Water Source Heat PumpAxiom™ Horizontal/Vertical — EXH/EXV, DXH/DXV

Water Source Heat Pump Axiom™ Horizontal/Vertical

27 avr. 2023 — Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.

Water Source Heat PumpAxiom™ Horizontal/Vertical — EXH/EXV, DXH/DXV

Instruction Manual for TRANE models including: DXHG 024-070 - 60 Hz, DXVG 024-070 - 60 Hz, EXHG 009-070 - 60 Hz, EXVG 009-070 - 60 Hz, DXHG 024-070 - 60 Hz Water Source Heat Pump, DXHG 024-070 - 60 Hz, Water Source Heat Pump, Source Heat Pump, Heat Pump, Pump

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 68 Pages, 4.39MB

Document DEVICE REPORTWSHP-SVX014J-EN 05132023
Installation, Operation, and Maintenance
Water Source Heat Pump AxiomTM Horizontal/Vertical -- EXH/EXV, DXH/DXV
0.75 to 6 Tons ­ 60 Hz, High Efficiency and TwoStage High Efficiency

Model Numbers: DXHG 024-070 - 60 Hz DXVG 024-070 - 60 Hz EXHG 009-070 - 60 Hz EXVG 009-070 - 60 Hz
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

May 2023

WSHP-SVX014J-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION NOTICE

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/ sleeves, butyl gloves, safety glasses, hard hat/ bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

©2023 Trane

WSHP-SVX014J-EN

WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
· Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in

Introduction
part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
· Removed EXHF/DXHF data and ZN524 data throughout the document.
· Added SymbioTM 400-B information throughout the document.
· Updated the dimensional data diagrams and tables for EXH/DXH in the Unit Dimensions chapter.
· Updated the Electrical data tables and Wiring Diagram chapter.

WSHP-SVX014J-EN

3

Table of Contents
Model Number Description . . . . . . . . . . . . . . . . . . . 6 EXVH/DXVH Models . . . . . . . . . . . . . . . . . . . . . . . 6
Overview of Manual. . . . . . . . . . . . . . . . . . . . . . . . . . 7 Unit Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Compressor Nameplate . . . . . . . . . . . . . . . . . . . . 7 Model Number Description . . . . . . . . . . . . . . . . . . 7
General Information . . . . . . . . . . . . . . . . . . . . . . . . . 8 Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Air-to-Refrigerant Coil . . . . . . . . . . . . . . . . . . . . . . 8 Water-to-Refrigerant Coil . . . . . . . . . . . . . . . . . . . 8 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 System Input Devices and Functions . . . . . . . . . 8 Deluxe 24V Controls (option) . . . . . . . . . . . . . . . 8 SymbioTM 400-B/Tracer® UC400-B (option). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Pump Module (Field Installed Accessory) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Waterside Economizer (Option) . . . . . . . . . . . . . 8 Boilerless Control/Electric Heat (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Unit Inspection Checklist. . . . . . . . . . . . . . . . . . . 10 Jobsite Inspection Checklist . . . . . . . . . . . . . . . . 10 Jobsite Storage . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Service Clearances . . . . . . . . . . . . . . . . . . . . . . . 12 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Weight Distribution for Hanging the DXH and EXH Model . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 General Installation Checks . . . . . . . . . . . . . . . . 27 Main Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Electric Heat Requirements . . . . . . . . . . . . . . . . 27

Low Voltage Wiring (AC) Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Filter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Supply-Air Ductwork . . . . . . . . . . . . . . . . . . . . . . 28 Return-Air Ductwork . . . . . . . . . . . . . . . . . . . . . . 28 Ducted Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Ducted Filter Rack . . . . . . . . . . . . . . . . . . . . . . . 30 Sound Attenuation Pad . . . . . . . . . . . . . . . . . . . . 30 Hanging the Horizontal Unit . . . . . . . . . . . . . . . . 30 Condensate Drain Connection. . . . . . . . . . . . . . 31 Supply Pipe Connections . . . . . . . . . . . . . . . . . . 31 Cleaning and Flushing the Water Loop. . . . . . . 31 Field Installed Power Wiring. . . . . . . . . . . . . . . . 32 Main Unit Power Wiring. . . . . . . . . . . . . . . . . . . . 32 Control Power Transformer . . . . . . . . . . . . . . . . 32 Thermostat Location . . . . . . . . . . . . . . . . . . . . . . 33
Thermostats and Zone Sensors . . . . . . . . . 33 Controls Using 24 Vac . . . . . . . . . . . . . . . . . . . . . 36 External Smoke Detection Wiring to Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Deluxe Controller . . . . . . . . . . . . . . . . . . . . . 39 SymbioTM 400-B/UC400-B Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Airflow Adjustment . . . . . . . . . . . . . . . . . . . . . . . . 39 Units with Deluxe 24V controls . . . . . . . . . . 39 Waterside Economizer Installation . . . . . . . . . . 40 Waterside Economizer Installation for Horizontal 0.75 to 6 Ton Units . . . . . . . . . . . 40 Waterside Economizer Installation for Vertical Units . . . . . . . . . . . . . . . . . . . . . . . . . 41
Waterside Economizer Start-Up Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Pre-Start Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . 51
Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Initial Unit Start-Up. . . . . . . . . . . . . . . . . . . . . . . . 52 Start-Up Checklist and Log. . . . . . . . . . . . . . . . . 52 Operating Pressures . . . . . . . . . . . . . . . . . . . . . . 52

4

WSHP-SVX014J-EN

Table of Contents

Water Pressure Drop. . . . . . . . . . . . . . . . . . . . . . 59 Water Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Preventative Maintenance . . . . . . . . . . . . . . . . . 61 Condensate Trap . . . . . . . . . . . . . . . . . . . . . . . . . 62
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Deluxe Controls . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Warranty Information . . . . . . . . . . . . . . . . . . . . . . . 67
Standard Warranty. . . . . . . . . . . . . . . . . . . . . . . . 67 Extended Warranty . . . . . . . . . . . . . . . . . . . . . . . 67

WSHP-SVX014J-EN

5

Model Number Description
EXVH/DXVH Models

Digits 1­3 -- Unit Configuration

Digit 13 -- Freeze Protection2

Digit 23 -- Unit Mounted Disconnect

EXV = High Efficiency Vertical DXV = Two-stage High Efficiency Vertical EXH = High Efficiency Horizontal DXH = Two-stage High Efficiency Horizontal
Digit 4 -- Development Sequence
G
Digits 5­7 -- Nominal Size (MBH)
009 = 9.0 MBH (EX only) 012 = 12.0 MBH (EX only) 015 = 15.0 MBH (EX only) 018 = 18.0 MBH (EX only) 024 = 24.0 MBH 030 = 30.0 MBH (EX only) 036 = 36.0 MBH 042 = 42.0 MBH (EX only) 048 = 48.0 MBH 060 = 60.0 MBH 070 = 70.0 MBH
Digit 8 -- Voltage (Volts/Hz/Phase)
4 = 460/60/3 7 = 265/60/1 A = 208-230/60/1 B = 208-230/60/3
Digit 9 -- Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper-Water Coil/Suction Line 8 = Insulated Cupro-Nickel Water Coil/Suction Line
Digit 10 -- Design Sequence
A = First Design Sequence
Digit 11 -- Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with Hot Gas Reheat 3 = Heating and Cooling Circuit with Waterside Economizer 4 = Heating and Cooling Circuit with Waterside Economizer, Hot Gas Reheat
Digit 12 -- Blower Configuration
K = Variable ECM Motor, Constant Torque

A = 20°F Freezestat (For Glycol Loop) B = 35°F Freezestat (For Water Loop)
Digit 14 -- Open Digit = 0
Digit 15 -- Supply-Air Arrangement
T = Top Supply-Air Arrangement B = Back Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
Digit 16 -- Return-Air Arrangement
L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 -- Control Types
D = Deluxe 24V Controls H = SymbioTM 400-B/UC400-B J = Symbio 400-B/UC400-B w/Air-Fi® Wireless Communications
Digit 18 -- Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 -- Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter Maintenance Timer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter Maintenance Timer and Condensate Overflow Sensor
Digit 20 -- Temperature Sensor
0 = No Additional Temperature Sensor 1 = Entering Water Sensor
Digit 21 -- Insulation 1 = Matte Faced Insulation 2 = Foil Faced Insulation
Digit 22 -- Electric Heat 0 = No Electric Heat 6 = Field Mounted External Boilerless LOW Electric Heat 7 = Field Mounted External Boilerless MED Electric Heat 8 = Field Mounted External Boilerless HIGH Electric Heat 9 = Boilerless Electric Heat Ready

0 = No Unit Mounted Disconnect 2 = Unit Mounted Disconnect
Digit 24 -- Filter Type
1 = 1-inch Throwaway Filter 2 = 2-inch Throwaway Filter 4 = 2-inch MERV 8 5 = 2-inch MERV 13
Digit 25 -- Acoustic Arrangement
1 = Standard Sound Attenuation 2 = Deluxe Sound Attenuation
Digits 26­36 -- Does Not Apply
00000000000 = Digits 26-36 are not applicable to the EXV or DXV products
Digit 37 -- Ducted Filter Rack
0 = Non-ducted filter rack A = Ducted Filter Rack Side Access/LH-RH C = Ducted Filter Rack (Bottom Access)
Digit 38 -- Isolation Valve
0 = No Isolation Valve 1 = Factory Mounted Isolation Valve
Digit 39 -- Power Connection
1 = Single Point 2 = Electric Heat Power Separate from Unit
Digit 40 -- Drain Pan
A = Polymer Drain Pan B = Stainless Steel Drain Pan
Model Number Note: Notes:
1. Deluxe Sound option to be made available in later product release.
2. 20°F Freezestat is typically used in a geothermal application. 35°F Freezestat is typically used in a boiler/tower application

6

WSHP-SVX014J-EN

Overview of Manual
Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems.
By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual.
Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Unit Nameplate
The unit nameplate is located on the outside of the control box access panel at the front of the unit. It includes the unit

model number, serial number, electrical characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the compressor shell.
Model Number Description
All products are identified by a multiple-character model number that precisely identifies a particular type of unit. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.

WSHP-SVX014J-EN

7

General Information
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control operation.

Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically bonded to the copper tubing.

Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel (option) and steel tube (tube-within-a-tube) design, leak tested to assure there is no cross leakage between the water tube (copper/cupro-nickel) and refrigerant gas (steel tube).

Table 1. High/low pressure switch

Trip

Recover

Unit

LP

40 +/-4

56 +/-4

psig

HP

650 +/-10

550 +/-10

psig

Controls
The available control type is a Deluxe 24V control option, a SymbioTM 400-B/Tracer® UC400-B BACnet® control option for all unit sizes.
All power wiring to the equipment is made at the unit's compressor contactor or optional disconnect switch for the EXH/V 0.75 to 6 ton units and the DXH/V 2 to 6 ton units. For units without the disconnect switch, the power wiring needs to be connected to the screw terminals of the compressor contactor. All low-voltage wiring is made at the unit's low voltage terminal plug.
System Input Devices and Functions
A thermostat, zone sensor, or building automation system is required to operate the water-source heat pump. The flexibility of having several mode capabilities depends upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V control systems may be located in the back of this manual. All digital control troubleshooting tips and connection diagrams are located in BAS-SVX065*-EN (UC400-B).
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board. The Trane microprocessor board is factory wired to a terminal plug to provide all necessary terminals for field connection.
8

The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, condensate overflow, unit safety control, diagnostics, and a generic relay (which may be available for field use).
SymbioTM 400-B/Tracer® UC400B (option)
The Symbio 400-B/UC400-B is a BTL Listed BACnet® controller that can operate stand- alone or within a Building Automation System (BAS) such as Tracer® SC+. For installation, operation, and maintenance, see BASSVX065*-EN (UC400-B).
Pump Module (Field Installed Accessory)
The pump module shall consist of either a single or dual 1/6 HP cast iron pump and a brass three-way shut-off valve. The pump module kits shall contain the necessary components for the installation, operation and maintenance of the water circuit of a closed-loop distributed pumping application.
Waterside Economizer (Option)
Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.
The waterside economizer is designed to begin economizing mode when water temperatures fall below the field adjustable temperature of 25, 35, 45, 55 or 60°F (for the Deluxe control option), or below the programmed setpoint (for the SymbioTM 400-B/UC400-B control option).
When the temperature is less than the setpoint, fluid will flow into the economizing coil, while simultaneously halting mechanical operation of the compressor. Mechanical cooling will continue on a call for a second stage from the thermostat or system control. Entering water temperature sensor is factory provided for field installation on the entering water side of the coil.
Boilerless Control/Electric Heat (Option)
This option targets building designs that do not incorporate a boiler to heat the loop system. During a heavy heating load, the loop temperature may begin to fall. As the loop temperature decreases, the heating capacity of the heat pump will also decrease. In the heating mode, when the loop temperature falls below 55°F (factory setting), the electric heater is energized, and the compressor is locked out. The system's electric heat source will continue to be utilized for primary heating until the loop temperature rises
WSHP-SVX014J-EN

above 60°F. Once the loop temperature rises above 60°F, the boilerless controller returns the unit to normal compressor heating operation and locks out the electric heater.
For the EXV/H and DXV/H models, the electric heat will be field installed by the contractor. Note: The boilerless controller has a field adjustable
entering water temperature setting of 25, 35, 45, 55, and 60 degrees. The compressor operation will return to normal operation when the loop temperature rises 5 degrees above the setpoint. This electric heat option is designed for primary heat only, not to run as supplemental heat to the heating function of the heat pump.
Table 2. Refrigerant charge (EXH/EXV)

Model (60 Hz)

Heat Pump w/ HGR

Heat Pump (oz)/Kg)

(oz)/Kg)

EXH/V009 EXH/V012 EXH/V015 EXH/V018 EXH/V024

35 / 0.992 35 / 0.992 39.5 / 1.12 56 / 1.588 60 / 1.701

37 / 1.049 37 / 1.049 42.5 / 1.205 59.5 / 1.687 64 / 1.814

General Information

Table 2. Refrigerant charge (EXH/EXV) (continued)

Model (60 Hz)

Heat Pump w/ HGR

Heat Pump (oz)/Kg)

(oz)/Kg)

EXH/V030 EXH/V036 EXH/V042 EXH/V048 EXH/V060 EXH/V070

67 / 1.899 68 / 1.928 83 / 2.353 87 / 2.466 101 / 2.863 122 / 3.459

72.5 / 2.055 74 / 2.098 90.5 / 2.566 95 / 2.693 111 / 3.147 132 / 3.742

Table 3. Refrigerant charge (DXH/DXV)

Model (60 Hz)

Heat Pump w/ HGR

Heat Pump (oz)/Kg)

(oz)/Kg)

DXH/V024 DXH/V036 DXH/V048 DXH/V060 DXH/V070

59 / 1.673 64 / 1.814 86 / 2.438 101 / 2.863 123 / 3.487

63 / 1.786 70 / 1.984 94 / 2.665 111 / 3.147 133 / 3.77

WSHP-SVX014J-EN

9

Pre-Installation
WARNING
Fiberglass Wool!
Exposure to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, a NIOSH approved dust/mist respirator, long sleeves and pants when working with products containing fiberglass wool.
Precautionary Measures:
· Avoid breathing fiberglass dust.
· Use a NIOSH approved dust/mist respirator.
· Avoid contact with the skin or eyes. Wear longsleeved, loose-fitting clothing, gloves, and eye protection.
· Wash clothes separately from other clothing; rinse washer thoroughly.
· Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator.
First Aid Measures:
· Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
· Skin Contact - Wash affected areas gently with soap and warm water after handling.
Unit Inspection Checklist
· Unpack all components of the kit.
· Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company. Important: Equipment is shipped FOB (Free on Board) at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
· Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
· If concealed damage is discovered, stop unpacking the shipment.
10

· Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
· Notify the carrier's terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
· Do not attempt to repair any damaged parts until the parts are inspected by the carrier's representative.
Jobsite Inspection Checklist
Always perform the following checks before accepting a unit:
· Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
· Verify that the power supply complies with the unit nameplate specifications.
· Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
Jobsite Storage
NOTICE
Microbial Growth!
Failure to follow instructions below could result in odors and damage to the equipment and building materials. The floor or foundation must be level and the condensate drain at the proper height for proper drainage and condensate flow. Standing water and wet surfaces inside the equipment can become an amplification site for microbial growth (mold). If there is evidence of microbial growth on the interior insulation, it should be removed and replaced prior to operating the system.
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unit should be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
· Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
· Cover the unit(s) with a water proof tarp to protect them from the elements.
WSHP-SVX014J-EN

· Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.

