

%'

$

#&

' "

#

!&

&%

&!

$"

$

'!%



'



&&

$#

$$

'#

#

&



#

'

$#

$'

'$

#

!%

&#

'"

$$

%

'%



'



!

$&

&

''&

$

&



"'

#

$&

&

#

#

!$

&!

&

$'

&#

!



&

&

&

%

'"

"#

%

&



"%

 

%

'$

#

#

!#

&

 

%

'&

#%



&

%

 %

%!



%!

&

&



"$

 '

%"

"

%'

#

!"

%'

!

%#

#

&"



%

$

!$

%$





'

&

'

""

!&

%%



$

#

!!

%$

"

%&

!





%

#



&

&

"!

#

!

%"



$

#



&

&

"

=^S`ObW]\\]b`SQ][[S\RSR

#

!

%



$

"

 

&

%

"

#

!

$'

1=>
!!#
!!& !" !$! !% !& " "& "% ""$ "#! "$ "&& "'! "'' # # #! # " # # # $

>S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV

1==:7<53/B&$%4

B1 Y0bcV

A1 Y0bcV

AB @ObW]

>]eS` 6@ YE Y0bcV

33@

=^S`ObW]\\]b`SQ][[S\RSR

=^S`ObW]\\]b`SQ][[S\RSR

 

%!

$

!&

!"

!&

 

%"

$

!$

!"

!!'

=^S`ObW]\\]b`SQ][[S\RSR

#

%

$

"

 '

&

$

%

$

!'

 '

!

%

$&

$!

"#

 !

!$

'

$'

$!

""

 !

"'



%

$"

"

 "

$$

"

$%

$"

#

 

''

#

$%

$"

#

 



%

$'

$"

"%

 !

"



$#

$#

#'

 

%



$$

$#

#$

 

&

!

$%

$#

#"

 

'

'#

$!

$%

$#

%

"#

'$

$#

$%

$

%

##

''

$#

$$

$

'

$"

'

$

$%

%

$

 %

'!

$

$%

$'

%

!#

'"

$!

$%

$%

%

"

=^S`ObW]\\]b`SQ][[S\RSR

'

$

$%

%$

$

&

'

$

$%

%"

$

 !

=^S`ObW]\\]b`SQ][[S\RSR

&$

#&

$%

&!

#

"

&%

#'

$&

&

#

%

=^S`ObW]\\]b`SQ][[S\RSR

&

##

$%

'

!

'

&!

#$

$&

&&

!

'#

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

17

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

NC12

!#@ObSR14;6SObW\U1]]ZW\U

3EB 4

4Z]e @ObS 5>;

EObS` >`Saac`S2`]^
>A7 4B62

61 Y0bcV

63/B7<53/B%4

>]eS`

63

:/B

YE Y0bcV

4

#



!



!

%

"

=^S`ObW]\\]b`SQ][[S\RSR

!#

!

%"

&$

&

#'

'&

#

'



=^S`ObW]\\]b`SQ][[S\RSR

!

!

%

!&



&#

%

'"!

!#

!

$'



&$

%!

'#

#

'



&

&&

%&

'$%

"

!

$

!%



&&

&

'%

!#

'

$$

!

&'

&

'%&

#

&

&

'

'

&&

''$

#

!

#

!#

 

'

'



!#

%

$

 !

'

'

$

#

&

%

!

'"

 !

$

!

"

!!

!"

'"



!"

!#

$

$

!%

'$

"

"

#

%

$

"#

'%



$"

%

!

"

!

"%

'&

"

$'

!#

#

#&

#



$

%%

#

%

#

#$

!

 

'"

&

!

!

!

#'

"

 !



!#

#

#%

$

#

 #

$

#

$

"

$%

%

!

 

'

!

!

'

$'

'

!

 &

!#

"

##

%



!"

!#

#

$

!



!



&

!#

!

#!

#

#





!



$

=^S`ObW]\\]b`SQ][[S\RSR

!#



#

#

#



 

!



#

!#



"'

1=>
!#
!"" !"& !$ !$$ !% !&$ !&' !'" "" "$ "' "!' "" "" ""# ""& "# "## "#$ "#%

>S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV

1==:7<53/B&$%4

B1 Y0bcV

A1 Y0bcV

AB @ObW]

>]eS` 6@ YE Y0bcV

33@

=^S`ObW]\\]b`SQ][[S\RSR

" ""
!% !' ! ! !!      "  ! # $ '   " #
'% '&
&' '
&# &%

=^S`ObW]\\]b`SQ][[S\RSR

'&

$'

"#

#&



$'

"

#'

=^S`ObW]\\]b`SQ][[S\RSR

'#

%

#"

##

'%

%

#

#$

'

%

$"

#

'

%

$

#

'"

%

#&

#!

&$

%

%

"#

&%

%

$&

"#

&'

%

$#

"$

&

%

%%

!&

&

%

%#

!&

&!

%

%

!'

%&

%!

&"

!#

%'

%!

&

!$

&

%!

%&

!%

%#

%!

'

!"

%$

%"

&&

!"

%%

%!

&#

!"

=^S`ObW]\\]b`SQ][[S\RSR

%!

%#



!

%"

%#

'%

!

=^S`ObW]\\]b`SQ][[S\RSR

$'

%%



 %

%

%%

&

 &

=^S`ObW]\\]b`SQ][[S\RSR

$%

%'

 

 $

$&

%&

&

 %

!$ !"
## %$  
& % %& ' "" # $!  $ !# "  &  "
'% 
& &"
% %"

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

18

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

NC15

"#@ObSR14;6SObW\U1]]ZW\U

3EB 4

4Z]e @ObS 5>;

EObS` >`Saac`S2`]^
>A7 4B62

61 Y0bcV

63/B7<53/B%4

>]eS`

63

:/B

YE Y0bcV

4



&

"



!