Pre-Installation
· Store units in the normal UP orientation to maintain oil in the compressor.
· Horizontal units may be stacked no more than three units high. Do not stack the vertical unit configurations.

WSHP-SVX014J-EN

11

Unit Dimensions
Service Clearances
Per NEC requirements, 36 inches of access and working space shall be provided and maintained around all control boxes and electrical equipment to permit ready and safe
Figure 1. Clearances - EXH/DXH 0.75 to 6 tons

14"

14"

LEFT RETURN BACK SUPPLY

LEFT RETURN RIGHT SUPPLY

14"

14"

14"

14"

UNIT FRONT 36"
14"
RIGHT RETURN BACK SUPPLY

UNIT FRONT 36"
14"
RIGHT RETURN LEFT SUPPLY

operation and maintenance of such equipment. Local codes may require more clearance to electrical equipment. Check all code requirements prior to unit installation.

A minimum 14­inch clearance for servicing the unit is required for all EXH 0.75 to 6 tons configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/maintenance ability. The optimum clearance required is 20 inches.

Notes: ·

Return air direction (left-hand or right hand) is NOT field convertible. Units must be ordered with correct return air side.

· For horizontal models, be sure to allow enough clearance between the condensate drain and the ceiling to allow for pitching of the condensate line. See Figure 20, p. 31 for pitching requirements.

14"

14"

14"

14"

UNIT FRONT 36"

UNIT FRONT 36"

12

WSHP-SVX014J-EN

1" 1"

Figure 2. Clearance ­ EXVG/DXVG 0.75 to 6 tons

24"

1"

RIGHT RETURN TOP/BACK SUPPLY

UNIT FRONT 36"

24"

1"

UNIT FRONT 36"

LEFT RETURN TOP/BACK SUPPLY

Unit Dimensions
A 24­inch clearance from other mechanical and electrical equipment (where shown) is recommended for most unit configurations. This will enable panel removal from the unit for service/maintenance. The 24­inch side clearance on EXVG/DXVG 0.75 to 6T models is for optimal access only. Side clearance is not a requirement as most components can be accessed from the front of the unit. A 1­inch minimum clearance between the filter rack and any obstacle is required for units in a free return application to provide proper air flow to the air-to-refrigerant coil. A 12­inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork. The 1­inch dimension shown in the back of the unit represents the supply duct collar for the back supply option. This clearance is needed to clear these flanges.

WSHP-SVX014J-EN

13

Unit Dimensions
Unit Dimensions
Figure 3. Left return/back supply (EXHG/DXHG)
N Dimensional data left return/back supply

TOP B M

BACK

E

D

H

D J
F 1.36 DRAIN

C NOMINAL

BB

FILTER SIZE

CC

NOMINAL FILTER SIZE LEFT SIDE
RIGHT SIDE

A L

BB AA
1.04

FRONT

HI VOLT
DISCONNECT SWITCH LOCATION

WO

K

CC

CC WCI MOUNTING

11.62

LOCATION

AA

2.56

BB LOW VOLT

WI 3.30

AA CC

Table 4. Dimensional data left return/back supply (EXHG/DXHG)

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

Hi Volt

EXHG009, EXHG012

A

B

C

D

E

F

H

J

K

25.50 46.00 17.75 13.50 3.50 2.00 10.13 9.38 15.00

EXHG015 25.50 49.00 18.75 13.50 3.88 2.25 10.50 11.25 16.00

EXHG018, EXHG/
DXHG024
EXHG030, EXHG/
DXHG036
EXHG042, EXHG/
DXHG048
EXHG/ DXHG060, 070

25.50 28.00 29.38 29.38

55.00 68.00 77.75 86.75

19.75 21.75 22.13 22.13

13.50 16.50 16.50 16.50

3.50 3.63 3.50 3.50

2.25 11.75 11.25 17.00 2.13 13.88 13.50 19.00 2.50 13.88 13.50 19.25 2.50 13.88 13.50 19.25

Note: Dimensions represent unit hanging dimensions including base rails for hanging.

Unit hanging location

L 23.50 23.50

M 19.88 21.38

N 23.00 24.50

23.50 24.38 27.50

26.00 30.88 34.00

27.25 30.88 43.75 27.25 30.88 52.75

Nominal
Filter Size 17 x 20
17 x 20
18 x 23
20 x 30
20 x 20 (x2)
20 x 20, 20 x 30

W.I. NPTI 0.50 0.75 0.75
1.00
1.00 1.00

W.O. DRAIN NPTI NPTI 0.50 0.75 0.75 0.75 0.75 0.75
1.00 0.75
1.00 0.75 1.00 0.75

14

WSHP-SVX014J-EN

Figure 4. Left return/right supply (EXHG/DXHG)

Dimensional data left return/right supply

TOP

B

N

M

Unit Dimensions

A L

BACK
NOMINAL FILTER SIZE C
BB CC
1.36 DRAIN

NOMINAL FILTER SIZE LEFT SIDE

BB AA
1.04

CC AA

RIGHT SIDE

D H

E

FRONT

K 2.56

HI VOLT
DICONNECT SWITCH LOCATION

WO

CC WCI MOUNTING

LOCATION

BB

WI

LOW VOLT

11.62 3.30

J D
AA CC
F

Table 5. Dimensional data left return/right supply (EXHG/DXHG)

Units

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

Hi Volt

EXHG009, EXHG012

A

B

C

D

E

F

H

J

K

25.50 46.00 17.75 13.50 3.38 3.00 10.13 9.38 15.00

EXHG015 25.50 49.00 18.75 13.50 5.88 4.00 10.50 11.25 16.00

EXHG018, EXHG/
DXHG024 EXHG030,
EXHG/ DXHG036 EXHG042,
EXHG/ DXHG048
EXHG/ DXHG060, 070

25.50 28.00 29.38 29.38

55.00 68.00 77.75 86.75

19.75 21.75 22.13 22.13

13.50 16.50 16.50 16.50

5.63 5.63 5.63 5.63

4.75 11.75 11.25 17.00 3.88 13.88 13.50 19.00 3.75 13.88 13.50 19.25 3.75 13.88 13.50 19.25

Note: Dimensions represent unit hanging dimensions including base rails for hanging.

Unit hanging location

L 23.50 23.50

M 19.88 21.38

N 23.00 24.50

23.50 24.38 27.50

26.00 30.88 34.00 27.25 30.88 43.75 27.25 30.88 52.75

Nominal
Filter Size 17 x 20
17 x 20
18 x 23
20 x 30
20 x 20 (x2)
20 x 20, 20 x 30

W.I. NPTI 0.50 0.75 0.75
1.00
1.00 1.00

W.O. DRAIN NPTI NPTI 0.50 0.75 0.75 0.75 0.75 0.75
1.00 0.75
1.00 0.75 1.00 0.75

WSHP-SVX014J-EN

15

Unit Dimensions

Figure 5. Right return/left supply (EXHG/DXHG)

TOP

B

Dimensional data right return/left supply

N

M

NOMINAL FILTER SIZE

1.56

NOMINAL FILTER SIZE

BACK

E

D

H

C
BB CC

D J

DRAIN 1.36

F

LEFT SIDE RIGHT SIDE

A L

BB AA
1.04

FRONT

HI VOLT
DISCONNECT SWITCH LOCATION

WO

K
CC

CC WCI MOUNTING

AA

LOCATION BB

WI

2.56

LOW VOLT

11.62 3.30

AA CC

Table 6. Dimensional data right return/left supply (EXHG/DXHG)

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

Hi Volt

EXHG009, EXHG012

A

B

C

D

E

F

H

J

K

25.50 46.00 17.75 13.50 5.50 2.00 10.13 9.38 15.00

EXHG015 25.50 49.00 18.75 13.50 5.88 2.25 10.50 11.25 16.00

EXHG018, EXHG/
DXHG024
EXHG030, EXHG/
DXHG036
EXHG042, EXHG/
DXHG048
EXHG/ DXHG060, 070

25.50 28.00 29.38 29.38

55.00 68.00 77.75 86.75

19.75 21.75 22.13 22.13

13.50 16.50 16.50 16.50

5.63 5.63 5.63 5.63

2.25 11.75 11.25 17.00 2.13 13.88 13.50 19.00 2.50 13.88 13.50 19.25 2.50 13.88 13.50 19.25

Note: Dimensions represent unit hanging dimensions including base rails for hanging.

Unit hanging location

L 23.50 23.50

M 19.88 21.38

N 23.00 24.50

23.50 24.38 27.50

26.00 30.88 34.00

27.25 30.88 43.75 27.25 30.88 52.75

Nominal
Filter Size 17 x 20
17 x 20
18 x 23
20 x 30
20 x 20 (x2)
20 x 20, 20 x 30

W.I. NPTI 0.50 0.75 0.75
1.00
1.00 1.00

W.O. DRAIN NPTI NPTI 0.50 0.75 0.75 0.75 0.75 0.75
1.00 0.75
1.00 0.75 1.00 0.75

16

WSHP-SVX014J-EN

Figure 6. Right return/back supply (EXHG/DXHG)

Dimensional data right return/back supply

TOP B

N

M

NOMINAL FILTER SIZE

NOMINAL FILTER SIZE

BACK

D

E

H

BB CC
DRAIN

J D C
F 1.36

LEFT SIDE RIGHT SIDE

Unit Dimensions

A L

BB AA
1.04

FRONT

HI VOLT
DISCONNECT SWITCH LOCATION

WO

K

CC

CC WCI

MOUNTING

LOCATION

AA

BB

WI

2.56

LOW VOLT

11.62 3.30

AA CC

Table 7. Dimensional data right return/back supply (EXHG/DXHG)

Unit

Width

Depth

Height

Duct Collar

Duct Collar Location

Blower Opening

Hi Volt

EXHG009, EXHG012

A

B

C

D

E

F

H

J

K

25.50 46.00 17.75 13.50 3.25 3.00 10.13 9.38 15.00

EXHG015 25.50 49.00 18.75 13.50 3.88 4.00 10.50 11.25 16.00

EXHG018, EXHG/
DXHG024
EXHG030, EXHG/
DXHG036
EXHG042, EXHG/
DXHG048
EXHG/ DXHG060, 070

25.50 28.00 29.38 29.38

55.00 68.00 77.75 86.75

19.75 21.75 22.13 22.13

13.50 16.50 16.50 16.50

3.50 3.63 3.50 3.50

4.75 11.75 11.25 17.00 3.88 13.88 13.50 19.00 2.50 13.88 13.50 19.25 3.75 13.88 13.50 19.25

Note: Dimensions represent unit hanging dimensions including base rails for hanging.

Unit hanging location

L 23.50 23.50

M 19.88 21.38

N 23.00 24.50

23.50 24.38 27.50

26.00 30.88 34.00

27.25 30.88 43.75 27.25 30.88 52.75

Nominal
Filter Size 17 x 20
17 x 20
18 x 23
20 x 30
20 x 20 (x2)
20 x 20, 20 x 30

W.I. NPTI 0.50 0.75 0.75
1.00
1.00 1.00

W.O. DRAIN NPTI NPTI 0.50 0.75 0.75 0.75 0.75 0.75
1.00 0.75
1.00 0.75 1.00 0.75

WSHP-SVX014J-EN

17

Unit Dimensions
Figure 7. Left return/top supply (EXVG/DXVG)
TOP

D

F

J

NOMINAL

FILTER

D

SIZE

H

E

LEFT SIDE

FRONT

RIGHT SIDE

NOMINAL FILTER SIZE

C

HI VOLT

DISCONNECT
SWITCH
LOCATION WO

K 1.75

WCI MOUNTING LOCATION
LOW VOLT

DRAIN WI

11.0 8.0
2.5

B

A

Table 8. Dimensional data left return/top supply (EXVG/DXVG)

Unit

Cabinet

Duct

Width Depth Height Collar

A

B

C

D

Duct Collar Location Blower Opening Hi Volt Nominal Filter

E

F

G

H

J

K

Size

EXVG009-012 21.50 21.50 34.00 13.25 4.00 1.00 3.50 10.50 9.60 14.25

16 x 19

W.I. NPTI
1/2

EXVG015 21.50 23.00 36.00 13.25 4.75 0.63 3.50 10.50 11.30 15.25

17 x 20

3/4

EXVG018,

EXVG/

21.50 26.00 38.00 13.25 6.25 0.63 3.50 11.80 11.30 16.25

18 x 23

3/4

DXVG024

EXVG030,

EXVG/

24.00 32.50 42.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25

20 x 30

1

DXVG036

EXVG042,

EXVG/

25.40 32.50 49.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25

27 x 30

1

DXVG048

EXVG/ DXVG060-070

25.40

32.50

55.00

16.50

7.25

0.75

3.50 13.70 13.50 18.25

30 x 33

1

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit's air-to-refrigerant coil.

W.O. NPTI 1/2 3/4 3/4
1
1
1

Drain NPTI 3/4 3/4 3/4
3/4
3/4
3/4

18

WSHP-SVX014J-EN

Figure 8. Right return/top supply (EXVG/DXVG)

G

D

TOP J

DH E

NOMINAL FILTER SIZE

Unit Dimensions

LEFT SIDE

FRONT

RIGHT SIDE

NOMINAL FILTER SIZE

C

HI VOLT
DISCONNECT SWITCH LOCATION
WO

K 1.75

WCI MOUNTING LOCATION
LOW VOLT

DRAIN WI

11.0 8.0
2.5

B

A

Table 9. Dimensional data right return/top supply (EXVG/DXVG)

Unit

Cabinet

Duct

Width Depth Height Collar

A

B

C

D

Duct Collar Location Blower Opening Hi Volt Nominal Filter

E

F

G

H

J

K

Size

EXVG009-012 21.50 21.50 34.00 13.25 4.00 1.00 3.50 10.50 9.60 14.25

16 x 19

W.I. NPTI
1/2

EXVG015 21.50 23.00 36.00 13.25 4.75 0.63 3.50 10.50 11.30 15.25

17 x 20

3/4

EXVG018,

EXVG/

21.50 26.00 38.00 13.25 6.25 0.63 3.50 11.80 11.30 16.25

18 x 23

3/4

DXVG024

EXVG030,

EXVG/

24.00 32.50 42.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25

20 x 30

1

DXVG036

EXVG042,

EXVG/

25.40 32.50 49.00 16.50 7.25 0.75 3.50 13.70 13.50 18.25

27 x 30

1

DXVG048

EXVG/ DXVG060-070

25.40

32.50

55.00

16.50

7.25

0.75

3.50 13.70 13.50 18.25

30 x 33

1

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit's air-to-refrigerant coil.

W.O. NPTI 1/2 3/4 3/4
1
1
1

Drain NPTI 3/4 3/4 3/4
3/4
3/4
3/4

WSHP-SVX014J-EN

19

Unit Dimensions

Figure 9. Left return/back supply (EXVG/DXVG)

Dimensional data left return/back supply

TOP B

A

E F
D J

BACK
D H

NOMINAL FILTER SIZE

NOMINAL FILTER SIZE LEFT SIDE

C

RIGHT SIDE

FRONT

HI VOLT

DISCONNECT

SWITCH

LOCATION

WO

K

DRAIN

WI

1.81

LOW VOLT

10.87 8.00
2.55

Table 10. Dimensional data left return/back supply (EXVG/DXVG)

Cab

Unit

EXVG DXVG

B 009, 012 ­

Width A
21.50

Depth
B 21.50

Height
C 34.00

Duct Collar
D
13.50

Duct Collar

Location

E

F

3.50 2.00

Blower Opening

H

J

10.13 9.38

Hi Volt K
14.25

Nominal Filter Size
16 x 19

W.I. NPTI
1/2

C

015

­

21.50 23.00 36.00 13.50 3.88 2.25 10.50 11.25 15.25 17 x 20

3/4

D 018, 024 024 21.50 26.00 38.00 13.50 3.50 2.75 11.75 11.25 16.25 18 x 23

3/4

E 030,036 036 24.00 32.50 42.00 16.50 3.63 2.13 13.88 13.50 18.25 20 x 30

1

F 042, 048 048 25.40 32.50 49.00 16.50 3.50 2.50 13.88 13.50 18.25 27 x 30

1

G 060, 070 060,070 25.40 32.50 55.00 16.50 3.50 2.50 13.88 13.50 18.25 30 x 33

1

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit's air-to-refrigerant coil.

W.O. NPTI
1/2 3/4 3/4 1 1 1

Drain NPTI
3/4 3/4 3/4 3/4 3/4 3/4

20

WSHP-SVX014J-EN

Figure 10. Right return/back supply (EXVG/DXVG)
TOP

Dimensional data right return/back supply

NOMINAL FILTER SIZE

A

Unit Dimensions

NOMINAL FILTER SIZE

BACK

D

E

H

F

J D

B LEFT SIDE

FRONT

C RIGHT SIDE

HI VOLT

DISCONNECT SWITCH LOCATION

WO

K

DRAIN

1.81

LOW VOLT

WI

10.87 8.00
2.55

Table 11. Dimensional data right return/back supply (EXVG/DXVG)

Cab

Unit

EXVG DXVG

B 009, 012 ­

Width A
21.50

Depth
B 21.50

Height
C 34.00

Duct Collar
D
13.50

Duct Collar

Location

E

F

3.25 1.00

Blower Opening

H

J

10.13 9.38

Hi Volt K
14.25

Nominal Filter Size
16 x 19

W.I. NPTI
1/2

C

015

­

21.50 23.00 36.00 13.50 3.88 1.00 10.50 11.25 15.25 17 x 20

3/4

D 018, 024 024 21.50 26.00 38.00 13.50 3.50 1.00 11.75 11.25 16.25 18 x 23

3/4

E 030,036 036 24.00 32.50 42.00 16.50 3.63 1.00 13.88 13.50 18.25 20 x 30

1

F 042, 048 048 25.40 32.50 49.00 16.50 3.50 1.00 13.88 13.50 18.25 27 x 30

1

G 060, 070 060,070 25.40 32.50 55.00 16.50 3.50 1.00 13.88 13.50 18.25 30 x 33

1

Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit's air-to-refrigerant coil.

W.O. NPTI
1/2 3/4 3/4 1 1 1

Drain NPTI
3/4 3/4 3/4 3/4 3/4 3/4

WSHP-SVX014J-EN

21

Unit Dimensions
Figure 11. Waterside economizer1 (EXHG/DXHG)
B D

B D

2" AIR FILTER (1.38 FOR 1")

2.38

A

2" AIR FILTER (1.38 FOR 1")

A

2.38

C

C

3.40 4.25

3.40 4.25

Table 12. Dimensional data waterside economizer (EXHG/DXHG)

Cab
B C D E F G

Unit

EXHG

009

012

015

­

018

024

030

036

042

048

060

070

DXHG

­

­

­

­

024

­

036

­

048

­

060

070

Width A
8.5

WSE Dimensions

Depth Height Depth W/Piping

B

C

D

21.5

18.25

29.00

23.0

19.25

30.50

26.0 22.25

33.50 38.25

32.5

29.25

50.50

35.25

59.50

Pipe Size

A

B

NPTI

NPTI

0.75

0.75

0.75

0.75

0.75

0.75

1

1

1

1

1

1

Table 13. Waterside economizer weights and part numbers - horizontal

Unit Model
EXHG009-012 LR EXHG015 LR
EX/DXHG018-024 LR EX/DXHG030-036 LR EX/DXHG042-048 LR

Waterside Economizer
WSHPECN00016 WSHPECN00017 WSHPECN00018 WSHPECN00019 WSHPECN00020

Weight w/out H2O
27 29 35 41 50

Weight w/H2O
30 33 40 48 59

1. Waterside economizer installation requires field piping. 22

WSHP-SVX014J-EN

Table 13. Waterside economizer weights and part numbers - horizontal (continued)

Unit Model
EX/DXHG060-070 LR EXHG009-012 RR EXHG015 RR
EX/DXHG018-024 RR EX/DXHG030-036 RR EX/DXHG042-048 RR EX/DXHG060-070 RR

Waterside Economizer
WSHPECN00021 WSHPECN00023 WSHPECN00024 WSHPECN00025 WSHPECN00026 WSHPECN00027 WSHPECN00028

Weight w/out H2O
59 27 29 35 41 50 59

Weight w/H2O
70 30 33 40 48 59 70

Figure 12. Waterside economizer (EXVG/DXVG)

Unit Dimensions

Table 14. Dimensional data waterside economizer (EXVG/DXVG)

Unit
EXVG009-012 EXVG015
EXVG018-024, DXVG024 EXVG030-036, DXVG036 EXVG042-048, DXVG048
EXVG/DXVG060-070

Cabinet
B C D E F G

A (Width)
8.5 8.5 8.5 8.5 8.5 8.5

WSE Dimensions B
(Depth)
21.5 23.0 26.0 32.5 32.5 32.5

C (Height)
18.25 19.25 22.25 22.25 29.25 35.25

WSHP-SVX014J-EN

23

Unit Dimensions
Figure 13. Waterside economizer (EXVG/DXVG)

Table 15. Dimensional data waterside economizer (EXVG/DXVG)

Pipe Size

WSE Size

Piping Location

Unit

Cabinet A

B

C

D

E

F

G

H

J

K

NPTI NPTI Width Depth Height Height Height Width Width Width

EXVG009-012

B

EXVG015

C

EXVG018-024, DXVG024

D

EXVG030-036, DXVG036

E

1/2

1/2

8.5

27.5 18.25 17.75 20.75

5.0

7.88

3.5

3/4

3/4

8.5

29.0 19.25 19.75 22.75

5.0

7.88

3.5

3/4

3/4

8.5

21.75 21.75 24.75

5.0

7.88

3.5

32.0

1

1

8.5

38.5 22.75 22.75 25.75

5.0

8

3.5

L Width 0.63 0.63
0.63
0.5

Drain

M

N

Width Height

4.25 15.75 4.25 16.75

4.25 15.75

4.25 19.75

EXVG042-048, DXVG048

F

1

1

8.5

38.5 22.75 22.75 25.75

5.0

8

3.5

0.5

4.25 19.75

EXVG/ DXVG060-070

G

1

1

8.5

38.5 22.75 22.75 25.75

5.0

8

3.5

0.5

4.25 19.75

Table 16. Waterside economizer weights and part numbers - vertical

Unit Model
EXVG009-012 LR EXVG015 LR
EX/DXVG018-024 LR EX/DXVG030-036 LR EX/DXVG042-048 LR EX/DXVG060-070 LR
EXVG009-012 RR EXVG015 RR
EX/DXVG018-024 RR EX/DXVG030-036 RR EX/DXVG042-048 RR EX/DXVG060-070 RR

Waterside Economizer
WSHPECN00002 WSHPECN00003 WSHPECN00004 WSHPECN00005 WSHPECN00006 WSHPECN00007 WSHPECN00009 WSHPECN00010 WSHPECN00011 WSHPECN00012 WSHPECN00013 WSHPECN00014

Weight w/out H2O (lbs) Weight w/H2O (lbs)

27

30

29

33

35

40

41

48

51

60

60

71

27

30

29

33

35

40

41

48

51

60

60

71

24

WSHP-SVX014J-EN

Figure 14. Waterside economizer coil piping diagram

Unit Water Outlet

Unit Heat Exchanger

Unit Water Inlet

WSE Coil Outlet

WSE Coil

Unit Dimensions
WSE Coil Inlet

TEE

Please match the entering water port marking with
the marking label on the valve prior
to using this diagram.

Port A
3 Way Valve

Port B

Port AB Entering Water

WSHP-SVX014J-EN

25

Weights

Table 17. Unit weights DXH 2 to 6 tons (Approximate)

DXH

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

024

393

269

036

458

313

048

560

381

060

613

434

070

613

434

Table 18. Unit weights DXVG 2 to 6 tons (Approximate)

DXV

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

024

296

236

036

342

279

048

419

354

060

440

371

070

506

437

Table 19. Unit weights EXVG 0.75 to 6 tons (Approximate)

EXV (60 Hz)

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

009

207

152

012

207

152

015

246

188

018

282

222

024

296

236

030

343

280

036

344

281

042

394

329

048

410

374

060

436

394

070

501

432

Table 20. Unit weights EXH 0.75 to 6 tons (Approximate)

EXH (60 Hz)

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

009

297

173

012

297

173

Table 20. Unit weights EXH 0.75 to 6 tons (Approximate) (continued)

EXH (60 Hz)

Shipping Weight with pallet (lbs)

Unit Weight without pallet (lbs)

015

297

173

018

393

269

024

393

269

030

458

313

036

458

313

042

560

381

048

560

381

060

613

434

070

613

434

Weight Distribution for Hanging the DXH and EXH Model
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
Approximate weight distribution for proper hanging of the unit is indicated by weight distribution in the figure below.
Tolerance on the weights determined are ±15%.
Figure 15. Weight distribution DXH 2 to 6 tons; EXH 0.75 to 6 tons

26

WSHP-SVX014J-EN

Installation
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
General Installation Checks
The checklist below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions that are in the applicable sections of this manual.
1. Remove packaging and inspect the unit. Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representation.
The EXH/V 0.75 to 6 tons and DXH/V 2 to 6 tons have been anchored to the skid with (4) angle brackets. Remove these brackets before lifting unit into place.
2. Verify the correct model, options and voltage from the unit nameplate.
3. Pull out all field attached parts (i.e. filter rack, duct collar, filter and mounting screws) from the unit packaging for field mounting.
4. Verify the installation location of the unit will provide the required clearance for proper operation.
5. Remove refrigeration access panel and inspect the unit. Be certain the refrigerant tubing has clearance from adjacent parts.
6. Fabricate and install duct work
7. Install and connect a condensate drain line and trap to the drain connection.

Main Electrical WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
1. Verify the power supply complies with the unit nameplate specifications.
2. Inspect all control panel components; tighten any loose connections.
3. Connect properly sized and protected power supply wiring to a field-supplied/installed disconnect switch and to the main compressor contactor/power block 1K1 for DXH/V 2 to 6 tons and EXH/V 0.75 to 6 ton units.
4. Install proper grounding wires to an earth ground. Note: All field-installed wiring must comply with NEC and
applicable local codes.
Electric Heat Requirements
1. Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate.
2. Inspect the heater junction box and control panel; tighten any loose connections.
3. Check electric heat circuits for continuity.
Low Voltage Wiring (AC) Requirements
1. Install the zone sensor or thermostat.
2. Connect properly sized control wiring to the proper termination points between the zone thermostat or sensor and the unit control panel.
Filter Installation
Each unit ships with 1 in. (25.4 mm) standard, 2 in. (50.8 mm) standard, 2 in. MERV 8 or 2 in. MERV 13 filter. The quantity of filters is determined by unit size. The EXH and DXH units require field installation of the 1 in. or 2 in. filters rack. All sheet metal bracket, filter and hardware are in a box located on the side of the unit within the unit packaging. All vertical units ship with the filter rack and filters factory installed. Note: Do not operate the unit without filters.

WSHP-SVX014J-EN

27

Installation
Supply-Air Ductwork
Horizontal DXH and EXH units require duct flanges to be field installed. The duct flange ships in a box on the side of the unit. Install the flange with (8) 3/8 in. (213 mm) factory supplied screws.
Install the 1 in. (25.4 mm) supply-air duct flange to the vertical and horizontal equipment with the (8) 5/16 in. (7.94 mm) factory-supplied head screws. The duct collar assembly for each unit is shipped with the unit in the same box where the IOM manual is located.
When attaching the field ductwork to the unit, provide a watertight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork (See the figure below).
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
Figure 16. Flexible supply-air connector (field provided)

Figure 17. Flexible return-air connector (field provided)
SUPPLY-AIR

RETURN AIR

Filter Flange (Factory Provided)

Return-Air Boot (Field Provided)

Supply-Air Boot (Field Supplied)
1-inch Duct Collar (Factory Provided)
Return-Air Ductwork
Install the 1/2 in. (25.4 mm/50.8 mm) adjustable filter rack to the horizontal equipment only with the use of (4) 5/16 in. (7.94 mm) factory supplied head screws. The vertical equipment factory ships with the filter rack and filter(s) installed. When attaching the field ductwork to the unit, provide a water-tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork. Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.

Ducted Panel
The return-air arrangement may be easily converted from a free return-air system, to a ducted return-air system with the addition of a return-air side panel. By replacing the filter racks with the return-air panel, a complete seal from the duct to the unit is possible. The 1.5 duct flange facilitates ease of field connection to the duct system. This accessory is typically used when the return-air filter is placed in a builtin ceiling grille, or placed within a field provided filter rack assembly.
Install the return-air duct panel to the return-air opening with the six screws provided for the filter rack assembly.