!"

%&

=^S`ObW]\\]b`SQ][[S\RSR

"#

#'

!$

%

'!

%#

'



%

!'

=^S`ObW]\\]b`SQ][[S\RSR

!

!

!!

%$

&

'#

&#

' 

"#

#%

!

 !

'%

'

'!!



%

!&

 %

'#

'"

'"

"

!

!

%#

 '

'$

'$

'"$

"#

#$

 '

!"

'&



'#$



$

!%

!'

'#

$

'$#

#

!

!

%!

"

'%

&

'%

"#

##

 %

"$

''



'%'



$

!$

#

'$

 

''"

$

!

!

%

#$

'%

 



"#

#"

 #

$



 %





#

!#

$$

'$

!!

 

%

!

!

%

%

'&

!%

!

"#

#!

 

%$



"

"



#

!"

&!

!

"&

#%

&

!

!

$&

&$

"

#

$!

"#

#

 

&'

#

#!

$&



"

!

'$

%

#'

&!

'

!

'

$%

''

'

$

&'

"#

#

&





$"

'#



"

!



!

&

$#

"#

#

$



!

!



!

&

$"

=^S`ObW]\\]b`SQ][[S\RSR

"#

"'

!



!

'

 

!

%

$

"#

"&



1=>
!!%
!$ !% !'! !'" " " % " & "! "$$ "$' "% ## #& # # # " # $ #!# #!$ #!&

>S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV

1==:7<53/B&$%4

B1

A1

Y0bcV Y0bcV

AB >]eS` 6@

@ObW]

YE Y0bcV

33@

=^S`ObW]\\]b`SQ][[S\RSR

=^S`ObW]\\]b`SQ][[S\RSR

%

 

%

"&

&%

!#$

%!

 "

%

"#

&'

!&"

=^S`ObW]\\]b`SQ][[S\RSR

$%

 

%

$

&&

%&

%

 

%

#%

&'

!

$

%

%

%#

&&

#

$"

&

%

%

&&

$

$$

 

%

$&

&'

""

##

"

%"

&"

&!

&!

#$

#

%"

&

&"

'

#'

&

%"

%%

&#

%

"%



%$

'"

%'

#%

"'

!

%$

'

&

$#

#

#

%$

&$

&

%&

"

'

%%



%$

"

"#



%%

'$

%%

#

"%



%$

'!

%&

#&

!%

$

%%

&

%"

 %

!'

&

%&

!

%"

!#

"

'

%%



%#

"

=^S`ObW]\\]b`SQ][[S\RSR

!"

#

%&

"

%!

&

!$

$

%&



%!

 !

=^S`ObW]\\]b`SQ][[S\RSR

 &



%'

 !

%

"

!

!

%'

 

%

&

=^S`ObW]\\]b`SQ][[S\RSR

!

'

&

!'

$

&

#

'!

&

!#

$

&#

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

19

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

NC18

#@ObSR14;6SObW\U1]]ZW\U

3EB 4

4Z]e @ObS 5>;

EObS` >`Saac`S2`]^
>A7 4B62

61 Y0bcV

63/B7<53/B%4

>]eS`

63

:/B

YE Y0bcV

4

!

&

"



"

"

'%

=^S`ObW]\\]b`SQ][[S\RSR

##

&

&#

!

 

&'

' 

!

%

!'

=^S`ObW]\\]b`SQ][[S\RSR

!

"

"

'$

"

 "



'"!

##

%'

&

"!

 #



'"#

!

%

!&

##

 $



'$%

"

"

"

'"

#&

 %

#

'%!

##

%&

%'

$

 &

&

'&

!

$

!%

%

 &

 &

'''

#

"

"

'

%$

 '

!

#

##

%$

%$

&

!

!$

#

!

$

!$

'

!

"&

!$

$

"

!'

'

'%

!

#

""

##

%#

%!

!

!"

#%

#$

!

#

!#

!

!

$&

%"

%

"

!'

&'

&

!"

%

&!

##

%"

%

#

!%

%&

'%

!

#

!"

!!

"

&$



&

"

!&

&&

!%

"

&'

'

##

%!

$'

"

"!

'

 "

!

"

!

"%

""

'&

!&

'

"

!%

&$

#

"$



"#

##

%

$$

##

"&

#

#

!

"

!



"

!%

&#

##

%

$!

!

!

!



"

!$

&!

=^S`ObW]\\]b`SQ][[S\RSR

##

$'

#'

!

!

'

 

"

!#

&

##

$&

#%

1=>
!$
!!# !!$ !$ !$# !% !'! !'& "# "!! "!% ""! "% "%# "& "&& "' "'! #! #" #$

>S`T]`[O\QSQO^OQWbWSaaV]e\W\bV]caO\Ra]T0bcV

1==:7<53/B&$%4

B1 Y0bcV

A1 Y0bcV

AB @ObW]

>]eS` 6@ YE Y0bcV

33@

=^S`ObW]\\]b`SQ][[S\RSR

 #
! % ! # & ' ' '# %$ %& & % %" %% $$ $' %
$" $$
#& $
"% #

=^S`ObW]\\]b`SQ][[S\RSR

$

%

$'

"$

$!

%

$#

"%

=^S`ObW]\\]b`SQ][[S\RSR

##

%

%'

"

#&

%!

%#

"

"&

%!

'!

!#

"'

%!