28

WSHP-SVX014J-EN

Figure 18. Return-air duct panel
Unit Top

Installation

Unit Side

1"

3 3/4"

Unit Top A
B

Unit Side

Duct Panel with 1 1/2"-Flange

Table 21. Ducted panel - return air
Unit Size EXVG009-012
EXVG015 EXVG018-024, DXVG024 EXVG030-036, DXVG036 EXVG042-048, DXVG048 EXVG060-070, DXVG060-070
EXHG009-012 EXHG015
EXHG018-024, DXHG024 EXHG030-036, DXHG036 EXHG042-048, DXHG048 EXHG060-070, DXHG060-070

A (in.) 18.50 20.00 23.00 29.50 29.50 29.50 18.50 20.00 23.00 29.50 38.88 47.88

B (in.) 16.50 17.50 18.50 20.50 27.25 33.25 16.50 17.50 18.50 20.50 19.75 19.75

Duct Collar Part Number WSHPPND00002 WSHPPND00003 WSHPPND00004 WSHPPND00005 WSHPPND00006 WSHPPND00007 WSHPPND00011 WSHPPND00012 WSHPPND00013 WSHPPND00014 WSHPPND00015 WSHPPND00016

WSHP-SVX014J-EN

29

Installation
Ducted Filter Rack
C
A

When it is necessary to have filter access at the unit in a ducted return, a ducted filter rack is available. This option allows access to the filter at the unit. Vertical unit filter racks are available in right or left access configurations. Horizontal units are available in bottom access configuration.

B

Table 22. Ducted filter opening size - 0.75 to 6 tons

Unit Size

A (in.)

EXHG 009-012

19.00

EXHG 015

20.50

EXHG 018-024, DXHG 024

23.50

EXHG 030-036, DXHG 036

30.00

EXHG 042-048, DXHG 048

40.50

EXHG 060-070, DXHG 060-070

50.50

EXVG 009-012

19.00

EXVG 015

20.50

EXVG 018-024, DXVG 024

23.50

EXVG 030-036, DXVG 036

30.00

EXVG 042-048, DXVG 048

30.00

EXVG 060-070, DXVG 060-070

30.00

Note: All dimensions in inches. All dimensions are for accessory 2 or 4-inch filter rack.

Sound Attenuation Pad
For sound-sensitive installations, a vibration pad (field provided) should be placed beneath the horizontal or vertical equipment. For the horizontal unit, the pad should be approximately twice the size of the unit foot print. For the vertical unit, the pad should be 0.5 in. (12.7 mm) thick, and equal to the overall unit foot print.

Hanging the Horizontal Unit
WARNING
Proper Structural Support Required!
Failure to ensure proper structural ceiling support could result in unit falling from its location which could result in death or serious injury. Ceiling structure must be strong enough to support the weight of the unit and any accessories. If unsure, check with a structural engineer.

B (in.) 16.25 17.25 18.25 20.25 21.00 21.00 16.25 17.25 18.25 20.25 27.00 32.75

C (in.) 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

To hang the horizontal configuration (see the figure below):
1. Install the hanging isolators (located in the return-air section of the unit) into the six hanging brackets.
2. The base of the unit (hanging rails) must be fully supported while unit is being lifted for install. This can be achieved by using a lift with a large enough supporting surface, or a wooden structure can fully support the base if desired.
3. Secure the equipment to a joist, concrete, etc. with the use of 3/8 in. (9.7 mm) field provided (all-thread) rod. Each rod should contain field provided nuts and washers to complete the hanging installation.
4. All plumbing to the unit should conform per national and local codes and is the responsibility of the contractor. The 0.5 to 6 ton horizontals and EX/DXHG models do not need to be sloped. EXHG and DXHG 0.75 to 6 ton models must be installed level.

30

WSHP-SVX014J-EN

Notes: ·
·

Rods must be perpendicular to the mounting holes in the base rail of the horizontal unit. For 0.75 to 6 ton EXHF and DXHF models, follow pitching instructions from previous generation IOM.

Figure 19. Hanging the unit

Condensate Drain Connection
Figure 20. Negative pressure system
CLEAN OUT (CAPPED and SEALED)
Install proper trapping to the equipment. The unit drain connection is 0.75 in. NPT for all DXH, DXV, and EXH/V 0.75 to 6 ton models. When designing the condensate trap for the water-source system, it is important to consider the unit draw-thru design requiring negative pressure trapping. In a properly trapped system, when condensate forms during normal operation, the water level in the trap rises until there is a constant flow. It is imperative to maintain water in the trap and not allow the trap to dry out during heating season. Keeping trap primed at all times will enable the water to flow properly. See the figure above for appropriate dimensions required in a negative pressure system.
WSHP-SVX014J-EN

Installation
Supply Pipe Connections
Figure 21. Supply/return pipe connections

WATER-OUT
WATER-IN
AUTOMATIC BALANCING HOSE KIT

RETURN TO LOOP
SUPPLY FROM CENTRAL PUMP

Connect the supply and return hoses to the water-inlet (from supply) and water-outlet (to return) of the unit. For vibration isolation, it is recommended that flexible steel braided hoses be installed instead of hard piping the equipment to the main loop system. Figure above shows connection of a Hays Mesurflo® balancing hose kit to the water-in and water-out of a vertical unit. Note: Above figure example incorporates the Hays
Mesurflo® balancing hose kit and a 2-position isolation valve into the system design. An isolation valve is often used in variable speed pumping applications. The isolation valve is designed to stop water flow to the unit during non operation times. This allows the loop water pumps to run only when a requirement for pumping is needed for greater energy efficiency of the overall system design.
Cleaning and Flushing the Water Loop
After the piping system is complete, the flexible hose connectors should be doubled back to complete the water circuit external to the unit (avoiding trash settle-out in the condenser). An extra pipe may be necessary to connect the hose kits.
1. Water circulation system should be filled with clean water using the water make up connections.
Note: Air vents should be open during filling.
2. With the air vents closed, start the circulating pump and then crack the air vents to bleed off the trapped air, assuring circulation through all components of the system.
Note: Make up water must be available to the system to replace the volume formerly occupied by the air that is bled off.
3. With the air vented and the water circulating, the entire system should be checked for leaks with repairs made as required.
4. Operate the supplementary heat system (boiler) making checks per manufacturer's instructions. During this operation, visual checks should be made for leaks
31

Installation
that may have occurred due to increased heat. Repair as required.
5. Open the system at the lowest point for the initial blow down (making sure the make up water is equal to the water being dumped). Continue blow down until the water leaving the drain runs clear, but not less than 2 hours.
6. Shut down pumps and supplementary heat system. Reconnect the hoses placing the water-to-refrigerant heat exchanger in the water circulating system.
Note: Vents should be open when the pumps and supplementary heat system are shut down.
Field Installed Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the equipment was not designed or qualified to accept other types of conductors.
Verify that the power supply available is compatible with the unit's nameplate. Use only copper conductors to connect the power supply to the unit.
Main Unit Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

A field supplied disconnect switch must be installed at or near the unit in accordance with the National Electric Code (NEC latest edition). Location of the applicable electric service entrance for HIGH (line voltage) may be found in the Dimensions section of this manual. The high-voltage connection is made at the 1K1 contactor or 1TB power block inside the unit control box (See the figure below). Refer to the customer connection diagram that is shipped with the unit for specific termination points. Provide proper grounding for the unit in accordance with the local and national codes.
Figure 22. Power wiring example
Control Power Transformer
The 24 V control power transformers are to be used only with the accessories called out in this manual. A 50 VA transformer is externally fused. Transformers rated greater than 50 VA are equipped with circuit breakers. If a circuit breaker trips, turn OFF all power to the unit before attempting to reset it.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
The transformer is located in the control panel.

32

WSHP-SVX014J-EN

Thermostat Location
Figure 23. Thermostat/sensor location

Installation
Location of the thermostat or zone sensor is an important element of effective room control. Areas where the thermostat or zone sensor should not be located include: · Behind doors or corners · Near hot or cold air ducts · Near radiant heat (heat emitted from appliances or the
sun) · Near concealed pipes or chimneys · On outside walls or other non conditioned surfaces · In airflows from adjacent zones or other units.

Thermostats and Zone Sensors

Table 23. Thermostat selection for use with the Deluxe controller

Thermostat

Part Number

Description

X13511535010

1 Heat/1 Cool, non-programmable commercial thermostat for conventional air conditioners and heat pumps that are configured without auxiliary heat
· 1 H/1 C

X13511536010

3 Heat/2 Cool, non-programmable commercial thermostat for conventional air conditioners and heat pumps that are configured with or without auxiliary heat.
· 3 H/2 C

X13511537010

3 Heat/2 Cool, programmable commercial thermostat for conventional (rooftop) air conditioners and heat pumps that are configured with or without auxiliary heat.
· 3 H/2 C

X13511538010

3Heat/2 Cool, programmable touch screen thermostat for conventional air conditioners and heat pump systems. The thermostat will provide the human interface, zone temperature sensing both local and optional remote temperature sensing, and set point scheduling on a daily/ weekly basis. This thermostat can also display humidity with a control signal for dehumidification with a local humidity sensor or optional remote humidity sensor.
· 3 H/2 C

WSHP-SVX014J-EN

33

Installation

Table 23. Thermostat selection for use with the Deluxe controller (continued)

Thermostat

Part Number Pivot -- BAYSTAT814A-W.

Description
Pivot Smart Thermostat is a Wi-Fi/ethernet thermostat for commercial applications. It has a very simple interface for occupants to adjust the thermostat. Cooling and heating control of multiple systems is made even easier and faster when connected to the Pivot App. Supports 2 stage heat pump with auxiliary heat.

XL824 - TCONT824AS52DB.

The XL824 Smart thermostat is a Wi-Fi/ethernet thermostat for Residential applications such as single family homes, condominiums and apartments. Supports 2 stage heat pump with auxiliary heat. The XL824 can be connected to the Nexia Home App and other home automation systems.

Table 24. Zone sensor selection for use with SymbioTM 400-B/Tracer® UC400-B controller

Sensor

Part Number X13790886010

Description
Wired temperature sensor with an LCD display
· Allows an occupant to control the temperature setpoint, request timed override of system operation, and provides a COMM module to service technicians. Symbio 400-B/UC400-B Compatible

X13651467020 X13511529010

Communication Module · Sold in packs of 12 · Provides local RJ22 connection to Trane® service tools for easy, low cost
maintenance.
Zone Sensor · Symbio 400-B/UC400-B compatible · External setpoint adjustment wheel

X13511527010

Zone Sensor · Symbio 400-B/UC400-B compatible · External setpoint adjustment wheel · ON and CANCEL buttons

34

WSHP-SVX014J-EN

Installation

Table 24. Zone sensor selection for use with SymbioTM 400-B/Tracer® UC400-B controller (continued)

Sensor

Part Number X1379084501

Description
Zone Sensor · Symbio 400-B/UC400-B compatible · External setpoint adjustment wheel · ON and CANCEL buttons · Fan switch AUTO-OFF

X1379044401

Temperature and relative humidity sensor · Symbio 400-B/UC400-B compatible

Awake

X13790993001 X13790992001

Commercial Touch Screen Programmable Zone Sensor

· Supports Standby, Occupied, and Unoccupied

· 7 day, 5+2 day, and 5+1+1 day

· Cannot be used with BAS as sensor ties up BACnet link. For use with factoryprogrammed Symbio 400-B/UC400-B.

Notes: ·

Adjusting the rotary switch on Symbio 400-B/UC400-B may be required to correspond address configuration in the sensor. See the installation manual for more information.

· Additional configuration is needed in the field to use the Programmable zone sensors (to put BAS points in service on Symbio 400-B/UC400B).

Residential Touch Screen Programmable Zone Sensor

· Supports Awake, Away, Home, and Sleep

· 7 day, 5+2 day, and 5+1+1 day

· Cannot be used with BAS as sensor ties up BACnet link. For use with factoryprogrammed Symbio 400-B/UC400-B.

Notes: ·

Adjusting the rotary switch on Symbio 400-B/UC400-B may be required to correspond address configuration in the sensor. See the installation manual for more information.

· Additional configuration is needed in the field to use the Programmable zone sensors (to put BAS points in service on Symbio 400-B/UC400B).

WSHP-SVX014J-EN

35

Installation

Table 25. Wireless zone sensor selection for use with Symbio 400-B/UC400-B controller

Sensor

Part Number X13790955010

Description
Trane Air-Fi® WCS-SD (display) · Symbio 400-B/UC400-B Compatible · Easy-to-use interface for clear and simple monitoring and control

X13790956010

Trane Air-Fi WCS-SB (base) · Symbio 400-B/UC400-B Compatible · Simplicity · Eliminates local temperature control when higher control level is required.

X13790973030

Wireless communications sensor accessory--2% relative humidity (RH) sensor module (WCS-SH) The optional RH sensor module plugs in to any WCS model, further simplifying installation by eliminating the needed for additional wiring.

Controls Using 24 Vac
Before installing any wire, refer to the electrical access locations in the Unit Dimensions and Weights sections of this manual.
Ensure that the AC control wiring between the controls and the unit termination point does not exceed 3 Ohms/ conductor for the length of the run.

NOTICE
Component Failure!
Resistance in excess of 3 ohms per conductor could result in component failure due to insufficient AC voltage supply.
Do not exceed three (3) ohms per conductor for the length of the run.

Check all loads and conductors for grounds, shorts, and mis-wiring. Use copper conductors unless otherwise specified. Do not run the AC low-voltage wiring in the same conduit with the high voltage power wiring.

Table 26. 24V AC conductors

Distance from unit to control

Recommended wire size

000-460 ft

18 gauge

461-732 ft

16 gauge

733-1000 ft

14 gauge

Low-voltage connection diagrams for deluxe 24 V control packages for these thermostats mounted on 0.75 to 6 ton equipment sizes are shown in the figures below.
Figure 24. Low voltage wire connection

36

WSHP-SVX014J-EN

Figure 25. Low voltage single wire connection

Figure 27. Deluxe controls

Installation

Make connection for a single-wire by inserting a single wire after stripping off the coating.
Figure 26. Low voltage stranded wire connection

Figure 28. TP1 connection type

Follow the steps to connect the stranded wire:
1. Release the spring with a dedicated screwdriver (blade width 2.5 mm)
2. Insert the stripped cable as far as it gets inserted.
3. Complete the connection by removing the screwdriver.

Present on all 0.5 to 5 ton H/V units.

WSHP-SVX014J-EN

37

Installation
Figure 29. Deluxe controls with WSE or DX two-stage

Figure 32. Deluxe controls general alarm and compressor disable

TP2 1 - (Y2)Compressor/Cool stage 2

Figure 30. TP2 connection type
Only present on units with Deluxe 24V controls and either 2-speed compressor (DXV/H) or water side economizer (WSE) coil DX and WSE on DLX. Figure 31. Deluxe controls humidistat connections between wires H1 and H2 in control box

Deluxe board (1U1) connections
AL1, AL2 - Alarm Contact output
CD1, CD2 - Compressor Disable input (24Vac)
For installation, operation and programming see BASSVX065*-EN (UC400-B) and BAS-SVX092*-EN (SymbioTM 400-B).
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

38

WSHP-SVX014J-EN

External Smoke Detection Wiring to Unit
Deluxe Controller
To inhibit operation of the compressor and fan for a safety shutdown, it is necessary to break the wire (21X) from the 24 Volt transformer to the 1TB1 terminal block. This can be done with the dry contacts of a relay. When that connection is opened, it terminates voltage to both the deluxe controller and the thermostat, which stops/prevents all control function to the fan and compressor.
SymbioTM 400-B/UC400-B Controller
To inhibit operation of the compressor and fan for a safety shutdown, it is necessary to break the wire (21A) from the 24 Volt transformer to the Symbio 400-B/UC400-B (1U1). This can be done with the dry contacts of a relay. When that connection is opened, it terminates the power voltage to the controller, which stops/prevents all control function including the fan and compressor.
Airflow Adjustment
WARNING
Rotating Components!
Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury. During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks.
Units with Deluxe 24V controls
The ECM is programmed for constant torque and delivers airflow similar to a PSC motor while operating at a higher efficiency.

Figure 33. ECM control box

Installation

Figure 34. ECM control board

1. Potentiometer will be used to adjust the PWM output
2. Seven segment display
Using a screwdriver, the potentiometer will be used to adjust the PWM output from 20% to 100% PWM. Increasing the PWM will increase the motor speed. When setting the airflow for air balancing, the high-speed terminal (GH) must have 24 Vac signal. This will ensure that the PWM output will be adjusted for the full load airflow.
The display will show the commanded motor speed percentage. If running on low speed (GL), the low-speed value will be displayed. If running in GH the high-speed value will be displayed. If both GH and GL input signals are present, the PWM output value will be the GH value. Note: ECM control board is only on units with Deluxe 24V
controls. Tracer® TU is used to adjust fan speed on units with SymbioTM 400-B/UC400-B controls.

WSHP-SVX014J-EN

39

Installation
Waterside Economizer Installation
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
Waterside Economizer Installation for Horizontal 0.75 to 6 Ton Units
The following steps were sequenced to aid in the installation and pairing of a water side economizer to a 0.75 to 6 ton horizontal water source heat pump.
1. Remove the filter bracket from the unit. It is secured by four screws: three on top (circled) and two on the bottom (not shown). Do not discard the filter brackets.
Figure 35. Step 1

fasteners (total of four for each bracket). The engagement hole locations and L-Bracket can be seen in the Figure 36, p. 40 . Figure 36. Step 2
3. Attach the filter bracket to the waterside economizer using the five screws removed earlier. Install the air filter.
4. Install the braided hose connecting point A (leaving the WSE) to point B (entering the WSHP). Connect the supply water to point D and the return water to point C.
Figure 37. Step 4

2. Mount the waterside economizer to the unit. It is secured to the unit using the three engagement holes used for the filter bracket on the top. Secure the sides of the economizer using the two L-Brackets on each side by lining up the engagement holes for the
40

5. Locate the entering water sensor that is located behind the unit's control box, and wire tie it to the water SUPPLY side of the piping. The sensor must be mounted before the two-position valve. Attaching the sensor anywhere else will cause the WSE to not operate correctly. Bundle up any excess sensor wire and wire tie the bundle neatly.
6. Locate the WSE valve wires (35B (COM), 36B (OPEN), 37B (CLOSE)) behind control box, and connect to the valve actuator. Bundle up any excess wire and wire tie the bundle neatly. Direction of rotation is reversible with switch.
7. Insulate the economizing piping package and the associated hoses via field pipe insulation. Insulating the
WSHP-SVX014J-EN

piping will prevent condensation from forming on the pipe and dripping on the floor.

Notes: ·

Trane does not provide insulation on the economizing piping package. The insulation must be field provided and field installed.

· Trane does not provide condensate overflow protection of the waterside economizer. This must be field provided and installed.

8. Field pipe the drain lines of the waterside economizer and water-source heat pump. Both the WSE and unit condensate drains must be separately trapped for proper handling of condensation (see Figure 38, p. 41 ). Both Vertical and Horizontal units will be piped similar to each other. The drain connection is located on the bottom side of the economizing coil.

Figure 38. Step 8

H

J

L

H
L J

NEGATIVE PRESSURE TRAPPING
H=1" (25.4 mm) FOR EVERY 1" (25.4 mm) OF MAXIMUM NEGATIVE STATIC PRESSURE +1" (25.4 mm).
J= HALF OF H.
L=H+J+ PIPE DIAMETER +INSULATION.

Installation

Table 27. Economizer part numbers

Supply-Air Arrangement

Unit

Part Number

Left Supply Right Supply

EXVG009-012
EXVG015
EXVG018-024, DXVG024
EXVG030-036, DXVG036
EXVG042-048, DXVG048
EXVG060-070, DXVG060-070
EXVG009-012
EXVG015
EXVG018-024, DXVG024
EXVG030-036, DXVG036
EXVG042-048, DXVG048
EXVG060-070, DXVG060-070

WSHPECN00016 WSHPECN00017 WSHPECN00018 WSHPECN00019 WSHPECN00020 WSHPECN00021 WSHPECN00023 WSHPECN00024 WSHPECN00025 WSHPECN00026 WSHPECN00027 WSHPECN00028

Waterside Economizer Installation for Vertical Units
The following steps were sequenced to aid in the installation and pairing of a water side economizer to a EXV and DXV water source heat pump.
1. Remove the filter bracket from the unit. It is secured by five screws: three on top (circled) and two on the bottom (not shown). Do not discard the filter brackets.

WSHP-SVX014J-EN

41

Installation
Figure 39. Step 1

Figure 41. Step 3

2. Mount the waterside economizer to the unit. It is secured to the unit using the five engagement holes that were used for the filter brackets: three on top and two on the bottom.
Figure 40. Step 2

4. Install the braided hose connecting point A (leaving the WSE) to point B (entering the WSHP). Connect the supply water to point D and the return water to point C.
Figure 42. Step 4

3. Attach the filter brackets to the waterside economizer using five screws. Install the air filter.
42

5. Locate the entering water sensor that is located behind the unit's control box, and wire tie it to the water SUPPLY side of the piping. The sensor must be mounted before the two-position valve. Attaching the sensor anywhere else will cause the WSE to not operate correctly. Bundle up any excess sensor wire and wire tie the bundle neatly.
6. Locate the WSE valve wires (35B (COM), 36B (OPEN), 37B (CLOSE)) behind control box, and connect to the valve actuator. Bundle up any excess wire and wire tie the bundle neatly. Direction of rotation is reversible with switch.
7. Insulate the economizing piping package and the associated hoses via field pipe insulation. Insulating the
WSHP-SVX014J-EN

piping will prevent condensation from forming on the pipe and dripping on the floor.

Notes: ·

Trane does not provide insulation on the economizing piping package. This insulation must be field provided and field installed.

· Trane does not provide condensate overflow protection of the waterside economizer. This must be field provided and installed.

8. Field pipe the drain lines of the waterside economizer and water-source heat pump together prior to installing a condensate trap for proper trapping of condensation (see ). The vertical units will be piped similar to the horizontal units.

Figure 43. Step 8

Installation

Table 28. Economizer part numbers

Supply-Air Arrangement

Unit

Part Number

Left Supply Right Supply

EXVG009-012
EXVG015
EXVG018-024, DXVG024
EXVG030-036, DXVG036
EXVG042-048, DXVG048
EXVG060-070, DXVG060-070
EXVG009-012
EXVG015
EXVG018-024, DXVG024
EXVG030-036, DXVG036
EXVG042-048, DXVG048
EXVG060-070, DXVG060-070

WSHPECN00002 WSHPECN00003 WSHPECN00004 WSHPECN00005 WSHPECN00006 WSHPECN00007 WSHPECN00009 WSHPECN00010 WSHPECN00011 WSHPECN00012 WSHPECN00013 WSHPECN00014

WSHP-SVX014J-EN

43

Waterside Economizer Start-Up Sequence

1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
3. Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/ temperature plugs and comparing to tables contained in specification sheet data. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9 to 12ºF); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
4. Check the cooling refrigerant pressures against values in "Operating Pressures," p. 52.
Note: If cooling mode is activated, and the entering water temperature of the heat pump falls below 55ºF, the 2-position, water side economizing valve will become energized (open) and compressor operation will halt allowing for free cooling in the space.
5. Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-energize.

6. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat system switch to the HEAT position.
9. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately 5 to 9°F leaving the heat exchanger should be noted. The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures against values in "Operating Pressures," p. 52.
Note: For units with boilerless electric heat option: In heating mode, if the entering water temperature of the heat pump falls below 45ºF, the electric heater will be energized, and compressor operation will halt. Once the entering water temperature rises above 50ºF, the boilerless controls returns the unit.
11. Set the thermostat to maintain the desired space temperature.
12. Instruct the owner on system operation.

Table 29. Waterside economizing three-way valve specifications (DXHG/DXVG units)

Unit Size

Valve Conn. Size

Valve Pres. Rating

DXHG/DXVG 024

3/4 FPT

600 psi

DXHG/DXVG 036-070

1 FPT

600 psi

Valve Close-off pressure 200 psi
200 psi

Valve Temp. Range

Actuator

0ºF to 212ºF -18ºC to 121ºC
0ºF to 212ºF -18ºC to 121ºC

Non-spring return type 24 Vac +/- 20%
135 second stroke time 24 Cv at full port
Non-spring return type 24 Vac +/- 20%
135 second stroke time 30 Cv at full port

Note: The valve body is constructed from forged brass with nickel plating, with the ball and stem constructed of stainless steel. For other information pertaining to the economizing water valve, see the valve's data plate.

Table 30. Waterside economizing three-way valve specifications (EXHG/EXVG units)

Unit Size

Valve Conn. Size

Valve Pres. Rating

Valve Close-off pressure

Valve Temp. Range

EXHG 009-015

1/2 FPT

600 psi

200 psi

0°F to 250°F -18°C to 121°C

EXHG 018-036 EXVG 009-024

3/4 FPT

600 psi

200 psi

0°F to 250°F -18°C to 121°C

Actuator
Non-spring return type 24 Vac +/- 20%
135 second stroke time 10 Cv at full port
Non-spring return type 24 Vac +/- 20%
135 second stroke time 24 Cv at full port

44

WSHP-SVX014J-EN

Waterside Economizer Start-Up Sequence

Table 30. Waterside economizing three-way valve specifications (EXHG/EXVG units) (continued)

Unit Size

Valve Conn. Size

Valve Pres. Rating

EXHG 042-070 EXVG 030-070

1 FPT

600 psi

Valve Close-off pressure
200 psi

Valve Temp. Range

Actuator

0°F to 250°F -18°C to 121°C

Non-spring return type 24 Vac +/- 20%
135 second stroke time 30 Cv at full port

Note: The valve body is constructed from forged brass with nickel plating, with the ball and stem constructed of stainless steel. For other information pertaining to the economizing water valve, see the valve's data plate.

WSHP-SVX014J-EN

45

Electrical Data

Table 31. Electrical data - 0.75 to 6 tons, EX*009-070

Model No.

Unit Volts

Total Unit FLA

Comp RLA

Comp LRA

Blower Motor Blower Motor

FLA

HP

Minimum Circuit
Ampacity

EXV/H009

208-230/60/1

4.2

3.6

27.0

0.6

EXV/H009

265/60/1

3.5

3.0

22.0

0.5

EXV/H012

208-230/60/1

6.6

5.7

27.0

0.9

EXV/H012

265/60/1

5.3

4.5

32.0

0.8

EXV/H015

208-230/60/1

8.1

7.3

36.0

0.8

EXV/H015

265/60/1

5.5

4.8

30.0

0.7

EXV/H018

208-230/60/1

9.8

8.5

38.0

1.3

EXV/H018

265/60/1

7.9

6.8

35.0

1.1

EXV/H024

208-230/60/1

15.2

13.5

58.3

1.7

EXV/H024

265/60/1

10.5

9.0

54.0

1.5

EXV/H024

208-230/60/3

8.8

7.1

55.4

1.7

EXV/H024

460/60/3

4.4

3.5

28.0

0.9

EXV/H030

208-230/60/1

15.6

14.1

73.0

1.5

EXV/H030

265/60/1

12.5

11.2

60.0

1.3

EXV/H030

208-230/60/3

10.4

8.9

58.0

1.5

EXV/H030

460/60/3

5.0

4.2

28.0

0.8

EXV/H036

208-230/60/1

18.0

16.0

77.0

2.0

EXV/H036

265/60/1

13.9

12.2

72.0

1.7

EXV/H036

208-230/60/3

12.0

10.0

71.0

2.0

EXV/H036

460/60/3

5.7

4.7

38.0

1.0

EXV/H042

208-230/60/1

19.9

16.7

79.0

3.2

EXV/H042

208-230/60/3

13.6

10.4

73.0

3.2

EXV/H042

460/60/3

7.4

5.8

38.0

1.6

EXV/H048

208-230/60/1

20.5

17.9

112.0

2.6

EXV/H048

208-230/60/3

16.1

13.5

88.0

2.6

EXV/H048

460/60/3

7.3

6.0

44.0

1.3

EXV/H060

208-230/60/1

25.2

21.4

135.0

3.8

EXV/H060

208-230/60/3

18.3

14.5

98.0

3.8

EXV/H060

460/60/3

8.2

6.3

55.0

1.9

EXV/H070

208-230/60/1

31.4

26.4

134.0

5.0

EXV/H070

208-230/60/3

21.0

16.0

110.0

5.0

EXV/H070

460/60/3

10.3

7.8

52.0

2.5

1/3

6/6

1/3

5

1/3

8/8

1/3

7

1/3

10/10

1/3

7

1/2

12/12

1/2

10

1/2

19/19

1/2

13

1/2

11/11

1/2

6

3/4

20/20

3/4

16

3/4

13/13

3/4

7

3/4

23/23

3/4

17

3/4

15/15

1

7

3/4

25/25

3/4

17/17

1

9

1

25/25

1

20/20

1

9

1

31/31

1

22/22

1

10

1

39/39

1

26/26

1

13

Maximum Overcurrent Protective
Device 15/15
15 15/15
15 15/15
15 20/20
15 30/30
20 15/15
15 30/30
25 20/20
15 35/35
25 20/20
15 40/40 25/25
15 40/40 30/30
15 50/50 35/35
15 60/60 40/40
20

46

WSHP-SVX014J-EN

Electrical Data

Table 32. Electrical data - 2 to 6 tons, DX*024-070

Model No.