&'

!#

#

%!

&"

!%

!'

%!



"

"

%!

'%

#

""

%"

'

$

!

%"

'

!

!

%"

$

#

!#

%"



$

 '

%#

 #

!

!

%#

'

#

!

%#

#

$

 $

%$

"

"

 &

%$

!"

#

 '

%#

!

#

=^S`ObW]\\]b`SQ][[S\RSR

 #

%$

"'

#

 $

%$

""

#

=^S`ObW]\\]b`SQ][[S\RSR

 

%%

$

!

 !

%%

#&

"

=^S`ObW]\\]b`SQ][[S\RSR

%

&

%%

&

'

%'

%

'

!  !"$
$' ' ' ! "& &% '%  $ $' & !% "% #! &  $ !
 #
'% 
&! &%

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

20

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Wiring Schematics

CCM - with ECM Motor and Electronic Stat

208-230-265/60/1

ECM Motor

Compressor

Green/Yellow

ECM Motor Module

Note 4

Red Black

Blue S

C R

Red

Blk

Tan (33)

Ground Lug
Handi - Box

T2

T1

CC

L2

L1

Brown (26)
Black (31) Red (32)

Unit Power Supply 208-230/60/1 or 265-277/60/1
G

White Yellow Blue Y LP LP HP HP CC CG LO R C Y LP LP HP HP CC CG LO R C

Fan Switch

High Low

4 Black (25)
RB

2 Black (27) 5
Brown (26)

Red (19)

Black

NOTE 1 Red

Blue

208V

230V

265V

Transformer

PB

24V

1

Yellow Black/White

Yellow (13)
Electronic THERMOSTAT IN PUT

Mode Switch Red (19)
4 5

6 1 Auto
2 3 Fan
White (18) Red (17) Red (11)

Ther

Black

ST

mistor

Black

T

Yellow (10)

Black (12) Black (22)

2 NOTE 2
3
Green (00)

HP
LP
FS NOTE 3

Black/White (1) Red (2) Brown (3) Violet (4) Violet (5) Black (6) Black (7) Blue (8) Blue (9) Yellow (10)

TEST PIN
COMPRESSOR CONTROL MODULE

A Heat T1
T2 T3
T4 T5
T6
B Cool

Red 24 V

AC

Black (12)

T3 Red (11)
Red T1
Orange
T2

T4

T6

T5 SHUT DOWN

Red (15) Red (16)

Red (17)

Fan Mode Sw Continuous

White (18) Black (22)

1

3

White (20)

RB

Yellow (13) Orange (14)

Cycled

RV

Orange (21)

Violet (5) Violet (4)

Damper Switch

ON

CC

White (34)

Blk/Wht (23)

Blk/Wht (24)

OFF

Blue (T6) 24VAC
Shutdown
Yellow (13)

Not Used

NC*09 NC*12 NC*15 NC*18

CHART 1 Blower Sengs

High

Low

Yellow

White

Blue

Yellow

Yellow

White

Blue

Yellow

Blue/Wht (36) 24 V Accessory

Damper Motor
D

Blue/Wht (35) DT

1 3 2
J1 Overide Shut down

Legend

Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring
Quick connect terminal
Wire nut

CC - Compressor Contactor DT - Damper Terminal Block FS - Freeze Sensing Device HP - High Pressure Switch LP - Low Pressure Switch PB - Power Block
RB - Blower Relay RV - Reversing Valve Coil ST - Entering Air Temperature Sensor

L1 P

Field wire lug Earth Ground Relay Contacts N.O., N.C.
Polarized connector

HP

Switch - High Pressure

LP Switch - Low Pressure

Relay coil

Capacitor

T

Thermistor

Temperature Switch

Notes:
1. Switch Red and Blue wires for 208 volt operation 2. Terminal C of 24 V PB is used as "L" output for Brown wire 3 for Lockout. 3. Optional field installed freeze sensing device. 4. Factory wired. Refer to blower table settings.

Page 1 WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and
specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

21

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Wiring Schematics cont.

CCM - with ECM, Electronic Heat and Electronic Stat

208-230-265/60/1

ECM Motor

Green/Yellow

ECM Motor Module

Note 5

Blue

White

White

T2

T1

EH

L2

L1

Blue (40) Tan (41)

Compressor

Blue S

C R

Red

Blk

Tan (33)

Ground Lug
Handi - Box

Blue (40)

T2

T1

CC

L2

L1

Brown (26) Black (31)

Unit Power Supply 208-230/60/1 or 265-277/60/1
G

White Yellow Blue Y LP LP HP HP CC CG LO R C Y LP LP HP HP CC CG LO R C

Fan Switch
High

Black (25)

Red Black
4
RB

2 Black (27)
5 Brown (26)

Tan (41)

Red (32)
Black
Blue 230V 265V

NOTE 1 Red 208V
Transformer

Low
Yellow (44) Yellow (13)
Electronic THERMOSTAT IN PUT
A Heat T1
T2 T3
T4 T5
T6 B Cool

Red (19)

Mode Switch Red (19) 4
5

1

3

E1

Black (12) Black (22)
Gray (42)

6 1 Auto
2 3 Fan

AQ

NOTE 4

Normal

White (18) Red (17) Red (11)

Ther

Black

ST

mistor

Black

T

Red 24 V

AC

Black (12)

T3 Red (11)
Red T1
Orange T2

T4

T6

Brown (43)

EHS Blue (T6)

Red

Fan Mode Sw

(17)

Continuous

White (18)

1

3

White (20)

RB

Yellow (13) Orange (14) Blue (T6)