Unit Volts

Total Unit FLA

Comp RLA

Comp LRA

Blower Motor Blower Motor

FLA

HP

Minimum Circuit
Ampacity

DXV/H024

208-230/60/1

13.3

11.7

58.3

1.6

DXV/H024

265/60/1

10.5

9.1

54.0

1.4

DXV/H024

208-230/60/3

8.1

6.5

55.4

1.6

DXV/H024

460/60/3

4.3

3.5

28.0

0.8

DXV/H036

208-230/60/1

15.1

13.1

73.0

2.0

DXV/H036

265/60/1

11.9

10.2

60.0

1.7

DXV/H036

208-230/60/3

10.7

8.7

58.0

2.0

DXV/H036

460/60/3

5.3

4.3

28.0

1.0

DXV/H048

208-230/60/1

20.4

17.9

96.0

2.5

DXV/H048

208-230/60/3

16.7

14.2

88.0

2.5

DXV/H048

460/60/3

7.5

6.2

44.0

1.3

DXV/H060

208-230/60/1

25.0

21.2

104.0

3.8

DXV/H060

208-230/60/3

17.8

14.0

83.1

3.8

DXV/H060

460/60/3

8.3

6.4

41.0

1.9

DXV/H070

208-230/60/1

31.9

26.9

139.9

5.0

DXV/H070

208-230/60/3

21.5

16.5

110.0

5.0

DXV/H070

460/60/3

9.7

7.2

52.0

2.5

1/2

17/17

1/2

13

1/2

10/10

1/2

6

3/4

19/19

3/4

15

3/4

13/13

1

7

1

25/25

1

21/21

1

10

1

31/31

1

22/22

1

10

1

39/39

1

26/26

1

12

Maximum Overcurrent Protective
Device 25/25
20 15/15
15 30/30
20 20/20
15 40/40 30/30
15 50/50 35/35
15 60/60 40/40
15

Table 33. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons)

MODEL EXV/H009 EXV/H009 EXV/H012 EXV/H012 EXV/H015 EXV/H015 EXV/H018 EXV/H018 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H036 EXV/H036 EXV/H036 EXV/H036

EH Size Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium Medium
Low Medium
High Low

Volts 208-230/60/1
265/60/1 208-230/60/1
265/60/1 208-230/60/1
265/60/1 208-230/60/1
265/60/1 208-230/60/1
265/60/1 208-230/60/3
460/60/3 208-230/60/1
265/60/1 208-230/60/3
460/60/3 208-230/60/1 208-230/60/1 208-230/60/1
265/60/1

kW 2.0/2.5
2.3 2.0/2.5
2.3 2.0/2.5
2.3 3.3/4.0
3.7 3.3/4.0
3.7 3.3/4.0
3.7 4.1/5.0
4.6 4.1/5.0
4.6 4.9/6.0 8.2/10.0 12.3/15.0
5.5

Amps 9.8/10.9
8.6 9.8/10.9
8.6 9.8/10.9
8.6 15.7/17.4
13.8 15.7/17.4
13.8 9.1/10.1
4.6 19.7/21.7
17.3 11.4/12.6
5.8 23.6/26.1 39.3/43.5 59.0/65.2
20.7

WSHP-SVX014J-EN

47

Electrical Data

Table 33. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)

MODEL EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070

EH Size Medium
High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High

Volts 265/60/1 265/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 208-230/60/3 208-230/60/3

kW 9.2 13.7 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0 8.2/10.0 12.3/15.0

48

Amps 34.5 51.8 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1 22.7/25.1 34.1/37.7
WSHP-SVX014J-EN

Table 33. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)

MODEL EXV/H070 EXV/H070 EXV/H070 DXV/H024 DXV/H024 DXV/H024 DXV/H024 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H036 DXV/H048 DXV/H048 DXV/H048 DXV/H048 DXV/H048 DXV/H048 DXV/H048 DXV/H048 DXV/H048 DXV/H060 DXV/H060 DXV/H060 DXV/H060 DXV/H060 DXV/H060 DXV/H060 DXV/H060 DXV/H060 DXV/H070 DXV/H070 DXV/H070 DXV/H070

EH Size Low
Medium High
Medium Medium Medium Medium
Low Medium
High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low Medium High Low

Volts 460/60/3 460/60/3 460/60/3 208-230/60/1 265/60/1 208-230/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 265/60/1 265/60/1 265/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 208-230/60/3 208-230/60/3 460/60/3 460/60/3 460/60/3 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3

kW 5.5 9.2 13.8 3.3/4.0 3.7 3.3/4.0 3.7 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.7 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0 8.2/10.0 12.3/15.0 5.5 9.2 13.8 4.9/6.0 8.2/10.0 12.3/15.0 4.9/6.0

WSHP-SVX014J-EN

Electrical Data
Amps 6.9 11.5 17.3
15.7/17.4 13.8
9.1/10.1 4.6
23.6/26.1 39.3/43.5 59.0/65.2
20.7 34.5 51.8 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1 22.7/25.1 34.1/37.7 6.9 11.5 17.3 23.6/26.1 39.3/43.5 59.0/65.2 13.6/15.1
49

Electrical Data

Table 33. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)

MODEL DXV/H070 DXV/H070 DXV/H070 DXV/H070 DXV/H070

EH Size Medium
High Low Medium High

Volts 208-230/60/3 208-230/60/3
460/60/3 460/60/3 460/60/3

kW 8.2/10.0 12.3/15.0
5.5 9.2 13.8

Note: Electric heat performance table with heat rise data can be found in Installation Instructions (WSHPSVN011*-EN).

Table 34. Electrical data - minimum and maximum

Digit 8

Rated Voltage

Hz

4

460

60

7

265

60

A

208-230

60

B

208-230

60

Ph

Minimum Utilization Voltage

3

414

1

239

1

197

3

187

Amps 22.7/25.1 34.1/37.7
6.9 11.5 17.3
Maximum Utilization Voltage 506 292 253 253

50

WSHP-SVX014J-EN

Pre-Start Checklist
Before energizing the unit, the following system devices must be checked:
· Is the high voltage power supply correct and in accordance with the nameplate ratings?
· Is phasing of the unit correct per compressor rotation (scroll compressor only)?
· Is the field wiring and circuit protection the correct size?
· Is the low voltage control circuit wiring correct per the unit wiring diagram?
· Is the piping system clean/complete and correct? (A recommendation of all system flushing of debris from the water-to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger be done in accordance with the Closed-Loop/Ground Source Heat Pump Systems Installation Guide).
· Is vibration isolation provided? (i.e. unit isolation pad, hose kits)
· Is unit serviceable? (See clearance specifications in Unit Dimensions and Weights).

· Are the low/high-side pressure temperature caps secure and in place?
· Are all the unit access panels secure and in place?
· Is the thermostat in the OFF position?
· Is the water flow established and circulating through all the units?
· Is the duct work correctly sized, run, taped, insulated and weather proofed with proper unit arrangement?
· Is the condensate line properly sized, run, trapped, pitched and primed?
· Is the zone sensor correctly wired and in a good location?
· Does the indoor blower turn freely without rubbing?
· Has all work been done in accordance with applicable local and national codes?
· Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?

WSHP-SVX014J-EN

51

Start-Up

Initial Unit Start-Up
Note: Start-up with the heat pump thermostat is included below:
1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
3. Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/ temperature plugs and comparing to tables contained in specification sheet data.
4. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 912ºF); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
5. Check the cooling refrigerant pressures against values in "Operating Pressures," p. 52.
6. Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-energize.
7. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
8. Turn the thermostat to the lowest setting.
9. Set the thermostat system switch to the HEAT position.
10. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately 5-9ºF leaving the heat exchanger should be noted. The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
11. Check the heating refrigerant pressures against values in "Operating Pressures," p. 52.
12. Set the thermostat to maintain the desired space temperature.
13. Instruct the owner on system operation.

Table 35. Checklist

MODE

Heat

Cool

Entering fluid temperature

_______F

_______F

Leaving fluid temperature

_______F

_______F

Temperature differential

_______F

_______F

Return-air temperature DB/WB

_______F

_______F

Table 35. Checklist (continued)

MODE
Supply-air temperature DB/WB

Heat _______F

Temperature differential
Water coil heat exchanger (Water Pressure IN)

_______F ________PSIG

Water coil heat exchanger (Water Pressure OUT)

________PSIG

Pressure Differential COMPRESSOR Amps

_________PSIG

Volts
Discharge line temperature (after 10 minutes)

_______F

Cool _______F _______F ________PSIG ________PSIG _________PSIG
_______F

Start-Up Checklist and Log
Installing Contractor: Use this checklist to thoroughly check-out the system and units before and during start-up. (This form need not be returned to the factory unless requested during technical service support).
Job Name:
Model Number:
Date:
Serial Number:
To minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.
Operating Pressures
There are many variables (airflow, air temperatures) in an air conditioning system that will affect operating refrigerant pressures and temperatures. The charts below shows approximate conditions and is based on air flow at the rated SCFM, entering air at 80.6°F (DB), 66.2°F (WB) in cooling, 68°F (DB) in heating. (+)Heating data with 35°F EWT is based on the use of an anti-freeze solution having a freezing point 20°F lower than the minimum expected entering temperature.

52

WSHP-SVX014J-EN

Start-Up

Table 36. Operating pressures in cooling/heating for DX* units

Model DXV/H024

Entering

Water Temp Entering
Water Temp

Water Flow (GPM)

(°F)

32

4.80

DXV/H024

32

6.00

DXV/H024

45

4.80

DXV/H024

45

6.00

DXV/H024

55

4.80

DXV/H024

55

6.00

DXV/H024

68

4.80

DXV/H024

68

6.00

DXV/H024

75

4.80

DXV/H024

75

6.00

DXV/H024

86

4.80

DXV/H024

86

6.00

DXV/H024

95

4.80

DXV/H024

95

6.00

DXV/H036

32

7.20

DXV/H036

32

9.00

DXV/H036

45

7.20

DXV/H036

45

9.00

DXV/H036

55

7.20

DXV/H036

55

9.00

DXV/H036

68

7.20

DXV/H036

68

9.00

DXV/H036

75

7.20

DXV/H036

75

9.00

DXV/H036

86

7.20

DXV/H036

86

9.00

DXV/H036

95

7.20

DXV/H036

95

9.00

DXV/H048

32

9.60

DXV/H048

32

12.00

DXV/H048

45

9.60

DXV/H048

45

12.00

DXV/H048

55

9.60

DXV/H048

55

12.00

DXV/H048

68

9.60

DXV/H048

68

12.00

DXV/H048

75

9.60

DXV/H048

75

12.00

Suction Pressure
(psig) -- --
132-152 132-151 132-152 132-152 136-156 136-156 139-159 138-159 143-164 143-164 145-167 145-167
-- -- 138-159 138-159 140-161 140-161 143-164 143-164 145-166 145-166 147-170 147-169 149-172 149-172 -- -- 135-155 135-155 137-157 137-157 141-162 140-162 142-164 142-164

Operating Data Cooling

Discharge Pressure
(pgig)

Water Temp Air Temp Rise (°F) Drop (°F DB)

Suction Pressure
(psig)

--

--

--

89-103

--

--

--

91-105

173-220

11-14

24-30

109-126

166-212

9-12

24-30

112-129

200-254

11-14

24-29

125-144

193-246

9-11

24-29

129-148

239-305

11-14

23-29

149-172

232-296

9-11

23-29

154-177

263-335

11-14

23-28

164-188

256-326

9-11

23-29

169-195

303-386

11-14

22-28

190-218

296-376

9-11

23-28

197-226

339-432

11-14

22-28

--

331-422

9-11

22-28

--

--

--

--

90-104

--

--

--

92-105

177-225

11-14

24-29

109-125

170-217

9-11

24-29

111-128

204-260

11-14

23-29

125-143

198-251

9-11

23-29

128-147

243-310

10-13

22-28

148-170

237-301

8-11

23-28

152-175

265-338

10-13

22-28

163-187

259-330

8-10

22-28

168-193

304-387

10-13

22-27

190-218

298-379

8-10

22-27

196-225

341-433

10-13

21-27

--

334-425

8-10

21-27

--

--

--

--

87-100

--

--

--

89-102

179-227

11-14

24-29

105-121

172-219

9-11

24-29

108-124

206-262

11-14

23-28

121-139

200-254

9-11

23-29

124-142

246-313

10-13

22-28

143-165

239-305

8-11

22-28

147-169

268-341

10-13

22-27

157-181

261-333

8-10

22-28

162-186

Heating

Discharge Pressure
(psig)

Water Temp Air Temp Drop (°F) Rise (°F DB)

285-362

5-7

18-28

288-366

4-5

19-28

301-383

7-8

23-33

304-387

5-7

24-33

318-404

8-10

27-37

321-408

6-8

28-38

342-436

9-12

32-42

345-439

7-10

33-43

354-451

10-13

34-45

357-455

8-10

35-46

373-475

11-14

38-49

376-478

9-11

39-50

--

--

--

--

--

--

262-333

5-6

16-24

263-335

4-5

16-25

278-354

6-7

19-28

280-357

5-6

20-29

293-373

7-9

22-32

295-376

5-7

23-32

314-399

8-10

27-37

317-403

7-8

27-37

326-415

9-11

29-39

329-419

7-9

30-40

346-440

10-12

33-44

350-446

8-10

34-45

--

--

--

--

--

--

260-331

5-6

16-25

262-333

4-5

16-25

278-353

6-8

20-29

280-356

5-6

20-30

292-372

7-9

23-33

294-375

6-7

24-34

312-398

8-11

28-38

316-402

7-9

29-39

324-412

9-12

30-41

328-417

7-9

31-42

WSHP-SVX014J-EN

53

Start-Up

Table 36. Operating pressures in cooling/heating for DX* units (continued)

Model DXV/H048

Entering

Water Temp Entering
Water Temp

Water Flow (GPM)

(°F)

86

9.60

DXV/H048

86

12.00

DXV/H048

95

9.60

DXV/H048

95

12.00

DXV/H060

32

12.00

DXV/H060

32

15.00

DXV/H060

45

12.00

DXV/H060

45

15.00

DXV/H060

55

12.00

DXV/H060

55

15.00

DXV/H060

68

12.00

DXV/H060

68

15.00

DXV/H060

75

12.00

DXV/H060

75

15.00

DXV/H060

86

12.00

DXV/H060

86

15.00

DXV/H060

95

12.00

DXV/H060

95

15.00

DXV/H070

32

14.00

DXV/H070

32

17.50

DXV/H070

45

14.00

DXV/H070

45

17.50

DXV/H070

55

14.00

DXV/H070

55

17.50

DXV/H070

68

14.00

DXV/H070

68

17.50

DXV/H070

75

14.00

DXV/H070

75

17.50

DXV/H070

86

14.00

DXV/H070

86

17.50

DXV/H070

95

14.00

DXV/H070

95

17.50

Suction Pressure
(psig) 145-167 145-166 146-168 146-168
-- -- 136-156 136-157 138-159 138-159 141-162 141-162 143-164 143-164 146-167 145-167 148-170 148-170 -- -- 130-150 130-150 132-151 131-151 136-156 136-156 139-160 139-159 143-164 142-164 145-166 144-166

Operating Data Cooling

Discharge Pressure
(pgig)

Water Temp Air Temp Rise (°F) Drop (°F DB)

Suction Pressure
(psig)

307-391

10-13

21-27

183-211

301-383

8-10

21-27

189-218

343-437

10-13

21-27

--

337-428

8-10

21-27

--

--

--

--

87-101

--

--

--

89-103

180-230

10-12

22-28

106-122

174-222

8-10

22-28

108-124

210-267

10-12

22-27

121-139

203-259

8-10

22-27

124-142

251-320

9-12

21-27

143-165

245-312

8-10

21-27

147-170

275-350

9-12

21-27

158-181

269-342

7-10

21-27

162-187

316-402

9-12

20-26

184-211

310-394

7-9

20-26

189-218

353-450

9-12

20-26

--

347-442

7-9

20-26

--

--

--

--

89-102

--

--

--

91-104

171-218

11-14

23-28

107-123

167-213

8-11

23-28

110-126

199-254

10-13

22-28

122-140

194-247

8-11

22-28

125-144

237-302

10-13

22-28

144-165

232-295

8-11

22-28

148-170

260-331

10-13

22-27

157-181

254-324

8-11

22-27

162-187

300-382

10-13

21-27

183-211

294-374

8-10

21-27

189-218

336-427

10-13

21-26

--

330-420

8-10

21-26

--

Heating

Discharge Pressure
(psig)

Water Temp Air Temp Drop (°F) Rise (°F DB)

343-437

10-13

34-45

348-443

8-11

35-46

--

--

--

--

--

--

285-363

5-6

15-24

288-366

4-5

16-24

299-381

6-7

19-28

302-384

5-6

20-29

313-398

7-9

22-32

315-401

6-7

23-33

333-424

8-10

27-37

335-427

7-8

28-38

343-436

9-11

29-40

345-439

7-9

30-40

361-460

10-13

33-44

364-463

8-10

34-45

--

--

--

--

--

--

277-353

4-6

16-25

278-354

4-5

17-25

296-376

6-7

20-30

298-379

5-6

21-30

312-397

6-8

23-33

314-400

5-7

24-34

333-424

8-10

28-38

336-428

6-8

28-39

345-439

8-11

30-40

348-443

7-9

31-41

363-462

10-12

34-45

367-467

8-10

35-45

--

--

--

--

--

--

54

WSHP-SVX014J-EN

Start-Up

Table 37. Operating pressures in cooling/heating for EX* units

Model
EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H009 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H012 EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H015

Entering Water Temp
Entering Water
Temp (°F) 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75

Water Flow (GPM)
1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 1.80 2.25 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 2.40 3.00 3.00 3.75 3.00 3.75 3.00 3.75 3.00 3.75 3.00 3.75

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

-- -- 137-157 137-157 138-158 137-158 143-164 142-164 146-168 145-167 150-173 150-173 153-176 153-176 -- -- 136-156 135-156 137-158 137-157 140-161 140-161 142-163 141-163 144-166 144-166 146-169 146-168 -- -- 131-151 131-151 134-154 134-154 138-159 138-159 140-161 140-161

-- -- 170-217 163-208 198-252 191-243 238-302 231-294 258-328 251-320 296-376 289-368 333-424 326-415 -- -- 173-220 165-210 201-255 193-246 241-306 233-297 263-334 255-325 302-384 294-375 340-432 332-423 -- -- 176-224 169-215 207-263 199-253 247-315 240-305 268-341 260-331

-- -- 10-13 8-11 10-13 8-11 10-13 8-10 10-13 8-10 10-13 8-10 10-12 8-10 -- -- 12-15 9-12 11-15 9-12 11-14 9-11 11-14 9-11 11-13 8-11 10-13 8-11 -- -- 12-16 10-12 12-15 10-12 12-15 10-12 12-15 9-12

-- -- 23-28 23-28 23-28 23-28 22-27 22-28 22-27 22-27 21-27 21-27 20-26 20-26 -- -- 25-30 25-30 24-29 24-30 23-29 23-29 23-28 23-28 22-27 22-27 21-27 21-27 -- -- 24-29 24-29 23-29 23-29 23-28 23-28 23-28 23-28

94-108 96-110 115-132 118-135 133-152 136-156 158-182 162-187 173-199 178-205 200-230 207-238
-- -- 91-104 92-106 111-128 114-131 128-148 132-152 153-176 158-182 168-193 174-200 194-223 201-232 -- -- 89-103 91-105 109-126 112-128 125-144 129-148 149-172 154-177 164-189 169-194

256-326 257-327 274-348 276-351 288-366 290-369 308-391 311-396 319-406 323-411 338-430 343-436
-- -- 265-338 267-340 286-364 288-367 302-385 305-389 325-414 329-419 338-430 343-436 359-457 365-465 -- -- 268-341 270-343 287-365 289-367 301-383 304-387 321-409 325-413 333-424 337-429

4-5 3-4 5-7 4-6 6-8 5-7 7-9 6-8 8-10 7-9 9-12 7-10 -- -- 5-6 4-5 6-8 5-6 7-9 6-8 9-11 7-9 10-13 8-10 11-14 9-12 -- -- 5-6 4-5 6-8 5-6 7-9 6-8 9-11 7-9 10-12 8-10

13-21 13-22 19-28 19-28 22-31 23-32 25-35 26-36 28-38 28-39 31-42 31-42
-- -- 17-26 17-26 22-31 22-32 26-36 26-36 31-41 32-42 34-44 35-45 37-48 38-50 -- -- 18-27 18-27 22-32 23-32 26-36 26-36 31-41 32-42 33-44 34-45

WSHP-SVX014J-EN

55

Start-Up

Table 37. Operating pressures in cooling/heating for EX* units (continued)

Model
EXV/H015 EXV/H015 EXV/H015 EXV/H015 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H018 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H024 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H030

Entering Water Temp
Entering Water
Temp (°F) 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55

Water Flow (GPM)
3.00 3.75 3.00 3.75 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 3.60 4.50 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 4.80 6.00 6.00 7.50 6.00 7.50 6.00 7.50

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

143-164 143-164 145-166 145-166
-- -- 133-153 133-153 134-155 134-154 138-159 138-159 141-162 141-162 144-166 144-166 146-168 146-168 -- -- 133-153 133-153 133-153 133-153 136-157 136-157 139-159 138-159 142-163 141-163 144-165 143-165 -- -- 136-157 136-156 136-157 136-156

306-389 298-380 345-439 337-429
-- -- 175-223 168-213 203-259 196-249 243-310 236-300 266-338 258-328 304-388 297-378 340-433 333-424 -- -- 176-224 171-217 203-258 197-250 243-310 236-300 267-340 260-331 308-392 300-382 344-438 337-428 -- -- 176-224 170-216 204-259 197-251

12-15 9-12 11-14 9-12 -- -- 12-15 10-12 12-15 10-12 12-15 9-12 12-15 9-12 12-15 9-12 11-14 9-12 -- -- 12-15 9-12 12-15 9-12 11-14 9-12 11-14 9-12 11-14 9-11 11-14 9-11 -- -- 12-15 9-12 12-15 9-12

22-28 22-28 22-27 22-27
-- -- 25-31 26-31 25-30 25-31 24-30 24-30 24-29 24-29 23-29 23-29 22-28 23-28 -- -- 23-28 23-28 22-28 22-28 22-28 22-28 22-27 22-28 21-27 21-27 21-27 21-27 -- -- 25-30 25-30 25-30 25-30

190-218 196-226
-- -- 92-105 93-107 111-128 114-131 127-146 130-150 150-173 155-178 165-190 170-196 191-220 198-228 -- -- 89-102 90-104 109-125 111-128 125-144 128-148 149-171 153-176 163-188 169-194 189-217 196-226 -- -- 90-103 92-105 109-125 111-128 124-143 128-147

354-451 359-457
-- -- 274-349 276-351 294-374 296-376 311-396 314-400 336-428 340-433 350-445 354-451 371-472 376-479 -- -- 280-356 282-359 302-384 305-388 321-408 324-412 346-440 350-445 359-457 363-463 379-482 384-488 -- -- 260-330 263-334 288-367 292-371 310-395 313-399

11-14 9-12 -- -- 5-6 4-5 6-8 5-6 7-9 6-8 9-11 7-9 10-12 8-10 11-14 9-12 -- -- 5-6 4-5 7-8 5-7 8-10 6-8 9-12 7-10 10-13 8-10 11-14 9-12 -- -- 5-6 4-5 6-8 5-7 8-10 6-8

38-49 39-50
-- -- 17-26 17-26 22-32 23-32 26-36 27-36 31-41 32-42 34-45 35-45 38-49 39-50 -- -- 17-26 18-27 23-33 24-33 27-37 28-38 32-42 33-43 35-46 35-46 39-50 39-51 -- -- 18-27 18-27 22-32 23-32 26-36 27-37

56

WSHP-SVX014J-EN

Start-Up

Table 37. Operating pressures in cooling/heating for EX* units (continued)

Model
EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H030 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H036 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H042 EXV/H048 EXV/H048

Entering Water Temp
Entering Water
Temp (°F) 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32

Water Flow (GPM)
6.00 7.50 6.00 7.50 6.00 7.50 6.00 7.50 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 7.20 9.00 8.40 10.50 8.40 10.50 8.40 10.50 8.40 10.50 8.40 10.50 8.40 10.50 8.40 10.50 9.60 12.00

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

138-159 138-159 140-162 140-161 143-165 143-165 145-167 145-167
-- -- 137-157 137-157 137-158 137-158 140-161 140-161 142-163 142-163 145-167 145-166 147-169 147-169 -- -- 138-158 138-158 138-159 138-159 140-161 140-161 142-163 142-163 145-166 145-166 146-168 146-168 -- --

245-312 237-302 269-342 261-333 310-395 302-385 347-441 339-431
-- -- 177-226 170-216 205-261 198-252 246-313 239-304 268-342 261-333 308-392 301-383 345-439 338-430 -- -- 173-220 168-213 201-256 195-249 240-306 234-297 263-335 257-327 304-386 297-378 340-433 333-424 -- --

12-15 9-12 12-15 9-12 11-14 9-11 11-14 9-11 -- -- 11-14 9-11 11-14 9-11 11-14 9-11 11-14 9-11 11-14 8-11 10-13 8-11 -- -- 11-13 8-11 10-13 8-11 10-13 8-10 10-13 8-10 10-13 8-10 10-12 8-10 -- --

24-29 24-29 24-29 24-29 23-29 23-29 23-28 23-28
-- -- 24-29 24-29 24-29 24-29 23-29 23-29 23-28 23-28 22-28 22-28 22-27 22-27 -- -- 23-29 23-29 23-28 23-28 22-28 22-28 22-27 22-27 21-27 21-27 21-26 21-26 -- --

148-170 152-175 162-187 168-193 189-217 195-225
-- -- 90-104 92-106 109-125 111-128 124-142 127-146 146-168 150-173 160-184 165-190 186-214 192-221 -- -- 89-102 91-104 108-124 110-127 123-142 126-145 146-169 151-173 161-185 166-191 188-216 194-223 -- -- 87-100 89-102

333-423 336-427 343-437 346-441 367-467 370-471
-- -- 270-344 272-346 290-369 293-372 306-390 309-393 328-418 332-422 340-433 344-438 360-458 365-464 -- -- 256-326 257-327 274-348 276-351 289-368 292-371 310-395 314-399 322-410 326-414 340-433 345-439 -- -- 261-332 262-334

9-12 7-9 10-12 8-10 11-14 9-11 -- -- 5-6 4-5 6-8 5-6 7-9 6-8 9-11 7-9 9-12 8-10 10-13 9-11 -- -- 4-6 4-5 6-7 5-6 7-9 6-7 8-11 7-9 9-12 7-9 10-13 8-11 -- -- 5-6 4-5

31-41 32-42 34-44 34-45 38-49 38-50
-- -- 17-26 17-26 21-31 22-31 25-34 25-35 29-39 30-40 32-42 33-43 36-46 36-47 -- -- 15-24 15-24 19-29 20-29 23-33 24-33 28-38 28-39 30-41 31-41 34-45 35-46 -- -- 16-25 16-25

WSHP-SVX014J-EN

57

Start-Up

Table 37. Operating pressures in cooling/heating for EX* units (continued)

Model
EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H048 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H060 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070 EXV/H070

Entering Water Temp
Entering Water
Temp (°F) 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86 95 95 32 32 45 45 55 55 68 68 75 75 86 86

Water Flow (GPM)
9.60 12.00 9.60 12.00 9.60 12.00 9.60 12.00 9.60 12.00 9.60 12.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 12.00 15.00 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50 14.00 17.50

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

137-157 137-157 137-158 137-157 140-161 140-161 142-163 142-163 145-167 145-166 147-169 147-169
-- -- 133-153 133-152 134-154 134-154 138-159 138-159 140-161 140-161 143-165 143-164 145-167 145-167 -- -- 132-152 132-151 134-154 134-154 138-158 138-158 140-161 140-161 143-164 143-164

181-230 174-222 210-267 203-258 250-318 243-310 273-347 266-339 313-398 306-390 350-446 344-438
-- -- 176-224 171-218 205-261 199-254 244-311 238-303 268-340 261-332 308-392 301-383 344-438 337-429 -- -- 172-219 168-214 200-255 195-249 239-304 233-296 261-333 256-325 301-383 295-376

11-14 9-11 11-14 9-11 10-13 8-11 10-13 8-11 10-13 8-10 10-13 8-10 -- -- 10-13 8-11 10-13 8-10 10-13 8-10 10-13 8-10 10-13 8-10 10-12 8-10 -- -- 10-13 8-10 10-13 8-10 10-13 8-10 10-12 8-10 10-12 8-10

23-29 23-29 23-28 23-29 22-28 22-28 22-28 22-28 21-27 21-27 21-26 21-26
-- -- 23-28 23-28 23-28 23-28 22-28 22-28 22-27 22-27 21-27 21-27 21-26 21-26 -- -- 22-28 22-28 22-28 22-28 22-27 22-27 22-27 22-27 21-27 21-27

105-121 108-124 121-139 124-142 144-166 148-170 158-182 163-188 185-212 191-219
-- -- 87-101 89-103 105-121 108-124 120-138 123-142 143-164 147-169 157-181 162-186 183-211 189-217 -- -- 90-104 92-106 108-124 111-127 123-141 126-145 144-166 148-171 158-182 163-187 184-212 190-219

279-354 281-357 293-373 296-376 313-398 316-403 324-413 328-418 343-437 347-442
-- -- 260-331 262-333 278-354 280-356 292-372 294-375 312-397 315-401 323-411 326-415 342-435 346-440 -- -- 275-350 276-352 296-376 298-379 313-398 315-401 335-427 338-431 347-442 350-446 365-465 369-470

6-8 5-6 7-9 6-7 8-11 7-9 9-12 7-9 10-13 8-11 -- -- 5-6 4-5 6-8 5-6 7-9 6-7 8-11 7-9 9-11 7-9 10-13 8-11 -- -- 5-6 4-5 6-8 5-6 7-9 6-7 8-10 7-8 9-11 7-9 10-13 8-10

20-29 20-30 23-33 24-34 28-38 29-39 31-41 31-42 35-45 36-46
-- -- 16-24 16-25 20-29 20-29 23-33 24-33 28-38 28-38 30-40 31-41 34-45 35-45 -- -- 16-25 16-25 20-29 20-30 23-32 23-33 27-37 28-38 30-40 30-41 33-44 34-45

58

WSHP-SVX014J-EN

Start-Up

Table 37. Operating pressures in cooling/heating for EX* units (continued)

Model
EXV/H070 EXV/H070

Entering Water Temp
Entering Water
Temp (°F)
95
95

Water Flow (GPM)
14.00 17.50

Operating Data Cooling

Heating

Suction Discharge Water Air Temp Suction Discharge Water Air Temp

Pressure Pressure Temp Rise Drop (°F Pressure Pressure Temp Rise (°F

(psig)

(pgig)

(°F)

DB)

(psig)

(psig) Drop (°F) DB)

145-167 337-429

10-12

21-26

--

--

--

--

145-167 331-421

8-10

21-26

--

--

--

--

Water Pressure Drop

Use the following tables to define feet of head/pressure drop. Please note the feet of pressure (ft/head) provided is at AHRI/ISO standard.
To calculate feet of head, when using gauges that read in PSIG, multiply PSI by 2.31.