Cycled RV

Yellow (44) Orange (21)

PB

24V

1 Yellow

2 NOTE 2

3 Black/White

Green (00)

HP
LP
FS NOTE 3

Black/White (1) Red (2) Brown (3) Violet (4) Violet (5) Black (6) Black (7) Blue (8) Blue (9) Yellow (10)

TEST PIN
COMPRESSOR CONTROL MODULE

Violet (4) Red (39)
Violet (5)

EH

Blue (38) 2

4

E1
5 Black (37)

CC

Blk/Wht (23)

White (34) Damper Switch

Blk/Wht (24)

ON

T5 SHUT DOWN

Red (15)

24VAC Shutdown

Red (16)

Blue/Wht (36)

NC*09 NC*12 NC*15 NC*18

CHART 1

Blower Sengs

High

Low

Yellow

White

Blue

Yellow

Yellow

White

Blue

Yellow

24 V Accessory
Damper Motor
D

OFF
Blue/Wht (35) DT

1 3 2
J1 Overide Shut down

LegLeegnednd

Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring
Quick connect terminal
Wire nut

AQ - Aquastat CC - Compressor Contactor DT - Damper Terminal Block E1 - Electric Heat Relay EH - Electric Heat Contactor EHS ­ Electric Heat Switch FS - Freeze Sensing Device HP - High Pressure Switch LP - Low Pressure Switch PB - Power Block
RB - Blower Relay RV - Reversing Valve Coil ST - Entering Air Temperature Sensor

L1 P

Field wire lug Earth Ground Relay Contacts N.O., N.C.
Polarized connector

HP

Switch - High Pressure

LP

Switch - Low Pressure

Relay coil

Capacitor

T

Thermistor

Temperature Switch

Notes:
1. Switch Red and Blue wires for 208 volt operation 2. Terminal C of 24 V PB is used as "L" output for Brown wire 3 for Lockout.
3. Optional field installed freeze sensing device.
4. Optional field installed aquastat.
5. Factory wired. Refer to blower table settings.

Page 1
WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

22

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Wiring Schematics cont.
ABC and UPC - ECM with Remote Stat

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz
208-230-265/60/1

ECM Motor Module
Grn

ECM Motor

Compressor

S C

Blue

R

Red Tan

Black

Handi - Box

Ground Lug

Unit Power Supply 208-230/60/1 or
265/60/1
G

White Yellow Blue

Note 2
Fan Speed Switch

High

Low

Gray/White Damper Switch
Off
White (34) On
Blue /Wht (35)

DT

D Damper Motor

Blue /Wht (36)

RB 42

Red Black
Black

Black (13)

RB

White (12)

Violet (14)

CC

Black (15)

Orange (01)

Orange (02)

RV

Yellow T
Yellow

Gray T
Gray

Blue (07)

Blue (08)

Black (09)

T2

T1

CC

L2

L1

Black

White Black
Blue 230V/265V

Note 1

Red 208V

RV FD LAT LP HP

Transformer

Black (10)

Black/White

P9 EH1 CC2 CC F C

P2

ES

LS

ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1
R

Com2 LED5
G RS485 NET

C

P8

K1-RV Relay

K3-CC2 Relay K2-CC Relay K4-Fan Relay
JW2

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS P4

C

R F1-3A

F

Aurora Base Control (ABC)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R - + P7

RS485 EXP C R - + P6 CO C EH1 C EH2 P3

Status LED3
G

PWM CFM

Fault

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Single

6

L Output Type

7

Future Use

8

SW2

Config

LED2

Y

Y1 G CC

Green (00)
Red Black/White

MV Note 3

Black/White

From UPC

Brown (23) Condensate

ES Yellow

Yellow

ES

Red

Red

24V Emergency Shutdown

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

23

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Wiring Schematics cont.

ABC and UPC - ECM with Remote Stat

Notes:
1 ­ Swap blue and red leads for 208V operation. 2 ­ Factory wired. Refer to blower table settings. 3 - When field installed 24VAC motorized valve is used, connect
to C and Y.

NC*09 NC*12 NC*15 NC*18

CHART 1

Blower Sengs

High

Low

Yellow

White

Blue

Yellow

Yellow

White

Blue

Yellow

Legend

Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal

T

Thermistor

Relay Coil

Switch - Condensate Overflow Switch - High pressure Switch - Low pressure

1 2 3

L1

Field Wiring Lug

Polarized connector

Ground Relay Contacts ­ N.O., N.C. Capacitor Fuse

G

Light Emitting Diode - Green

Y

Light Emitting Diode - Yellow

Temperature Switch

R

Light Emitting Diode - Red

Wire nut

CC ­ Compressor Contactor CO ­ Condensate Overflow Sensor ES ­ Emergency Shutdown HP ­ High Pressure Switch LP ­ Low Pressure Switch FD ­ Freeze Detection Sensor F1 ­ Fuse

SW1 ­ Push button SW2 ­ DIP package 8 position PB ­ Power Block RB ­ Blower Relay RV ­ Reversing Valve Coil

208-230-265/60/1

Accessory Relay

Operation

SW2-4 SW2-5

Cycle with Blower

On On

Cycle with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Aurora Timing Events

Event

Normal Mode

Random Start Delay

5 to 80 seconds

Compressor On Delay

5 seconds

Compressor Minimum On Time

2 minutes

Compressor Short Cycle Delay

4 minutes

Blower Off Delay

30 seconds

Fault Recognition Delay ­ High Pressure

Less than 1 second

Start-Up Bypass ­ Low Pressure

2 minutes

Fault Recognition Delay ­ Low Pressure

30 seconds

Start-Up Bypass ­ Low Water/Air Coil Limit

2 minutes

Fault Recognition Delay ­ Low Water/Air Coil Limit

30 seconds

Fault Recognition Delay ­ Condensate Overflow

30 seconds

Thermostat Call Recognition Time

2 seconds

Auxiliary Heat Staging Delay

5 minutes

Emergency Heat Staging Delay

2 minutes

Water Valve Slow Open Delay

90 seconds

Reheat Delay

30 seconds

Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds

Aurora LED Flash Codes

Slow Flash 1 second on and 1 second off

Fast Flash 100 milliseconds on and 100 milliseconds off

Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating

Random Start Delay

Status LED (LED1, Green)

Fast Flash

Configuration LED (LED2, Yellow)

Fast Flash

Fault LED (LED3, Red)

Fast Flash

Status LED (LED1, Green)

Configuration LED (LED2, Yellow)

Fault LED (LED3, Red)

Normal Mode

ON

No Software Overide Flash ECM Setting Normal Mode

OFF

Control is Non-Functional

OFF DIP Switch Overide

Slow Flash Input Fault Lockout

Flash Code 1

Test Mode

Slow Flash ECM Configure Mode

Fast Flash High Pressure Lockout

Flash Code 2

Lockout Active

Fast Flash Reset Configure Mode

Off

Low Pressure Lockout

Flash Code 3

Dehumidification Mode

Flash Code 2

Low Air Coil Limit Lockout - FP2 Flash Code 4

Reserved

Flash Code 3

Low Water Coil Limit Lockout - FP1 Flash Code 5

Reserved

Flash Code 4

Reserved

Flash Code 6

Load Shed

Flash Code 5

Condensate Overflow Lockout

Flash Code 7

ESD

Flash Code 6

Over/Under Voltage Shutdown

Flash Code 8

Reserved

Flash Code 7

Reserved

Flash Code 9

Reserved

Flash Code 10

Air/Water Coil Limit Sensor Error Flash Code 11

PWM CFM
C

CC2 Factory Factory Use

HP P4

ECM PWM

HP

P13

LP

LP

FP2

Factory

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

G

P5

LO

HI

CCG

CC

FG

F

R

F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1 JW2 Alarm
P2

Field Connections

Off LED1 FP1 ­ 15oF/30oF

On 1 LED2

R FP2 ­ 15oF/30oF

2Y

Fault

RV ­ B/O

ACC ­ Dip 4

LED3 G

ACC ­ Dip 5 CC ­ Dual/Single L ­ Pulse/Continuous

Status

Reheat/Normal

3 Config
4
5
6
7
8

SW2

AURORA BASE CONTROLTM
Com1 G

EH1
P3 EH2 C
EH1 C CO N/A

Factory

RS485 Exp

P6

(+)

(-)

R

C

P7

(+)

RS 485

(-)

R

C

P11

P8

Com2 G

P9

Factory Fan Connection

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Field Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

RS485 NET CC C

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

24

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Wiring Schematics cont.
ABC - ECM with Electric Heat and Remote Stat

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz
208-230-265/60/1

ECM

Blue

ECM Motor Module

Motor

Grn

Note 2 Fan Speed
Switch
High

White Yellow Blue

Low Black (25)

White

White

T2

T1

EH

L2

L1

RB 42

Black (27)

Tan (41) Blue (40)
Red
Black

Damper Switch Off

Blue /Wht (35)

DT

D Damper

On

Motor

Blue /Wht (36)

White (34)

Compressor S
C

Blu

R

Red

Blk

Tan

Handi - Box

Ground Lug

T2

T1

CC

L2

L1

Black (31) Red (32)

Black Blue 230V/265V

Unit Power Supply 208-230/60/1 or
265/60/1
G

Red 208V

Note 1

Transformer

Yellow

24V Emergency Shutdown

Black/White

Red

ES

Red

ES Yellow

TB Emerg Shutdown ES

Load Shed

LS

Lockout Circuit A LO1

24VAC

R

24VAC Common

C

Reversing Valve

O

Fan

G

Compressor A

Y1

Electric Heat

W

Dehumidification DH

Lockout Circuit B LO2

Compressor B

Y2

Class 2

Note 3 AQ

Black/ White

Black/ White

4

5

Red (39)

E1

2

Blue (38)

EH

CC Yellow (44)

Black (15) Black (13)
RB White (12)

470 T
RV

470

Resistor

RV FD

LP HP

Black (10) Black (09) Blue (08) Blue (07)
Yellow Yellow Orange (02) Orange (01)

Violet (14)

P9 EH1 CC2 CC F C

P2

ES

LS ALM ALG ACC COM

K5-Alarm Relay

ACC NO ACC NC

K6-Acc Relay

LO R C O/B G Y1 Y2 W DH P1
R

Com2 LED5
G RS485 NET

C

P8

JW2

K1-RV Relay

R

F

FG

CC

CCGCHCI2

CC2 LO

CC2 G

P5

REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS P4

C

R F1-3A

F

K3-CC2 Relay K2-CC Relay K4-Fan Relay

Aurora Base Control (ABC)

SW1 Test Mode

Com1 LED5
G RS485 NET
C R - + P7

RS485 EXP C R - + P6 CO C EH1 C EH2 P3

Status LED3
G

PWM CFM

Fault

C

LED1

P13

R

Off On

FP1 ­ 15°F/30°F

1

FP2 ­ 15°F/30°F

2

RV ­ B/O

3

Acc ­ Dip 4

4

Acc ­ Dip 5

5

CC ­ Dual/Single

6

L Output Type

7

Future Use

8

SW2 Config

LED2

Y

Y1 G CC

1

3

E1

Green (00)

Brown (23) Condensate

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

25

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Wiring Schematics cont.
ABC - ECM with Electric Heat and Remote Stat

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Notes:

208-230-265/60/1
05

1 ­ Swap blue and red leads for 208V operation. 2 ­ Factory wired. Refer to blower table settings. 3 Optional field installed Aquastat for use with single heat.

Accessory Relay

Operation Cycle with Blower

SW2-4 SW2-5 On On

Cycle with Compressor

Off Off

Water Valve Slow Open On Off

Outdoor Air Damper

Off On

Aurora Timing Events

Event

Normal Mode

Random Start Delay

5 to 80 seconds

Compressor On Delay

5 seconds

Compressor Minimum On Time

2 minutes

Compressor Short Cycle Delay

4 minutes

Blower Off Delay

30 seconds

Fault Recognition Delay ­ High Pressure

Less than 1 second

Start-Up Bypass ­ Low Pressure

2 minutes

Fault Recognition Delay ­ Low Pressure

30 seconds

Start-Up Bypass ­ Low Water/Air Coil Limit

2 minutes

Fault Recognition Delay ­ Low Water/Air Coil Limit

30 seconds

Fault Recognition Delay ­ Condensate Overflow

30 seconds

Thermostat Call Recognition Time

2 seconds

Auxiliary Heat Staging Delay

5 minutes

Emergency Heat Staging Delay

2 minutes

Water Valve Slow Open Delay

90 seconds

Reheat Delay

30 seconds

Test Mode 1 second < 1 second 5 seconds 15 seconds 2 seconds Less than 1 second 30 seconds 30 seconds 30 seconds 30 seconds 30 seconds 2 seconds 20 seconds 7.5 seconds 90 seconds 30 seconds

NC*09 NC*12 NC*15 NC*18

CHART 1

Blower Sengs

High

Low

Yellow

White

Blue

Yellow

Yellow

White

Blue

Yellow

Legend

Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal

T

Thermistor

Relay Coil

Switch - Condensate Overflow Switch - High pressure Switch - Low pressure

1 2 3

L1

Field Wiring Lug

Polarized connector

Ground Relay Contacts ­ N.O., N.C. Capacitor Fuse

G

Light Emitting Diode - Green

Y

Light Emitting Diode - Yellow

Temperature Switch

R

Light Emitting Diode - Red

AQ ­ Aquastat CC ­ Compressor Contactor CO ­ Condensate Overflow Sensor ES ­ Emergency Shutdown HP ­ High Pressure Switch LP ­ Low Pressure Switch FD ­ Freeze Detection Sensor F1 ­ Fuse

Wire nut
SW1 ­ Push button SW2 ­ DIP package 8 position PB ­ Power Block RB ­ Blower Relay RV ­ Reversing Valve Coil

Aurora LED Flash Codes

Slow Flash 1 second on and 1 second off

Fast Flash 100 milliseconds on and 100 milliseconds off

Flash Code 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating

Random Start Delay

Status LED (LED1, Green)

Fast Flash

Configuration LED (LED2, Yellow)

Fast Flash

Fault LED (LED3, Red)

Fast Flash

Status LED (LED1, Green)

Configuration LED (LED2, Yellow)

Fault LED (LED3, Red)

Normal Mode

ON

No Software Overide Flash ECM Setting Normal Mode

OFF

Control is Non-Functional

OFF DIP Switch Overide

Slow Flash Input Fault Lockout

Flash Code 1

Test Mode

Slow Flash ECM Configure Mode

Fast Flash High Pressure Lockout

Flash Code 2

Lockout Active

Fast Flash Reset Configure Mode

Off

Low Pressure Lockout

Flash Code 3

Dehumidification Mode

Flash Code 2

Low Air Coil Limit Lockout - FP2 Flash Code 4

Reserved

Flash Code 3

Low Water Coil Limit Lockout - FP1 Flash Code 5

Reserved

Flash Code 4

Reserved

Flash Code 6

Load Shed

Flash Code 5

Condensate Overflow Lockout

Flash Code 7

ESD

Flash Code 6

Over/Under Voltage Shutdown

Flash Code 8

Reserved

Flash Code 7

Reserved

Flash Code 9

Reserved

Flash Code 10

Air/Water Coil Limit Sensor Error Flash Code 11

PWM CFM
C

CC2 Factory Factory Use

Factory Factory

HP P4

ECM PWM

HP

P13

LP

LP

FP2

FP2

FP1

FP1

SW1 Test

REV

REV

RV ­ K1

CC2 CC ­ K2

G

P5

LO

HI

CCG

CC

FG

F

R

F

CC Hi ­ K3 Fan ­ K4 Alarm ­ K5

CC

Acc ­ K6

G

Y1 JW2 Alarm
P2

Field Connections

Off LED1 FP1 ­ 15oF/30oF

On 1 LED2

R FP2 ­ 15oF/30oF

2Y

Fault

RV ­ B/O

ACC ­ Dip 4

LED3 G

ACC ­ Dip 5 CC ­ Dual/Single L ­ Pulse/Continuous

Status

Reheat/Normal

3 Config
4
5
6
7
8

SW2

AURORA BASE CONTROLTM
Com1 G

EH1
P3 EH2 C
EH1 C CO N/A

RS485 Exp

P6

(+)

(-)

R

C

P7

(+)

RS 485

(-)

R

C

P11

P8

Com2 G

P9

Factory Fan Connection

DH

W

Y2

Y1

G

O/B

C

R

LO

P1

Field Connections

3A-Fuse

DH

W

Y2

Y1

G

O/B

C

R

LO

ES LS ALM ALG ACC c ACC no ACC nc

RR

RS485 NET CC C

P WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and
specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

26

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Wiring Schematics cont.
Aurora UPC

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz
To ABC - P8
12345678

BACnet or N2 Network
Connections
Devices Must Be Wired in Daisy Chain Configuration

Orange Red
White Black

Blue Green
Brown Yellow

NET+ NETCOM NET+ NETCOM

Optional LON Add-On Module
LON OC

LON Network Connections

Devices Must Be Wired in Daisy Chain Configuration

Service
LED1

21

LED2

Tx
LED3
Rx
LED4
Net

ECHELON

12

12

GND
ZS Sensor 1 RNET+

Addr: 0

RNET-

+12V

ZS Sensor 2 Addr: 1

GND RNET+ RNET-
+12V

ZS Sensor 3 Addr: 2

GND RNET+ RNET-
+12V

NET+ NETCOM
NET+ NETN N/C Signal

LED1 TX
LED2 RX
LON DAPTER PORT
LED6 TX
LED7 2W RX

4W

GND RNET+ RNET+12V
RNET

GND LN+ LN+12
/S
LOCAL ACCESS

POWER
GND 24 VAC
LED3 POWER
FORMAT BATT
Communication Options
NOTE 1

12345678

LED4 RUN
LED5 ERR

ON
TEN'S 89 0 12 73 654
89 0 12 73
654 ONE'S

MAC Address Setting

ZS Sensor Information

Notes

Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.

1. Use DIP Switches 5 ­ 8 to change communication protocol and DIP switches 1 ­ 2 to change BACnet baud rate

DIP Switch Value
1 2 4 8

ON 1 2 34

Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.

Legend
Factory Low Voltage Wiring Field Low Voltage Wiring 12345678 RJ45 Connector

Page 1
WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

27

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Engineering Guide Specifications

General
Furnish and install WaterFurnace Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Chassis shall be installed with factory built cabinet or other custom cabinet approved by WaterFurnace engineering. Chassis SHALL NOT be installed without an approved cabinet enclosure. Capacities and characteristics as listed in the schedule and the specifications that follow. The reverse cycle heating/ cooling units shall be floor mounted console type with horizontal air inlet and up-flow air discharge. Units shall be AHRI/ISO 13256-1 certified and listed by a nationally recognized safety-testing laboratory or agency, such as ETL Testing Laboratory. Each unit shall be computer runtested at the factory with conditioned water and operation verified to catalog data. Each unit shall be mounted on a pallet and shipped in a corrugated box or stretch-wrapped. The units shall be designed to operate with entering liquid temperature between 20°F and 120°F [-6.7°C and 48.9°C].

The drain pan shall be of stainless steel construction to inhibit corrosion and bacterial growth. Drain outlet shall be located on pan as to allow complete and unobstructed drainage of condensate. The unit as standard will be supplied with solid-state electronic condensate overflow protection with Aurora Base Control. Mechanical float switches WILL NOT be accepted. Condensate tube shall be constructed of stainless steel and have an internal factory installed condensate trap.
Refrigerant Circuit All units shall utilize the non-ozone depleting and low global warming potential refrigerant R410A. All units shall contain a sealed refrigerant circuit including a hermetic motorcompressor, bi-directional thermostatic expansion valve, finned tube air-to-refrigerant heat exchanger, reversing valve, coaxial tube water-to-refrigerant heat exchanger, and service ports.

Chassis & Cabinet The cabinet shall be fabricated from heavy-gauge galvanized steel and finished with a beige textured epoxy powder coating on both sides for added protection. This corrosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117.
The cabinet shall be easily removable to allow for ease of service to the controls compartment, chassis, and piping. The top of the cabinet and grille is a horizontally flat (optional sloped) surface with a hinged control door cover. The return air filter shall be 1 in. (25.4 mm) fiberglass disposable type media.
The return and supply air sections are insulated with a 1/4 in. (6.4 mm) thick, dual density, 2 lb/ft3 (32 kg/m3) coated mat glass fiber with edges sealed or tucked under flanges to prevent the introduction of glass fibers into the discharge supply air through the aluminum grille. Standard cabinet panel insulation must meet NFPA 90A requirements, air erosion and mold growth limits of UL-181, stringent fungal resistance test per ASTM-C1071 and ASTM G21, and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not be accepted.
Option: A Super Quiet Sound package shall include multidensity full coverage compressor blanket.
Option: Shipped with motorized outside air damper and damper assembly for 25% make-up air.

Compressors shall be high-efficiency single speed rotary type designed for heat pump duty and mounted on durometer grommets to provide vibration free compressor mounting. Compressor motors shall be single-phase ECM with internal overload protection.
Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled aluminum tube construction rated to withstand 600 psig (4135 kPa) refrigerant working pressure.
Option: AlumiSeal electro-coated air coil.
The coaxial water-to-refrigerant heat exchanger shall be designed for low water pressure drop and constructed of a convoluted copper (cupronickel option) inner tube and a steel outer tube. Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled copper tube construction rated to withstand 600 PSIG (4135 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG (4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure. The thermostatic expansion valve shall provide proper superheat over the entire liquid temperature range with minimal "hunting." The valve shall operate bi-directionally without the use of check valves.
Option: Cupro-nickel refrigerant to water heat exchanger shall be of copper-nickel inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

28

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Engineering Guide Specifications cont.

(4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure. Water lines shall also be of cupronickel construction.
Option: ThermaShield coated water-to-refrigerant heat exchanger, water lines and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures below 50°F.
Blower Motor and Assembly The blower shall be a direct drive centrifugal type with a twin dynamically balanced wheel. The housing and wheel shall be designed for quiet, low outlet velocity operation. The blower housing shall be constructed of galvanized steel and shall be removable from the unit for servicing of the blower motor. The blower motor shall be 3-speed highefficiency electrically commutated motor (ECM) and shall be isolated from the housing by rubber grommets. The motor shall be permanently lubricated and have thermal overload protection.
Electrical A control box shall be located within the unit compressor compartment and shall contain a 75VA transformer, 24 Volt activated, 2 pole compressor contactor, and solidstate controller for complete unit operation. Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be 24 Volt and provide heating or cooling as required by the remote thermostat/sensor.
Unit mounted controls shall consist of switches for "OFF", "FAN", and "AUTO" or "HEAT/COOL". An additional switch is provided for blower speed setting of "HI" or "LO". The unit shall be equipped with a blower switch on the side of the control to provide "CONTINUOUS" or "CYCLED" blower operation. "CYCLED" blower will turn the blower on with the compressor. A unit-mounted electronic thermostat with a remote electronic thermistor located in the return air will control compressor operation in heating and cooling modes. Unit mounted thermostat shall be the standard thermostat option. All unit mounted thermostats shall be auto changeover. Manual changeover WILL NOT be accepted. Electromechanical operation WILL NOT be accepted.
Controls
Standard: A compressor control module (CCM) shall be included to disable compressor operation in the event of a trip of any of the safety switches and to send a signal to activate a fault indicator light at the thermostat. The CCM shall be capable of being reset from the thermostat or from the unit main disconnect switch. A terminal block with

screw terminals shall be provided for field connection of all low-voltage wiring.
An Aurora microprocessor-based controller that interfaces with a multi-stage electronic thermostat to monitor and control unit operation shall be provided. The control shall provide operational sequencing, blower speed control, high and low pressure switch monitoring, freeze detection, condensate overflow sensing, lockout mode control, LED status and fault indicators, fault memory, field selectable options and accessory output. The control shall provide fault retry three times before locking out to limit nuisance trips. A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal.
Option: An Aurora Unitary Protocol Converter (UPC) shall be included that communicates directly with the Aurora Heat Pump Controls and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC shall convert the internal Aurora Modbus protocol to BACnet MS/TP, or N2 protocols for communication over a BAS system. Additional individual unit configuration items such freeze protection settings shall be directly available over the BAS without the need for access to the actual heat pump.
Option: Aurora UPC DDC communication protocols: LonWorks
Option: Remote mounted thermostat is available for CCM and Aurora Base Control. A terminal block with screw terminals will be provided for field control wiring.
Piping Supply and return water connections shall be 1/2 in. [12.7 mm] FPT copper threaded fittings. All water piping shall be insulated to prevent condensation at low liquid temperatures.
A stainless steel tube stubbed out from the chassis is provided for condensate drain attachment. A short piece of polyvinyl hose is supplied to assist in adapting to drain.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

29

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Engineering Guide Specifications cont.

Accessories
Hose Kits ­ Ball Valves (field-installed)
A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A full port ball valve shall be provided with integral P/T (pressure/ temperature) port on supply hose. Specifications: Temperature range of 35°F [2°C] to 180°F [82°C]. Max. working pressure of 400 psi [2757 kPa] for 1/2 in. and 3/4 in. hose kits; max. working pressure of 350 psi [kPa] for 1 in. and 1-1/4 in. hose kits.
Hose Kits ­ Automatic Balancing and Ball Valves
(field-installed)
A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A full port ball valve shall be provided with integral P/T (pressure/ temperature) port on supply hose and automatic balancing valve with integral P/T ports and full port ball valve on return hose.

and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A "y" strainer is provided on one end for fluid straining and integral "blowdown" valve.. A full port ball valve shall be provided with integral P/T (pressure/temperature) port on supply hose and automatic balancing valve with integral P/T ports and full port ball valve on return hose.
Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C]. · Max. working pressure of 400 psi [2757 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi [2413 kPa] for 1 and 1-1/4 in. hose kits. · Minimum burst pressure of four times working pressure.
Auxiliary Heater (field-installed 208-230V units only)
An electric resistance heater shall provide supplemental and/or emergency heating capability. A manual switch shall be mounted on the side of the control compartment with "NORMAL" or "BOILERLESS" mode. "NORMAL" will run the compressor when there is a call for heating or cooling. "BOILERLESS" mode operation will run electric heat whenever there is a call for heating and run the compressor for a cooling call.

Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C]. · Max. working pressure of 400 psi [2757 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi [2413 kPa] for 1 in. and 1-1/4 in. hose kits. · Minimum burst pressure of four times working pressure.

Hose Kits ­ Automatic Balancing and Ball Valves with `Y' strainer (field-installed)
A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

30

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec 500 Console - Formerly Envision Console 0.75-1.5 Tons, 60Hz

Revision Guide

Pages: Cover
6 All All All 30

Description: Naming Update Updated Flat Top Dimensional Data Updated Nomenclature and Wiring Schematics (ABC and UPC Controls) Obsoleted PSC Option, Updated Nomenclature, Updated Wiring Schematics Updated With Aluminum Air Coils Added Revision Guide

Date:

By:

30 Jan 2022

JM

03 May 2016

MA

1 Sept 2015

MA

04 Mar 2015

MA

02 Mar 2014

DS

02 Mar 2014

DS

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1010CNB 01/22

31

Page _____ of _____