Table 38. Cooling water pressure drop (WPD) in feet of head for DX* units

Unit Size

EWT °F

GPM

Ft. Pressure

DXV/H024

86

6.0

3.0

DXV/H036

86

9.0

6.0

DXV/H048

86

12.0

6.4

DXV/H060

86

15.0

11.2

DXV/H070

86

17.5

9.4

Table 39. Cooling water pressure drop (WPD) in feet of head for EX* units

Unit Size (60 Hz)

EWT °F

GPM

Ft. Pressure

EXV/H009

86

2.3

3.4

EXV/H012

86

3.0

5.9

EXV/H015

86

3.8

8.2

EXV/H018

86

4.5

1.9

EXV/H024

86

6.0

3.0

EXV/H030

86

7.5

4.1

EXV/H036

86

9.0

5.8

EXV/H042

86

10.5

4.9

EXV/H048

86

12.0

5.9

EXV/H060

86

15.0

10.6

EXV/H070

86

17.5

9.3

Table 40. Heating water pressure drop (WPD) in feet of head for DX* units

Unit Size

EWT °F

GPM

Ft. Pressure

DXV/H024

68

6.0

3.3

DXV/H036

68

9.0

6.3

DXV/H048

68

12.0

6.6

DXV/H060

68

15.0

12.0

DXV/H070

68

17.5

10.0

Table 41. Heating water pressure drop (WPD) in feet of head for EX* units

Unit Size (60 Hz)

EWT °F

GPM

Ft. Pressure

EXV/H009

68

2.3

3.7

EXV/H012

68

3.0

6.4

EXV/H015

68

3.8

8.8

EXV/H018

68

4.5

2.0

EXV/H024

68

6.0

3.2

EXV/H030

68

7.5

4.5

EXV/H036

68

EXV/H042

68

9.0

6.1

10.5

5.1

EXV/H048

68

12.0

6.2

EXV/H060

68

15.0

11.4

EXV/H070

68

17.5

9.9

WSHP-SVX014J-EN

59

Start-Up

Water Volume
The information below is provided for use in calculating glycol requirements for the unit.

Table 42. Water volume for DX* units

Unit Size

Water Side Water Side Volume (in3) Volume (ft3)

Water Side Volume (gallons)

DXV/H024

118.6

0.069

0.513

DXV/H036

118.6

0.069

0.513

DXV/H048

196.5

0.114

0.851

DXV/H060

222.6

0.129

0.964

DXV/H070

284.0

0.164

1.229

Table 43. Water volume for EX* units

Unit Size (60 Hz)

Water Side Volume (in3)

Water Side Volume (ft3)

EXV/H009 EXV/H012 EXV/H015 EXV/H018 EXV/H024 EXV/H030

34.6 34.6 41.0 118.6 118.6 118.6

0.02 0.02 0.024 0.069 0.069 0.069

Water Side Volume (gallons)
0.15
0.15 0.177
0.513
0.513 0.513

Table 43. Water volume for EX* units (continued)

Unit Size (60 Hz)
EXV/H036 EXV/H042 EXV/H048 EXV/H060 EXV/H070

Water Side Volume (in3)
118.6 196.5 196.5 222.6 284.0

Water Side Volume (ft3)
0.069 0.114 0.114 0.129 0.164

Water Side Volume (gallons)
0.513
0.851
0.851
0.964
1.229

60

WSHP-SVX014J-EN

Maintenance
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.

Preventative Maintenance
Maintenance on the unit is simplified with the following preventive suggestions:
Filter maintenance must be performed to assure proper operation of the equipment. Filters should be inspected at least every three months, and replaced when it is evident they are dirty. Filter sizing is shown below.
Table 44. Filter sizing DX* models

Size
024 036 048 060 070
024 036 048 060 070

Filter Size (Nominal) inches DXHG 18 x 23 20 x 30 20 x 20 (Qty = 2) 20 x 20 and 30 x 20 20 x 20 and 30 x 20 DXVG 18 x 23 20 x 30 27 x 30 30 x 33 30 x 33

Table 45. Filter sizing EX* models

Size
009 012 015 018 024 030 036 042 048 060 070
009 012 015 018 024 030 036 042 048 060 070

Filter Size (Nominal) inches EXHG 16 x 19 16 x 19 17 x 20 18 x 23 18 x 23 20 x 30 20 x 30 20 x 20 (Qty = 2) 20 x 20 (Qty = 2) 20 x 20 and 30 x 20 20 x 20 and 30 x 20 EXVG 16x19 16x19 17x20 18x23 18x23 20x30 20x30 27x30 27x30 33x30 30x33

Check the contactors and relays within the control panel at least once a year. It is good practice to check the tightness of the various wiring connections within the control panel.
A strainer (60 mesh or greater) must be used on an open loop system to keep debris from entering the unit heat exchanger and to ensure a clean system.
For units on well water, it is important to check the cleanliness of the water-to-refrigerant heat exchanger. Should it become contaminated with dirt and scaling as a result of bad water, the heat exchanger will have to be back flushed and cleaned with a chemical that will remove the scale. This service should be performed by an experienced service person.

WSHP-SVX014J-EN

61

Maintenance

WARNING
Hazardous Chemicals!
Failure to follow this safety precaution could result in death or serious injury. Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin or eyes occurs.
Handle chemical carefully and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer's Materials Safety Data Sheet and follow all recommended safe handling practices.

It should be noted that the water quality should be checked periodically (See below).
Table 46. Water quality

Scaling
Calcium and magnesium (total hardness)

Amount Less than 350 ppm

Corrosion pH Hydrogen Sulfide

7-9.5 Less than 1 ppm

Table 46. Water quality (continued)

Scaling Sulfates Chlorides Carbon Dioxide Total dissolved solids (TDS)

Amount Less than 25 ppm Less than 125 ppm Less than 75 ppm Less than 1000 ppm

Biological Growth

Iron Bacteria

Low

Erosion

Suspended Solids

Low

Condensate Trap
For units incorporating a negative trap design, ensure that the condensate system is primed with water at all times. Allowing a negative, pressure condensate system to run dry could cause a break in the condensate seal allowing the fan to draw water from the condensate line to spray moisture into the mechanical system. By maintaining a primed condensate trap, a seal will be created and will help prevent these complications.

62

WSHP-SVX014J-EN

Troubleshooting

WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.

Table 47. Diagnostic LEDs

Color: Green LED1 OFF ON

LED2 OFF OFF

Color: Red

LED3 OFF OFF

ON

OFF

FLASH

ON

OFF

ON

FLASH

ON

OFF

ON

FLASH

ON

ON

FLASH

FLASH

ON

ON

ON

ON

ON

FLASH

ON

FLASH

OFF

ON

ON

OFF

Deluxe Controls
Troubleshooting units which contain the deluxe control option may be made easy by using the three LEDs (light emitting diodes). These LEDs are provided for indicating the operating mode of the controller. The LEDs are intended to aid in troubleshooting. The LEDs are labeled on the circuit board with numbers as referenced in the table below.
Controller Mode
Control OFF Normal/Compressor OFF
Anti-short cycle Normal/Compressor ON
Brownout Condition Soft Lockout (low pressure) Soft Lockout (high pressure) Manual Lockout (low pressure) Manual Lockout (high pressure) Manual Lockout (condensate overflow)
Compressor Disable

Table 48. Troubleshooting table

Problem

Heating

Cooling

Cause

Correction

X

X

No response to any thermostat

X

X

setting

X

X

X

X

Unit short cycles

X

X

X

X

WSHP-SVX014J-EN

Main power off Defective control transformer Broken or loose connection
Defective thermostat Transformer
Thermostat or sensor improperly located

Check fuses Replace Repair Replace
Reset Transformer Relocate
63

Troubleshooting

Table 48. Troubleshooting table (continued)

Problem

Heat- Cool-

ing

ing

Cause

X

X

Blower runs, but compressor does

X

not

X

X

X

X

X

X

X

X

Defective compressor overload

X

Defective compressor contactor

X

Supply Voltage too low

X

Defective compressor capacitor

X

Defective windings

X

Limit switches open

X

Dirty filter

X

Blower RPM too low

X

Loss of conditioned air due to leaks in ductwork

X

Introduction of excessively hot return-air

Introduction of excessively cold return-air

X

X

Low on refrigerant charge

Insufficient capacity
High pressure switch open High head pressure

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Restricted thermal expansion valve Defective reversing valve
Thermostat improperly located Unit undersized
Inadequate water flow Scaling in heat exchanger
Water too hot Water too cold Filter drier blocked Defective reversing valve Inadequate GPM Water too hot Inadequate air flow
Dirty filter Overcharged with refrigerant
Defective pressure switch Trash in heat exchanger
Low water flow Overcharge of refrigerant Non-condensable in system
Water too hot Dirty filter
Inadequate air flow

Correction
Replace (if external) Replace Correct Replace Replace
Check cause/Replace or repair Replace/clean Correct Repair leaks Correct Correct
Locate leak, repair and recharge by weight (not by superheat) Replace
See WSHP-IOM-# for touch test chart Relocate
Recalculate heat gains/losses Increase GPM Clean or replace
Decrease temperature Increase temperature
Replace Check or replace Increase water flow to unit Decrease temperature Check, clean blower and coil
Clean/replace Decrease charge Check or replace
Backflush Increase GPM Decrease charge Evacuate and recharge by weight Decrease temperature Clean / replace Check, clean blower and coil

64

WSHP-SVX014J-EN

Table 48. Troubleshooting table (continued)

Problem

Heat- Cool-

ing

ing

X

X

Low suction pressure

X

X

X

X

X

X

X

X

Low pressure switch open

X

X

X

X

X

X

X

Cause
Undercharged Restricted thermal expansion valve
Inadequate air flow Dirty filter
Inadequate GPM Inadequate GPM
Water too cold Inadequate air flow
Dirty filter Undercharged with refrigerant
Defective pressure switch Heat transfer fluid too cold

Troubleshooting
Correction Locate leak, repair and recharge
Repair / replace Check, clean blower and coil
Clean/replace Increase GPM Increase GPM Increase temperature Increase CFM Clean/replace Increase charge
Replace Raise water temperature

WSHP-SVX014J-EN

65

Wiring Diagrams

This section contains wiring diagrams and isolation valve wiring connections.
Table 49. Isolation valve wiring connections

Control Type Deluxe 24V

3-Wire Isolation Valve Connections

Common

Close

Open

93B

92B

91B

Note: For field installed valves, wires 91B, 92B and 93B are coiled behind control box. For field-provided two wire valves connect to wires 91B and 93B.
Note: Wiring diagrams can be accessed via e-Library by entering the diagram number in the literature order number search field or by calling technical support.

Table 50. Wiring diagram matrix for GEV/H, EXV/H, and DXV/H models

Number 23115845 23115846 23115847 23115848 23115849 23115850 23115851 23115852 23115861 23115862 23116088 23116089 23116151 23116152 23116153 23116154 23116156 23116157

Unit Description DELUXE CONTROLS 2 STAGE HEAT PUMP w/ECM MOTOR, SINGLE PHASE DELUXE CONTROLS HEAT PUMP w/HOT GAS REHEAT AND ECM MOTOR, SINGLE PHASE DELUXE CONTROLS HEAT PUMP w/WATER SIDE ECONOMIZER AND ECM MOTOR, SINGLE PHASE
DELUXE CONTROLS HEAT PUMP w/ECM MOTOR, SINGLE PHASE DELUXE CONTROLS 2 STAGE HEAT PUMP w/ECM MOTOR, THREE PHASE DELUXE CONTROLS HEAT PUMP w/HOT GAS REHEAT AND ECM MOTOR, THREE PHASE DELUXE CONTROLS HEAT PUMP w/WATER SIDE ECONOMIZER AND ECM MOTOR, THREE PHASE
DELUXE CONTROLS HEAT PUMP w/ECM MOTOR, THREE PHASE SYMBIOTM 400-B/UC400-B CONTROLS w/ECM MOTOR, SINGLE PHASE
SYMBIO 400-B/UC400-B CONTROLS w/ECM MOTOR, THREE PHASE DELUXE CONTROLS 2 STAGE HEAT PUMP w/HOT GAS REHEAT, SINGLE PHASE DELUXE CONTROLS 2 STAGE HEAT PUMP w/HOT GAS REHEAT, THREE PHASE DELUXE CONTROLS HEAT PUMP w/BOILERLESS ELECTRIC HEAT, SINGLE PHASE DELUXE CONTROLS HEAT PUMP w/BOILERLESS ELECTRIC HEAT, THREE PHASE 400-B CONTROLS HEAT PUMP w/BOILERLESS ELECTRIC HEAT CONTROL, SINGLE PHASE 400-B CONTROLS HEAT PUMP w/BOILERLESS ELECTRIC HEAT CONTROL, THREE PHASE 400-B CONTROLS HEAT PUMP AND HOT GAS REHEAT w/BOILERLESS ELEC HEAT CONTROL, SINGLE PHASE 400-B CONTROLS HEAT PUMP AND HOT GAS REHEAT w/BOILERLESS ELEC HEAT CONTROL, THREE PHASE

Model DX only EX/GE EX/GE EX/GE DX only EX/GE EX/GE EX/GE EX/DX/GE EX/DX/GE DXV/H DXV/H EX/GE EX/GE EX/DX/GE EX/DX/GE EX/DX/GE EX/DX/GE

66

WSHP-SVX014J-EN

Warranty Information
Standard Warranty
The standard water-source heat pump warranty is Trane's parts-only warranty, running 12 months from startup, not to exceed 18-months from shipment.
There is a standard 5-year compressor warranty.

Extended Warranty
The optional extended warranty is a second through fifth year warranty. The time starts at the end of the standard 1 year coverage through the fifth year.
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be ordered prior to start-up.

WSHP-SVX014J-EN

67

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane. com or tranetechnologies.com.

Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

WSHP-SVX014J-EN 13 May 2023 Supersedes WSHP-SVX014H-EN (June 2022)

©2023 Trane



References

PDFlib PDI 9.0.6 (C /Win64) PTC Arbortext Publishing Engine

Search Any Device: