Allied Air Enterprise KHA092S4MN Specification Sheet

Thos. Somerville Co. | AH570 KHA120S4MN PKGHP/10 TON/460-3/HP EC

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 44 Pages, 2.18MB

Document DEVICE REPORT353-14633
PRODUCT SPECIFICATIONS

PACKAGED HEAT PUMP
KH
K-Series Rooftop Units 60 HZ
Bulletin No. KHA-092-150 (3/2014)

ASHRAE 90.1 COMPLIANT
7.5 to 12.5 Tons Net Cooling Capacity - 87,000 to 138,000 Btuh Net Heating Capacity - 89,000 to 138,000 Btuh
Optional Electric Heat - 7.5 to 60 kW
MODEL NUMBER IDENTIFICATION

Brand/Family K = K-Series
Unit Type H = Packaged Heat Pump
Major Design Sequence A = 1st Generation

K H A 120 S 4 B N 1 Y

Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz

Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision

Nominal Cooling Capacity - Tons 092 = 7.5 Tons 102 = 8.5 Tons 120 = 10 Tons
150 = 12.5 Tons
Cooling Efficiency S = Standard Efficiency

Factory Installed Electric Heat N = No Heat
Blower Type B = Belt Drive, Constant Air Volume (CAV)\ M = Single Zone VAV Supply Fan Supply Air Blower Option, Belt Drive
Refrigerant Type 4 = R-410A

FEATURES AND BENEFITS

E D

K G H
L
B

F

J

C

I

Unit shown with optional
Economizer and Outdoor Air Hoods

K-SeriesTM rooftop units from Allied are the new standard for reliable, efficient rooftop units built for long-lasting performance that can significantly improve indoor environments. K-SeriesTM rooftop units feature:
· R-410A Refrigerant - Environmentally friendly. · Scroll Compressors - Single speed scroll compressors are furnished on all models. · High Pressure Switches - Protect compressor. · Isolated Compressor Compartment - Allows performance check during normal compressor operation without
disrupting airflow. · Independent Outdoor Fan Motor Mounts - Allows for easy and efficient service access without removing the top
panel. · Constant Air Volume (CAV) or Single Zone VAV Supply Fan Blower Option - Allows constant or multi-staged
air delivery. · Downflow or Horizontal Airflow - Easy field conversion. · Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost any angle. · Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved
serviceability. · Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range. · MERV 8 or MERV 13 Filters - Available as field installed option, provide an enhanced level of indoor air quality, and
can help the building qualify for additional LEED credits. · Common Components - Many maintenance items are standard throughout the entire product line, reducing the
need to carry different parts to the job or maintain in inventory.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 2

FEATURES AND BENEFITS

CONTENTS Accessory Dimensions .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 35 Blower Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 22 Dimensions .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33 Electrical/Electric Heat Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 26 Electric Heat Capacities .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 30 Features And Benefits  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .2 Model Number Identification  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .1 Options / Accessories  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9 Outdoor Sound Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31 Ratings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 14 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Unit Clearances  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 30 Weight Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 32

APPROVALS
Units are ETL listed.
Units are CSA listed.
Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.
All models are certified in accordance with the ULE certification program, which is based on AHRI Standard 340/3602007.
All models are ASHRAE 90.1-2010 energy efficiency compliant and meet or exceed requirements of Section 6.8.
Models equipped with the Single Zone VAV Supply Fan option meet California Code of Regulations, Title 24 and ASHRAE 90.1-2010 Section 6.4.3.10 requirements for staged airflow.
ISO 9001 Registered Manufacturing Quality System.

WARRANTY
Limited five years on compressors.
Limited five years Optional High Performance Economizers.
Limited one year all other covered components.
COOLING/HEATING SYSTEM
Designed to maximize sensible and latent cooling performance at design conditions.
System can operate in the cooling mode from 30°F to 125°F without any additional controls.
R-410A Refrigerant Non-chlorine based, ozone friendly, R-410A.
B Scroll Compressors
Scroll compressors on all models for high performance, reliability and quiet operation.
Resiliently mounted on rubber grommets for quiet operation.
Compressor Crankcase Heaters Protects against refrigerant migration that can occur during low ambient operation.
Check/Thermal Expansion Valves Assures optimal performance throughout the application range.
Removable element head.

4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa.
Filter/Driers High capacity filter/drier protects the system from dirt and moisture.
High Pressure Switches Protects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation.
Freezestats Protects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant charge.
C Coil Construction
Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer. Factory leak tested.
Indoor Coil Cross row circuiting with rifled copper tubing optimizes both sensible and latent cooling capacity.
Condenser Coil Two independent formed coils allow separation for cleaning.
Condensate Drain Pan Plastic pan, sloped to meet drainage requirements of ASHRAE 62.1.
Side or bottom drain connections.
Reversible to allow connection at back of unit.
Outdoor Coil Fan Motors Thermal overload protected, totally enclosed, permanently lubricated ball bearings, shaft up, wire basket mount.
D Outdoor Coil Fans
PVC coated fan guard furnished.

Reversing Valves

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 3

FEATURES AND BENEFITS

COOLING/HEATING SYSTEM (continued)
Required Selections

Exterior Panels Constructed of heavy-gauge, galvanized steel with a two-layer enamel paint finish.

Cooling Capacity Specify nominal cooling capacity of the unit
Options/Accessories

Insulation All panels adjacent to conditioned air are fully insulated with nonhygroscopic fiberglass insulation.

Field Installed
Condensate Drain Trap Available in copper or PVC.
Drain Pan Overflow Switch Monitors condensate level in drain pan, shuts down unit if drain becomes clogged.
Low Ambient Kit Cycles the outdoor fan while allowing compressor operation in the cooling cycle. This intermittent fan operation allows the system to operate without icing the evaporator coil and losing capacity. Designed for use in ambient temperatures no lower than 0°F.
CABINET
E Construction
Heavy-gauge steel panels and full perimeter heavy-gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have forklift slots.
Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building.
Airflow Choice Units are shipped in downflow (vertical) configuration, can be field converted to horizontal airflow with optional Horizontal Discharge Kit.
Duct Flanges Provided for horizontal duct attachment.

Unit base is fully insulated in conditioned area. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation.
Access Panels Access panels are provided for the filter section, heating/blower section, and the compressor/ controls section.
Options/Accessories
Factory Installed
Corrosion Protection A completely flexible immersed coating with an electrodeposited dry film process. (AST ElectroFin E-Coat) Meets Mil Spec MIL-P-53084, ASTM B117 Standard Method Salt Spray Testing.
Indoor Corrosion Protection: - Coated coil - Painted blower housing - Painted base
Outdoor Corrosion Protection: - Coated coil - Painted base
Hinged Access Panels Large access panels are hinged and have quarter-turn latches for quick and easy access to maintenance areas (filter, compressor / controls, heating / blower).
Field Installed
Coil Guards Painted, galvanized steel wire guards to protect outdoor coil.
Not used with Hail Guards.

Power Entry Electrical lines can be brought through the unit base or through horizontal access knock-outs

Hail Guards Constructed of heavy gauge steel, painted to match cabinet, helps protect outdoor coils from hail damage.

Not used with Coil Guards.
K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 4

Horizontal Discharge Kit Consists of duct covers to block off downflow supply and return air openings for horizontal applications.
Also includes return air duct flanges for end return air when economizer is used in horizontal applications.
NOTE - When configuring unit for horizontal application with economizer, a separate Horizontal Barometric Relief Damper with Hood must be ordered separately for installation in the return air duct.Return Air Adaptor Plate
For same size LC/LG/LH and TC/ TG/TH unit replacement.
Installs on return air opening in unit to match return air opening on existing roof curbs. Also see Accessory Air Resistance table.
F BLOWER
A wide selection of supply air blower options are available to meet a variety of airflow requirements.
Motor Overload protected, equipped with ball bearings. Belt drive motors are offered on all models and are available in several different sizes to maximize air performance.
Supply Air Blower Forward curved blades, double inlet, blower wheel is statically and dynamically balanced. Equipped with ball bearings and adjustable pulley (allows speed change).
Blower assembly slides out of unit for servicing.
Required Selections
Select Constant Air Volume (CAV) or Single Zone VAV Supply Fan Supply Air Blower Option Order blower motor horsepower and drive kit number required when base unit is ordered, see Drive Kit Specifications Table.
CAV Operation On units ordered with the Constant Air volume (CAV) option, the supply air blower will provide a constant volume of air.

FEATURES AND BENEFITS

BLOWER (continued)
Single Zone VAV Supply Fan Operation Units ordered with the Single Zone VAV Supply Fan option utilize a Variable Frequency Drive (VFD) to stage the supply air blower airflow. The VFD alters the frequency and voltage of the power supply to the blower to control blower speed.
The supply air blower has two speeds:
1. Low speed for part-load cooling operation. Note - Low speed is 66% of high speed.
2. High speed for full load cooling and all heat modes.
Full speed blower operation is set by adjusting the motor pulley to deliver the desired air volume.
The ventilation speed is selectable between high and low speed.
NOTE - Part load airflow in cooling mode on Single Zone VAV Supply Fan units should not be set below 220 cfm/nominal full load ton to reduce the risk of evaporator coil freeze-up.
The VFD has an operational range of -40 to 125° F outdoor air ambient temperature.
Lower operating costs are obtained when the blower is operated on lower speeds.
Single Zone VAV Supply Fan Sequence of Operation Ventilation speed is determined by the VENT SPEED switch setting on VFD control board (LO or HI).
Blower operates in low speed for mechanical cooling (Y1).
Blower operates in high speed for any other mode (free cooling, mechanical cooling Y1+Y2, and heating).
Economizer damper minimum position is fully closed in unoccupied mode.
In occupied mode, the economizer damper minimum position is determined by the setting of the two potentiometers on VFD control board.

· LO SPD MIN POS potentiometer sets the minimum position when blower is operating at low speed.
· HI SPD MIN POS potentiometer sets the minimum position when blower is operating at high speed.
Options/Accessories
Field Installed
VFD Manual Bypass Kit VFD Manual Bypass Control is available as a kit for units equipped with the Single Zone VAV Supply Fan option.
The VFD Manual Bypass Control is a manual bypass and is set by reconfiguring the wiring on the unit.
CONTROLS
G Unit Control
All control voltage is provided via a 24V (secondary) transformer with built-in circuit breaker protection.
Heat/Cool Staging - Capable of up to 2 heat / 2 cool staging with a third party DDC control system or thermostat.
Low Voltage Terminal Block Provides screw terminal connections for thermostat or controller wiring.
Night Setback Mode - Saves energy by closing outdoor air dampers and operating supply fan on thermostat demand only.
Defrost Control Provides a defrost cycle, if needed, every 30 or 60 or 90 minutes (adjustable) of compressor on" time at outdoor coil temperature below 35°F. Temperature switch mounted on outdoor coil liquid line terminates defrost cycle.

Options/Accessories
Field Installed
Smoke Detector Photoelectric type, installed in supply air section, return air section or both sections. Available with power board and single sensor (supply or return) or power board and two sensors (supply and return).

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 5

FEATURES AND BENEFITS

ELECTRICAL
Marked & Color-Coded Wiring All electrical wiring is color-coded and marked to identify which components it is connecting.
Electrical Plugs Positive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation.
Phase Monitor (Factory Installed on Units Equipped with the Single Zone VAV Supply Fan) Phase monitor located in the control compartment detects the phasing of incoming power. If the incoming power is out of phase or if any of the three phases are lost, an indicator LED on the phase monitor will turn red and the unit will not start. In normal operation with correct incoming power phasing, the LED will be green.
Required Selections
Voltage Choice Specify when ordering base unit.
Options/Accessories
Factory or Field Installed
H Disconnect Switch
Accessible from outside of unit, spring loaded weatherproof cover furnished. Main power to the unit is field connected to the disconnect which allows all power to be shut off for service. See Electrical/ Electric Heat tables for ordering information, page 29.

Field Installed
I Electric Heat
Helix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block is furnished as standard. See Options / Accessories tables for ordering information.
GFI Weatherproof Cover Single-gang cover.
Heavy-duty UV-resistant polycarbonate case construction.
Hinged base cover with gasket.
INDOOR AIR QUALITY
J Air Filters
Disposable 2-inch filters furnished as standard.
Options/Accessories
Field Installed
High Efficiency Air Filter Disposable MERV 8 or MERV 13 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2-inch pleated filters.
Replacement Filter Media Kit With Frame Replaces existing pleated filter media. Includes washable metal mesh screen and metal frame with clip for holding replaceable nonpleated filter.

GFI Service Outlets (2) 115V ground fault circuit interrupter (GFCI) type, non-powered, fieldwired.

UVC Germicidal Lamps
Germicidal lamps emit ultra-violet (UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds. This process either destroys the organism or controls its ability to reproduce. UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan). Lamps are field installed in the blower/evaporator coil section. All necessary hardware for installation is included. Lamps operate on 208/230V power supply. Step-down transformer must be field supplied when used with 460V and 575V rooftop units. Magnetic safety interlock terminates power when access panels are removed. Approved by ETL.
Indoor Air Quality (CO2) Sensors Monitors CO2 levels, reports to the Unit Controller which adjusts economizer dampers as needed.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 6

OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS
Factory or Field Installed
K Economizer Features
(Standard and High Performance Common Features) Downflow or Horizontal with Outdoor Air Hood and Barometric Relief Dampers with Exhaust Hood.
L Barometric Relief Dampers allow
relief of excess air, aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle, bird screen furnished.
NOTE - Optional Horizontal Low Profile Barometric Relief Dampers with Exhaust Hood are available for field installation in a reduced space.
Occupied/Unoccupied mode with field furnished setback thermostat.
Demand Control Ventilation (DCV) ready using optional CO2 sensors. Mixed Air Sensor is furnished for field installation in the rooftop unit. Sensor is factory installed when Economizers are factory installed.
Single sensible sensor is furnished with Economizer and enables economizer operation if the outdoor temperature is less than the setpoint of the control.
Standard Economizer Features (Not for Title 24) Parallel, gear-driven action, return air and outdoor air dampers, plug-in connections to unit, nylon bearings, neoprene seals, 24volt, fully-modulating spring return motor.
Standard Economizer Control Module The Standard Economizer Control Module can be adjusted to operate based on outdoor air temperatures.

Economizer Controls:
· Damper Minimum Position Can be set lower than traditional minimum air requirements resulting in cost savings.
· IAQ Sensor - Signals dampers to modulate and maintain 55°F when CO2 is higher than the CO2 setpoint.
· Demand Control Ventilation (DCV) LED - A steady green Demand Control Ventilation LED indicates the IAQ reading is higher than setpoint and requires more fresh air.
· Free Cool LED - A steady green LED indicates outdoor air is suitable for free cooling.
Free Cooling runs when outdoor air temperature is lower than the set temperature on the economizer control.
NOTE: The Free Cooling default setting for outdoor air temperature sensor is 55°F.
High Performance Economizer Features Approved for California Title 24 building standards. ASHRAE 90.1-2010 compliant.
Gear-driven action, high torque 24-volt fully-modulating spring return damper motor, return air and outdoor air dampers, plug-in connections to unit, stainless steel bearings, enhanced neoprene blade edge seals and flexible stainless steel jamb seals to minimize air leakage.
NOTE - High Performance Economizers are not approved for use with enthalpy controls in Title 24 applications.
High Performance Economizer Control Module Module provides inputs and outputs to control economizer based on parameter settings. Module automatically detects sensors by polling to determine which sensors are installed in system.

messages (fault detection and diagnostics) as an aid in troubleshooting.
Non-volatile memory retains parameter settings in case of power failure.
Keypad with four navigation buttons and LCD screen is furnished for setting economizer parameters.
· Menu Up/Exit button returns to the main menu.
· Arrow Up button moves to the previous or next parameter within the selected menu.
· Arrow Down button moves to the next parameter within the selected menu.
· Select (enter) button confirms parameter selection.
Main Menu Structure: · STATUS (economizer and system operation status)
· SETPOINTS (settings for various setpoint parameters)
· SYSTEM SETUP (settings/ information about the system)
· ADVANCED SETUP (freeze protection, CO2 settings, stage 3 delay and additional calibration settings)
· CHECKOUT (damper positions)
· ALARMS (output signal that can be configured for remote alarm monitoring)
NOTE - The Free Cooling setpoint for Title 24 applications must be set based on the Climate Zone where the system is installed. See Section 140.4 "Prescriptive Requirements for Space Conditioning Systems" of the California Energy Commission's 2013 Building Energy Efficiency Standards.
Refer to Installation Instructions for complete setup information and menu parameters available.

Module displays any alarm

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 7

OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS continued
Factory or Field Installed
Single Enthalpy Temperature Control (Not for Title 24) Outdoor air enthalpy sensor enables economizer if the outdoor enthalpy is less than the setpoint of the control. Single enthalpy control is furnished with economizer.
Field Installed
Differential Enthalpy Control (Not for Title 24) Order two Single Enthalpy Control Kits. One is field installed in the return air section, the other in the outdoor air section. Allows the economizer control board to select between outdoor air or return air, whichever has lower enthalpy.

EXHAUST OPTIONS
Field Installed
Horizontal Low Profile Barometric Relief Dampers Replaces barometric relief dampers furnished with Economizer.
For use when unit is configured for horizontal applications in a reduced space requiring an economizer.
Allows relief of excess air.
Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle.
Field installed in return air duct.
Exhaust hood with bird screen furnished.
Requires Horizontal Discharge Kit.
Power Exhaust Fan Installs internal to unit for downflow applications only with economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fan runs when outdoor air dampers are 50% open (adjustable), motor is overload protected. Requires Economizer with Outdoor Air Hood and Barometric Relief Dampers. Fan is 20 in. diameter with 5 blades (K1PWRE10B) WITH 1/3 hp motor.
OUTDOOR AIR OPTIONS
Factory or Field Installed
Outdoor Air Damper - Downflow or Horizontal With Air Hood Linked mechanical dampers, 0 to 25% (fixed) outdoor air adjustable, installs in unit. Includes outdoor air hood. Automatic model features fully modulating spring return damper motor with plug-in connection.
Manual model features a slide damper.
Maximum mixed air temperature in cooling mode: 100°F.

ROOF CURBS
Hybrid Roof Curbs, Downflow Nailer strip furnished, mates to unit, U.S. National Roofing Contractors Approved, shipped knocked down.
Roof curb can be assembled using interlocking tabs to fasten corners together. No tools required.
Curb can also be fastened together with furnished hardware.
Available in 8, 14, 18, and 24 inch heights.
Adaptor Curbs (not shown) Curbs are regionally sourced. Dimensions will vary based upon the source. Contact your local sales representative for a detailed cut sheet with applicable dimensions.
CEILING DIFFUSERS
Ceiling Diffusers (Flush or Step-Down) Aluminum grilles, large center grille, insulated diffuser box with flanges, hanging rings furnished, interior transition (even air flow), internally sealed (prevents recirculation), adapts to T-bar ceiling grids or plaster ceilings.
Transitions (Supply and Return) Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 8

OPTIONS / ACCESSORIES
Item Description
COOLING SYSTEM Condensate Drain Trap
Corrosion Protection Drain Pan Overflow Switch Efficiency

Model Number
PVC - C1TRAP20AD2 Copper - C1TRAP10AD2
K1SNSR71AB1-

Low Ambient Kit (Includes Compressor Crankcase Heater)
Refrigerant Type

208/230V-3ph - K1LOAM02*-B0Y 460V-3ph - K1LOAM02*-B0G 575V-3ph - K1LOAM02*-B0J

BLOWER - SUPPLY AIR

Blower Option

CAV (Constant Air Volume)

Single Zone VAV Supply Fan

Blower Motors

Belt Drive - 2 hp

Belt Drive - 3 hp

Belt Drive - 5 hp

VFD Manual Bypass Kit (for Single Zone VAV Supply Fan equipped units only)

KVFDB12C-1

Drive Kits

Kit #1 590-890 rpm

See Blower Data Tables for selection

Kit #2 800-1105 rpm

Kit #3 795-1195 rpm

Kit #4 730-970 rpm

Kit #5 940-1200 rpm

Kit #6 1015-1300 rpm

Kit #10 900-1135 rpm

Kit #11 1040-1315 rpm

Kit #12 1125-1425 rpm

CABINET

Coil Guards Hail Guards Hinged Access Panels Horizontal Discharge Kit Return Air Adaptor Plate (for LC/LG/LH and TC/TG/TH unit replacement)

E1GARD21B-1 E1GARD11B-1
K1HECK00B-1 C1CONV10B-1

CONTROLS

Commercial Controls BACnet® BACnet® Thermostat with Display BACnet® Thermostat without Display Novar® 2051 Plenum Cable (75 ft.) Smoke Detector - Supply or Return (Power board and one sensor) Smoke Detector - Supply and Return (Power board and two sensors)
NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed

K0CTRL31B-1 K0SNSR01FF1 K0SNSR00FF1 K0CTRL30B-1 K0MISC00FF1 C1SNSR44B-1 C1SNSR43B-1

Catalog Number
76W26 76W27 Factory 74W42
High Standard
10A88 10A89 10A90 R-410A
Factory Factory Factory Factory Factory
90W53
Factory Factory Factory Factory Factory Factory Factory Factory Factory
92W62 92W61 Factory 51W25 54W96
96W15 97W23 97W24 96W12 97W25 53W80 53W81

Unit Model No 092 102 120 150
XXXX XXXX OOOO XXXX OOOO OOOO XXXX XXXX XXXX OOOO
OOOO OOOO OOOO OOOO OOOO
XXXX
OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO
XXXX XXXX OOOO XXXX
OX OX OX OX XXXX XXXX OX OX OX OX XXXX XXXX XXXX

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 9

OPTIONS / ACCESSORIES

Item Description

Model Catalog

Unit Model No

Number Number 092 102 120 150

INDOOR AIR QUALITY

Air Filters

High Efficiency Air Filters

MERV 8 - C1FLTR15B-1 50W61 X X X X

20 x 25 x 2 (Order 4 per unit)

MERV 13 - C1FLTR40B-1 52W41 X X X X

Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media)

C1FLTR30B-1- Y3063 X X X X

Indoor Air Quality (CO2) Sensors Sensor - Wall-mount, off-white plastic cover with LCD display

C0SNSR50AE1L 77N39 X X X X

Sensor - Wall-mount, off-white plastic cover, no display

C0SNSR52AE1L 87N53 X X X X

Sensor - Black plastic case with LCD display, rated for plenum mounting

C0SNSR51AE1L 87N52 X X X X

Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting

C0MISC19AE1 87N54 X X X X

CO2 Sensor Duct Mounting Kit - for downflow applications Aspiration Box - for duct mounting non-plenum rated CO2 sensors (87N53 or 77N39)

C0MISC19AE1- 85L43 X X X X C0MISC16AE1- 90N43 X X X X

UVC Germicidal Lamps 1 UVC Light Kit (208/230v-1ph)

C1UVCL10B-1 54W62 X X X X

ELECTRICAL

Voltage 60 hz

208/230V - 3 phase

460V - 3 phase

575V - 3 phase

Disconnect Switch - See Electrical/Electric Heat tables for selection 80 amp - C1DISC080B-1

150 amp - C1DISC150B-1

GFI Service Outlets 15 amp non-powered, field-wired (208/230V, 460V only) LTAGFIK10/15

20 amp non-powered, field-wired (575V only) C1GFCI20FF1

Weatherproof Cover for GFI

C1GFCI99FF1

2 ELECTRIC HEAT

7.5 kW

208/230V-3ph - C1EHO075B-1Y

460V-3ph - C1EHO075B-1G

575V-3ph - C1EHO075B-1J

15 kW

208/230V-3ph - C1EHO015B-1Y

460V-3ph - C1EHO150B-1G

575V-3ph - C1EHO150B-1J

22.5 kW

208/230V-3ph - C1EHO225B-1Y

460V-3ph - C1EHO225B-1G

575V-3ph - C1EHO225B-1J

30 kW

208/230V-3ph - C1EHO300B-1Y

460V-3ph - C1EHO300B-1G

575V-3ph - C1EHO300B-1J

45 kW

208/230V-3ph - C1EHO450B-1Y

460V-3ph - C1EHO450B-1G

Factory Factory Factory 54W56 54W57 74M70 67E01 10C89
56W38 56W39 56W40 56W41 56W42 56W43 56W44 56W45 56W46 56W47 56W48 56W49 56W50 56W51

OOOO OOOO OOOO OX OX OX OX OX OX OX OX OX OX OX OX XXXX XXXX
OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX OX

575V-3ph - C1EHO450B-1J 56W52 OX OX OX OX

60 kW

208/230V-3ph - C1EHO600B-1Y 55W02

OX OX

460V-3ph - C1EHO600B-1G 55W03

OX OX

575V-3ph - C1EHO600B-1J 55W04

OX OX

1 Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s).

2 NOTE - Factory installed electric heat is only available with high efficiency models.

NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 10

OPTIONS / ACCESSORIES

Item Description

Model Number

ECONOMIZER

Standard Economizer (Not for Title 24)
Standard Economizer with Single Temperature Control Downflow or Horizontal Applications - Includes Barometric Relief Dampers and Air Hoods

K1ECON20B-1

Standard Economizer Controls (Not for Title 24) Single Enthalpy Control

C1SNSR64FF1

Differential Enthalpy Control (order 2)

C1SNSR64FF1

High Performance Economizer (Approved for California Title 24 Building Standards)

High Performance Economizer with Single Temperature Control

K1ECON22B-1

Downflow or Horizontal Applications - Includes Barometric Relief

Dampers and Air Hoods

High Performance Economizer Controls (Not for Title 24) Single Enthalpy Control

C1SNSR60FF1

Differential Enthalpy Control (order 2) Horizontal Low Profile Barometric Relief Dampers With Exhaust Hood Horizontal Low Profile Barometric Relief Dampers With Exhaust Hood

C1SNSR60FF1 LAGEDH03/15

OUTDOOR AIR

Outdoor Air Dampers with Outdoor Air Hood Motorized Manual

C1DAMP20B-1 C1DAMP10B-1

POWER EXHAUST

Standard Static

208/230V-3ph - K1PWRE10B-1Y 460V-3ph - K1PWRE10B-1G 575V-3ph - K1PWRE10B-1J

ROOF CURBS

Hybrid Roof Curbs, Downflow 8 in. height 14 in. height

C1CURB70B-1 C1CURB71B-1

18 in. height

C1CURB72B-1

24 in. height

C1CURB73B-1

Adjustable Pitched Curb

14 in. height

C1CURB55B-1

CEILING DIFFUSERS

Step-Down - Order one Flush - Order one

RTD11-95 RTD11-135 RTD11-185
FD11-95

FD11-135

FD11-185

Transitions (Supply and Return) - Order one

LASRT08/10 LASRT10/12
LASRT15

NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed

Catalog Number
54W55
53W64 53W64
10U58
10Z75 10Z75
53K04
53W49 53W48
53W44 53W45 53W46
11F54 11F55 11F56 11F57
54W50
29G04 29G05 29G06 29G08 29G09 29G10 24L14 49K55 49K56

Unit Model No 092 102 120 150
OX OX OX OX
OX OX OX OX XXXX
OX OX OX OX
OX OX OX OX XXXX
XXXX
OX OX OX OX OX OX OX OX
XXXX XXXX XXXX
XXXX XXXX XXXX XXXX
XXXX
X XX X
X XX X
X XX X

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 11

SPECIFICATIONS

General Data

Nominal Tonnage

7.5 Ton

7.5 Ton

8.5 Ton

8.5 Ton

Model Number KHA092S4B

KHA092S4M

KHA102S4B

KHA102S4M

Efficiency Type

Standard

Standard

Standard

Standard

Blower Type

Constant Air Volume (CAV)

Single Zone VAV Supply Fan

Constant Air Volume (CAV)

Single Zone VAV Supply Fan

Cooling Performance

Gross Cooling Capacity - Btuh 1 Net Cooling Capacity - Btuh

91,600 89,000

91,600 89,000

103,400 100,000

103,400 100,000

AHRI Rated Air Flow - cfm

3000

3000

3400

3400

Total Unit Power - kW

8.1

8.1

9.1

9.1

1 EER (Btuh/Watt)

11

11

11

11

1 IEER (Btuh/Watt)

12.2

12.5

12.2

12.5

Refrigerant Type

R-410A

R-410A

R-410A

R-410A

Refrigerant Charge Circuit 1 12 lbs. 8 oz.

12 lbs. 8 oz.

13 lbs. 8 oz.

13 lbs. 8 oz.

Furnished Circuit 2 12 lbs. 0 oz.

12 lbs. 0 oz.

13 lbs. 0 oz.

13 lbs. 0 oz.

Heating

1 Total High Heat Capacity - Btuh

Performance

Total Unit Power - kW

1 C.O.P.

89,000 7.9 3.3

89,000 7.9 3.3

100,000 8.9 3.3

100,000 8.9 3.3

1 Total Low Heat Capacity - Btuh

53,000

53,000

55,000

55,000

Total Unit Power (kW)

6.9

6.9

7.2

7.2

1 C.O.P.

2.25

2.25

2.25

2.25

Electric Heat Available - See page 27

7.5, 15, 22.5, 30 & 45 kW

Compressor Type (number)

Scroll (2)

Scroll (2)

Scroll (2)

Outdoor

Net face area (total) - sq. ft.

28.8

28.8

28.8

28.8

Coils

Tube diameter - in.

3/8

3/8

3/8

3/8

Number of rows

2

2

2

2

Fins per inch

20

20

20

20

Outdoor Coil Fans

Motor - (No.) horsepower Motor rpm

(2) 1/3 1075

(2) 1/3 1075

(2) 1/2 1075

(2) 1/2 1075

Total Motor watts

665

665

775

775

Diameter - (No.) in.

(2) 24

(2) 24

(2) 24

(2) 24

Number of blades

3

3

3

3

Total Air volume - cfm

8200

8200

8600

8600

Indoor

Net face area (total) - sq. ft.

12.8

12.8

12.8

12.8

Coils

Tube diameter - in.

3/8

3/8

3/8

3/8

Number of rows

3

3

4

4

Fins per inch

14

14

14

14

Drain connection - Number and size

(1) 1 in. NPT coupling

Expansion device type

Balance port TXV, removable head

2 Indoor Blower and Drive Selection

Nominal motor output Maximum usable motor output
(US Only) Motor - Drive kit number

2 hp, 3 hp, 5 hp 2.3 hp, 3.45 hp, 5.75 hp
2 hp 3 Kit 1 590-890 rpm Kit 2 800-1105 rpm Kit 3 795-1195 rpm
3 hp

Kit 4 730-970 rpm Kit 5 940-1200 rpm Kit 6 1015-1300 rpm
5 hp

Kit 10 900-1135 rpm Kit 11 1040-1315 rpm Kit 12 1125-1425 rpm

Blower wheel nominal diameter x width - in.

(1) 15 X 15

(1) 15 X 15

(1) 15 X 15

(1) 15 X 15

Filters

Type of filter

Disposable

Number and size - in.

(4) 20 x 25 x 2

Electrical characteristics

208/230V, 460V or 575V - 60 hertz - 3 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.

1 AHRI Certified to AHRI Standard 340/360:
Cooling Ratings - 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air. High Temperature Heating Ratings - 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air. Low Temperature Heating Ratings - 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air.

2 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

4 Standard motor and drive kit furnished with unit.

NOTE ­ Units equipped with Single Zone VAV Supply Fan option are limited to a motor service factor of 1.0.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 12

SPECIFICATIONS

General Data

Nominal Tonnage

10 Ton

10 Ton

12.5 Ton

12.5 Ton

Model Number KHA120S4B

KHA120S4M

KHA150S4B

KHA150S4M

Efficiency Type Blower Type

Standard Constant Air Volume (CAV)

Standard Single Zone VAV
Supply Fan

Standard Constant Air Volume (CAV)

Standard Single Zone VAV
Supply Fan

Cooling Performance

Gross Cooling Capacity - Btuh 1 Net Cooling Capacity - Btuh

121,500 118,000

121,500 118,000

144,300 138,000

144,300 138,000

AHRI Rated Air Flow - cfm

3600

3600

4500

4500

Total Unit Power - kW

10.7

10.7

13.0

13.0

1 EER (Btuh/Watt)

11

11.0

10.6

10.6

1 IEER (Btuh/Watt)

11.3

12.5

10.7

12.0

Refrigerant Type

R-410A

R-410A

R-410A

R-410A

Refrigerant Charge Circuit 1 15 lbs. 0 oz.

15 lbs. 0 oz.

22 lbs. 0 oz.

22 lbs. 0 oz.

Furnished Circuit 2

Heating

1 Total High Heat Capacity - Btuh

Performance

Total Unit Power - kW

15 lbs. 0 oz. 116,000 10.3

15 lbs. 0 oz. 116,000 10.3

23 lbs. 0 oz. 138,000 12.6

23 lbs. 0 oz. 138,000 12.6

1 C.O.P.

3.3

3.30

3.2

3.20

1 Total Low Heat Capacity - Btuh

72,000

72,000

82,000

82,000

Total Unit Power (kW)

9.4

9.4

11.7

11.7

1 C.O.P.

2.25

2.25

2.05

2.05

Electric Heat Available - See page 27

15, 22.5, 30, 45 & 60 kW

Compressor Type (number)

Scroll (2)

Scroll (2)

Scroll (2)

Scroll (2)

Outdoor

Net face area (total) - sq. ft.

28.8

28.8

40.8

40.8

Coils

Tube diameter - in.

3/8

3/8

3/8

3/8

Number of rows

3

3

3

3

Fins per inch

20

20

20

20

Outdoor Coil Fans

Motor - (No.) horsepower Motor rpm

(2) 1/2 1075

(2) 1/2 1075

(3) 1/3 1075

(3) 1/3 1075

Total Motor watts

806

806

1150

1150

Diameter - (No.) in.

(2) 24

(2) 24

(3) 24

(3) 24

Number of blades

3

3

3

3

Total Air volume - cfm

8800

8800

11,000

11,000

Indoor

Net face area (total) - sq. ft.

12.8

12.8

12.8

12.8

Coils

Tube diameter - in.

3/8

3/8

3/8

3/8

Number of rows

4

4

4

4

Fins per inch

14

14

14

14

Drain connection - Number and size

(1) 1 in. NPT coupling

2 Indoor Blower and Drive Selection

Expansion device type Nominal motor output Maximum usable motor output
(US Only) Motor - Drive kit number

Balance port TXV, removable head 2 hp, 3 hp, 5 hp
2.3 hp, 3.45 hp, 5.75 hp
2 hp 3 Kit 1 590-890 rpm Kit 2 800-1105 rpm Kit 3 795-1195 rpm
3 hp

Kit 4 730-970 rpm Kit 5 940-1200 rpm Kit 6 1015-1300 rpm
5 hp

Kit 10 900-1135 rpm Kit 11 1040-1315 rpm Kit 12 1125-1425 rpm

Blower wheel nominal diameter x width - in.

(1) 15 X 15

(1) 15 X 15

(1) 15 X 15

(1) 15 X 15

Filters

Type of filter

Disposable

Number and size - in.

(4) 20 x 25 x 2

Electrical characteristics

208/230V, 460V or 575V - 60 hertz - 3 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.

1 AHRI Certified to AHRI Standard 340/360:
Cooling Ratings - 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air. High Temperature Heating Ratings - 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air. Low Temperature Heating Ratings - 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air.

2 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

4 Standard motor and drive kit furnished with unit.

NOTE ­ Units equipped with Single Zone VAV Supply Fan option are limited to a motor service factor of 1.0.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 13

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

7.5 TON COOLING STANDARD EFFICIENCY KHA092S4 (1ST STAGE) - CONSTANT AIR VOLUME

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

75°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

2400 48.9 2.15 0.61 0.75 0.93 46.1 2.43 0.61 0.77 0.96 43.2 2.75 0.62 0.8 0.99 40.2 3.12 0.63 0.83 1

63°F 3000 51.7 2.16 0.65 0.85 1 48.7 2.44 0.66 0.88 1 45.7 2.76 0.67 0.91 1 42.5 3.12 0.7 0.95 1

3600 53.8 2.16 0.7 0.94 1 50.8 2.45 0.72 0.97 1 47.6 2.76 0.75 1 1 44.5 3.13 0.78 1

1

2400 52 2.16 0.48 0.59 0.7 49.2 2.44 0.48 0.59 0.72 46.2 2.76 0.48 0.6 0.75 43.1 3.12 0.48 0.61 0.78

67°F 3000 54.9 2.16 0.51 0.63 0.8 51.9 2.45 0.51 0.64 0.83 48.7 2.77 0.51 0.65 0.86 45.3 3.13 0.52 0.67 0.9

3600 57.1 2.17 0.53 0.67 0.89 53.9 2.45 0.54 0.69 0.93 50.5 2.77 0.54 0.72 0.96 46.9 3.13 0.55 0.75 0.99

2400 55.1 2.16 0.37 0.47 0.57 52.3 2.45 0.37 0.47 0.57 49.1 2.77 0.36 0.47 0.58 45.9 3.13 0.35 0.48 0.59

71°F 3000 58.2 2.17 0.38 0.5 0.61 55.1 2.45 0.38 0.5 0.62 51.7 2.77 0.37 0.51 0.63 48.1 3.14 0.37 0.51 0.65

3600 60.4 2.18 0.39 0.52 0.65 57.1 2.46 0.39 0.53 0.66 53.6 2.78 0.39 0.54 0.69 50 3.14 0.39 0.55 0.72

7.5 TON COOLING STANDARD EFFICIENCY KHA092S4 (2ND STAGE) - CONSTANT AIR VOLUME

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2400 87.3 5.43 0.7 0.85 0.99 81.3 6.15 0.71 0.87 1 74.9 6.99 0.72 0.9 1 67.7 7.97 0.74 0.95 1

63°F 3000 92.5 5.44 0.75 0.93 1 86 6.16 0.77 0.96 1 79.2 7 0.8 0.99 1 72.4 7.98 0.83 1

1

3600 96.3 5.45 0.81 1 1 90 6.17 0.84 1

1 83.7 7 0.87 1 1 76.7 7.98 0.91 1

1

2400 93.3 5.44 0.54 0.68 0.81 87.2 6.17 0.54 0.69 0.83 80.3 6.99 0.55 0.7 0.87 72.9 7.97 0.55 0.72 0.9

67°F 3000 98.4 5.45 0.58 0.73 0.9 91.6 6.17 0.58 0.75 0.93 84.4 7.01 0.59 0.77 0.96 76.7 7.99 0.6 0.8 1

3600 102.1 5.46 0.61 0.79 0.97 94.9 6.18 0.62 0.81 1 87.1 7 0.63 0.85 1 79.2 7.98 0.65 0.89 1

2400 99.3 5.45 0.4 0.53 0.65 92.7 6.17 0.4 0.53 0.66 85.8 7.01 0.39 0.54 0.68 78.1 7.97 0.39 0.55 0.7

71°F 3000 104.5 5.46 0.42 0.57 0.71 97.4 6.18 0.42 0.57 0.73 90 7.02 0.41 0.58 0.75 81.9 7.98 0.41 0.6 0.78

3600 108.3 5.48 0.44 0.6 0.77 101.1 6.19 0.44 0.61 0.79 93.2 7.02 0.43 0.63 0.82 84.6 7.98 0.43 0.64 0.86

7.5 TON HEATING STANDARD EFFICIENCY KHA092S4 - CONSTANT AIR VOLUME

Indoor Coil Air Volume
70°F Dry Bulb cfm
2400 3000 3600

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

109.2

7.13

111.1

6.64

112.8

6.34

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

83.2

6.60

56.4

6.13

37.0

5.20

85.2

6.12

58.3

5.64

38.9

4.72

86.8

5.82

60.0

5.34

40.6

4.42

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

18.4

3940

20.3

3455

22.0

3155

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 14

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

8.5 TON COOLING STANDARD EFFICIENCY KHA102S4 (1ST STAGE) - CONSTANT AIR VOLUME

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

75°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

2720 53 2.42 0.63 0.77 0.95 50.3 2.73 0.63 0.79 0.98 47.4 3.08 0.64 0.82 1 44.4 3.49 0.66 0.85 1

63°F 3400 55.9 2.43 0.67 0.87 1

53 2.74 0.68 0.9 1 49.8 3.09 0.7 0.94 1 46.6 3.5 0.73 0.98 1

4080 58.1 2.44 0.73 0.97 1 54.9 2.75 0.75 0.99 1 52.1 3.1 0.78 1 1 49 3.5 0.81 1

1

2720 56.4 2.43 0.5 0.61 0.72 53.7 2.74 0.5 0.61 0.74 50.7 3.1 0.5 0.63 0.77 47.5 3.5 0.51 0.64 0.8

67°F 3400 59.3 2.44 0.53 0.65 0.82 56.2 2.75 0.53 0.66 0.85 53.1 3.1 0.54 0.68 0.89 49.6 3.51 0.55 0.7 0.93

4080 61.4 2.45 0.56 0.7 0.92 58.1 2.76 0.56 0.72 0.96 54.7 3.11 0.57 0.75 0.99 51.1 3.51 0.58 0.78 1

2720 60.1 2.45 0.38 0.48 0.59 57 2.76 0.38 0.49 0.59 54 3.1 0.38 0.49 0.6 50.5 3.51 0.37 0.5 0.62

71°F 3400 63 2.46 0.39 0.51 0.63 59.6 2.76 0.39 0.52 0.64 56.5 3.12 0.39 0.53 0.66 52.9 3.52 0.39 0.54 0.68

4080 65.1 2.46 0.41 0.55 0.68 61.8 2.77 0.41 0.56 0.7 58.1 3.12 0.41 0.56 0.72 54.5 3.52 0.41 0.57 0.75

8.5 TON COOLING STANDARD EFFICIENCY KHA102S4 (2ND STAGE) - CONSTANT AIR VOLUME

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2720 98.8 6.36 0.71 0.87 1 92.4 7.2 0.73 0.89 1 85.6 8.16 0.74 0.92 1 78.4 9.32 0.77 0.97 1

63°F 3400 103.8 6.38 0.77 0.95 1 97.2 7.21 0.8 0.99 1 90.4 8.18 0.82 1 1 83.5 9.31 0.86 1

1

4080 108.4 6.4 0.84 1 1 102.1 7.23 0.86 1

1 95.7 8.2 0.9 1 1 88.4 9.34 0.94 1

1

2720 105.5 6.39 0.56 0.69 0.83 98.9 7.22 0.56 0.71 0.85 91.4 8.18 0.57 0.72 0.89 83.8 9.32 0.58 0.75 0.93

67°F 3400 110.5 6.41 0.6 0.75 0.92 103.4 7.23 0.61 0.77 0.95 95.6 8.2 0.61 0.8 0.99 87.2 9.33 0.63 0.83 1

4080 113.8 6.41 0.63 0.82 0.99 106.6 7.24 0.64 0.84 1 98.5 8.21 0.66 0.88 1 89.8 9.32 0.68 0.92 1

2720 112.4 6.41 0.42 0.55 0.67 105.2 7.24 0.42 0.55 0.69 97.7 8.19 0.41 0.56 0.7 89.7 9.34 0.41 0.57 0.73

71°F 3400 117.5 6.43 0.44 0.59 0.73 110.2 7.26 0.44 0.6 0.75 102 8.22 0.43 0.61 0.78 93.4 9.34 0.43 0.62 0.81

4080 121 6.44 0.45 0.62 0.79 113.4 7.27 0.45 0.64 0.82 105.2 8.23 0.46 0.66 0.85 95.8 9.34 0.46 0.67 0.89

8.5 TON HEATING STANDARD EFFICIENCY KHA102S4 - CONSTANT AIR VOLUME

Indoor Coil Air Volume
70°F Dry Bulb cfm
2720 3400 4080

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

124.0

7.58

126.0

7.09

128.0

6.79

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

93.6

6.91

62.2

6.24

40.0

5.44

95.6

6.43

64.1

5.75

41.9

4.95

97.6

6.12

66.2

5.44

43.9

4.64

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

20.1

4120

22.1

3635

24.1

3325

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 15

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

10 TON COOLING STANDARD EFFICIENCY KHA120S4 (1ST STAGE) - CONSTANT AIR VOLUME

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

3200 64.2 2.87 0.66 0.8 0.94 60.6 3.26 0.67 0.81 0.96 56.8 3.7 0.67 0.83 0.99 52.9 4.18 0.68 0.85 1

63°F 4000 67.9 2.9 0.71 0.87 1 64 3.29 0.72 0.9 1 60.1 3.72 0.73 0.92 1 56 4.21 0.75 0.96 1

4800 70.6 2.92 0.75 0.95 1 66.6 3.32 0.78 0.97 1 62.6 3.75 0.79 0.99 1 58.5 4.24 0.82 1

1

3200 68.4 2.9 0.53 0.64 0.76 64.8 3.3 0.52 0.64 0.77 61 3.73 0.52 0.65 0.79 56.9 4.22 0.52 0.66 0.81

67°F 4000 72.2 2.93 0.55 0.68 0.83 68.3 3.33 0.56 0.7 0.86 64.2 3.76 0.56 0.71 0.88 59.7 4.25 0.56 0.72 0.91

4800 74.7 2.95 0.58 0.73 0.91 70.7 3.35 0.59 0.75 0.94 66.4 3.79 0.59 0.77 0.97 61.8 4.27 0.6 0.8 0.99

3200 73.3 2.93 0.4 0.51 0.62 69.1 3.34 0.4 0.51 0.62 65.1 3.77 0.39 0.51 0.63 60.9 4.26 0.38 0.51 0.64

71°F 4000 76.6 2.97 0.41 0.54 0.66 72.7 3.37 0.41 0.55 0.67 68.3 3.81 0.41 0.55 0.69 63.7 4.29 0.4 0.55 0.7

4800 79.5 3 0.43 0.57 0.71 75.1 3.39 0.42 0.57 0.72 70.6 3.84 0.42 0.59 0.75 65.8 4.32 0.42 0.6 0.77

10 TON COOLING STANDARD EFFICIENCY KHA120S4 (2ND STAGE) - CONSTANT AIR VOLUME

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

105°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

3200 117.9 7.41 0.7 0.85 0.99 110 8.38 0.71 0.87 1 101.4 9.49 0.73 0.9 1 92.3 10.78 0.75 0.94 1

63°F 4000 124.8 7.47 0.76 0.93 1 116.4 8.44 0.78 0.96 1 107.2 9.55 0.8 0.99 1 98 10.83 0.83 1

1

4800 130 7.52 0.82 1 1 121.5 8.49 0.84 1

1 113.1 9.61 0.87 1 1 104.1 10.89 0.91 1

1

3200 126.6 7.48 0.55 0.68 0.82 118.3 8.46 0.55 0.69 0.84 109.1 9.57 0.55 0.71 0.86 99.4 10.85 0.55 0.73 0.9

67°F 4000 133.2 7.55 0.58 0.74 0.9 124 8.52 0.59 0.75 0.93 114.5 9.63 0.6 0.78 0.96 104.1 10.9 0.61 0.81 0.99

4800 137.8 7.6 0.62 0.8 0.97 128.3 8.57 0.63 0.82 0.99 118.1 9.67 0.64 0.85 1 107.2 10.93 0.66 0.89 1

3200 135.1 7.57 0.41 0.54 0.66 126.5 8.55 0.4 0.54 0.67 116.9 9.66 0.4 0.54 0.69 106.7 10.91 0.39 0.55 0.7

71°F 4000 141.8 7.64 0.43 0.57 0.72 132.2 8.61 0.41 0.58 0.73 122.7 9.72 0.42 0.59 0.76 111.9 10.99 0.41 0.6 0.79

4800 146.7 7.69 0.44 0.61 0.78 136.8 8.67 0.44 0.62 0.8 126.5 9.77 0.44 0.63 0.84 115.3 11.02 0.44 0.65 0.86

10 TON HEATING STANDARD EFFICIENCY KHA120S4 - CONSTANT AIR VOLUME

Indoor Coil Air Volume
70°F Dry Bulb cfm
3200 4000 4800

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

141.7

9.39

144.9

8.77

148.1

8.37

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

109.6

8.57

76.1

7.74

52.6

6.77

112.9

7.95

79.4

7.12

55.9

6.15

116.1

7.55

82.6

6.72

59.0

5.74

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

25.4

5130

28.7

4510

31.9

4105

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 16

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

12.5 TON COOLING STANDARD EFFICIENCY KHA150S4 (1ST STAGE) - CONSTANT AIR VOLUME

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

3800 75.5 3.48 0.64 0.79 0.95 71.4 3.88 0.64 0.8 0.97 67 4.32 0.65 0.82 0.99 62 4.79 0.65 0.85 1

63°F 4400 78.5 3.49 0.67 0.85 1 74.2 3.89 0.67 0.86 1 69.6 4.32 0.68 0.89 1 64.5 4.79 0.7 0.92 1

5000 81 3.5 0.7 0.9 1 76.7 3.89 0.72 0.92 1 71.8 4.32 0.72 0.95 1 67 4.8 0.75 0.98 1

3800 81.1 3.5 0.5 0.62 0.75 76.9 3.9 0.5 0.62 0.76 72.2 4.32 0.5 0.62 0.78 67.1 4.8 0.49 0.63 0.8

67°F 4400 84 3.51 0.52 0.64 0.8 79.7 3.9 0.52 0.65 0.82 75 4.33 0.52 0.66 0.84 69.7 4.8 0.52 0.67 0.87

5000 86.4 3.52 0.54 0.68 0.85 82.1 3.9 0.54 0.69 0.88 77.2 4.33 0.54 0.71 0.9 71.5 4.8 0.54 0.72 0.93

3800 86.8 3.52 0.39 0.49 0.59 82.3 3.9 0.38 0.49 0.6 77.6 4.33 0.37 0.49 0.6 72.5 4.8 0.36 0.49 0.61

71°F 4400 89.9 3.52 0.39 0.51 0.62 85.3 3.91 0.39 0.51 0.63 80.5 4.34 0.38 0.51 0.64 75.2 4.81 0.37 0.51 0.65

5000 92.5 3.53 0.4 0.53 0.65 87.9 3.92 0.4 0.53 0.66 82.7 4.34 0.39 0.54 0.67 77.2 4.81 0.38 0.53 0.69

12.5 TON COOLING STANDARD EFFICIENCY KHA150S4 (2ND STAGE) - CONSTANT AIR VOLUME

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

105°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

3800 138.4 8.45 0.7 0.86 1 128.4 9.38 0.71 0.88 1 117.7 10.42 0.72 0.9 1 106.5 11.6 0.74 0.94 1

63°F 4400 144 8.45 0.74 0.91 1 133.6 9.39 0.76 0.94 1 122.8 10.43 0.77 0.97 1 111.6 11.6 0.8 1

1

5000 148.6 8.45 0.78 0.96 1 138.6 9.39 0.8 0.98 1 127.6 10.43 0.82 1 1 116.8 11.61 0.85 1

1

3800 149.2 8.46 0.54 0.68 0.82 138.7 9.39 0.54 0.69 0.84 128.2 10.43 0.54 0.7 0.86 116.2 11.6 0.54 0.72 0.89

67°F 4400 155 8.47 0.57 0.72 0.87 144.3 9.39 0.57 0.73 0.89 132.8 10.42 0.57 0.75 0.93 120.4 11.59 0.58 0.77 0.96

5000 159.6 8.47 0.59 0.76 0.92 148.7 9.39 0.59 0.77 0.95 136.9 10.43 0.6 0.8 0.98 124.6 11.62 0.61 0.82 1

3800 160.3 8.47 0.4 0.53 0.66 149.9 9.39 0.39 0.53 0.67 138.9 10.44 0.38 0.53 0.68 126.5 11.61 0.37 0.54 0.69

71°F 4400 166.4 8.48 0.41 0.56 0.69 155.5 9.4 0.41 0.56 0.71 143.7 10.43 0.4 0.56 0.72 131.4 11.62 0.39 0.57 0.74

5000 171 8.49 0.42 0.58 0.74 159.7 9.4 0.41 0.58 0.75 148.1 10.44 0.41 0.59 0.77 135.5 11.62 0.41 0.6 0.8

12.5 TON HEATING STANDARD EFFICIENCY KHA150S4 - CONSTANT AIR VOLUME

Indoor Coil Air Volume
70°F Dry Bulb cfm
3800 4400 5000

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

167.2

10.04

170.6

9.68

174.0

9.41

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

127.6

9.22

86.4

8.39

58.2

7.34

131.1

8.86

89.8

8.03

61.7

6.97

134.5

8.59

93.2

7.76

65.1

6.71

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

28.6

5465

32.0

5100

35.4

4835

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 17

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

7.5 TON COOLING STANDARD EFFICIENCY KHA092S4 (1ST STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

75°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

1680 44.1 2.13 0.57 0.69 0.81 41.7 2.42 0.57 0.69 0.83 39.2 2.74 0.58 0.7 0.85 36.5 3.11 0.58 0.72 0.87

63°F 2100 47.5 2.14 0.6 0.74 0.89 44.9 2.43 0.61 0.76 0.91 42.2 2.75 0.61 0.77 0.94 39.2 3.11 0.62 0.8 0.97

2520 50.1 2.15 0.64 0.8 0.96 47.2 2.43 0.65 0.82 0.98 44.3 2.75 0.66 0.85 1 41.2 3.12 0.67 0.87 1

1680 47.1 2.14 0.46 0.55 0.65 44.6 2.43 0.46 0.55 0.65 42 2.75 0.46 0.55 0.66 39.2 3.12 0.45 0.56 0.68

67°F 2100 50.6 2.15 0.48 0.58 0.7 47.9 2.44 0.48 0.58 0.72 45.1 2.75 0.48 0.59 0.73 42 3.12 0.48 0.6 0.75

2520 53.3 2.16 0.5 0.61 0.76 50.4 2.44 0.5 0.62 0.78 47.3 2.76 0.5 0.63 0.8 44.1 3.12 0.5 0.65 0.83

1680 50.1 2.15 0.37 0.45 0.53 47.5 2.43 0.36 0.45 0.53 44.7 2.75 0.35 0.44 0.53 41.9 3.12 0.34 0.44 0.54

71°F 2100 53.8 2.16 0.37 0.47 0.56 50.9 2.44 0.37 0.47 0.56 47.9 2.76 0.36 0.47 0.57 44.8 3.13 0.35 0.47 0.58

2520 56.5 2.17 0.38 0.49 0.59 53.5 2.45 0.38 0.49 0.6 50.3 2.77 0.37 0.49 0.61 46.9 3.13 0.36 0.49 0.62

7.5 TON COOLING STANDARD EFFICIENCY KHA092S4 (2ND STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2400 87.3 5.43 0.7 0.85 0.99 81.3 6.15 0.71 0.87 1 74.9 6.99 0.72 0.9 1 67.7 7.97 0.74 0.95 1

63°F 3000 92.5 5.44 0.75 0.93 1 86 6.16 0.77 0.96 1 79.2 7 0.8 0.99 1 72.4 7.98 0.83 1

1

3600 96.3 5.45 0.81 1 1 90 6.17 0.84 1

1 83.7 7 0.87 1 1 76.7 7.98 0.91 1

1

2400 93.3 5.44 0.54 0.68 0.81 87.2 6.17 0.54 0.69 0.83 80.3 6.99 0.55 0.7 0.87 72.9 7.97 0.55 0.72 0.9

67°F 3000 98.4 5.45 0.58 0.73 0.9 91.6 6.17 0.58 0.75 0.93 84.4 7.01 0.59 0.77 0.96 76.7 7.99 0.6 0.8 1

3600 102.1 5.46 0.61 0.79 0.97 94.9 6.18 0.62 0.81 1 87.1 7 0.63 0.85 1 79.2 7.98 0.65 0.89 1

2400 99.3 5.45 0.4 0.53 0.65 92.7 6.17 0.4 0.53 0.66 85.8 7.01 0.39 0.54 0.68 78.1 7.97 0.39 0.55 0.7

71°F 3000 104.5 5.46 0.42 0.57 0.71 97.4 6.18 0.42 0.57 0.73 90 7.02 0.41 0.58 0.75 81.9 7.98 0.41 0.6 0.78

3600 108.3 5.48 0.44 0.6 0.77 101.1 6.19 0.44 0.61 0.79 93.2 7.02 0.43 0.63 0.82 84.6 7.98 0.43 0.64 0.86

7.5 TON HEATING STANDARD EFFICIENCY KHA092S4 - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Indoor Coil Air Volume
70°F Dry Bulb cfm
2400 3000 3600

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

109.2

7.13

111.1

6.64

112.8

6.34

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

83.2

6.60

56.4

6.13

37.0

5.20

85.2

6.12

58.3

5.64

38.9

4.72

86.8

5.82

60.0

5.34

40.6

4.42

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

18.4

3940

20.3

3455

22.0

3155

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 18

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

8.5 TON COOLING STANDARD EFFICIENCY KHA102S4 (1ST STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

75°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

1920 48.3 2.39 0.58 0.69 0.82 46 2.71 0.58 0.7 0.84 43.4 3.06 0.58 0.71 0.86 40.8 3.47 0.59 0.73 0.89

63°F 2400 51.7 2.41 0.6 0.75 0.9 49.1 2.72 0.61 0.77 0.93 46.3 3.07 0.62 0.78 0.96 43.3 3.47 0.63 0.81 0.99

2880 54.2 2.42 0.64 0.81 0.98 51.4 2.73 0.66 0.83 1 48.5 3.08 0.67 0.86 1 45.3 3.48 0.69 0.89 1

1920 51.8 2.41 0.47 0.56 0.65 49.3 2.72 0.47 0.56 0.66 46.5 3.07 0.47 0.56 0.67 43.7 3.48 0.46 0.57 0.69

67°F 2400 55.1 2.42 0.48 0.58 0.71 52.5 2.73 0.48 0.59 0.72 49.5 3.08 0.49 0.6 0.74 46.4 3.49 0.49 0.61 0.77

2880 57.6 2.43 0.5 0.62 0.77 54.8 2.74 0.51 0.63 0.79 51.7 3.09 0.51 0.65 0.82 48.3 3.49 0.51 0.66 0.85

1920 55.1 2.42 0.37 0.45 0.53 52.5 2.73 0.36 0.45 0.54 49.7 3.08 0.36 0.45 0.54 46.7 3.49 0.35 0.45 0.54

71°F 2400 58.6 2.43 0.38 0.47 0.56 55.8 2.74 0.37 0.47 0.57 52.7 3.09 0.37 0.47 0.58 49.5 3.5 0.37 0.48 0.59

2880 61.2 2.44 0.38 0.49 0.6 58.3 2.75 0.38 0.49 0.6 55.1 3.1 0.38 0.5 0.62 51.5 3.5 0.37 0.5 0.64

8.5 TON COOLING STANDARD EFFICIENCY KHA102S4 (2ND STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2720 98.8 6.36 0.71 0.87 1 92.4 7.2 0.73 0.89 1 85.6 8.16 0.74 0.92 1 78.4 9.32 0.77 0.97 1

63°F 3400 103.8 6.38 0.77 0.95 1 97.2 7.21 0.8 0.99 1 90.4 8.18 0.82 1 1 83.5 9.31 0.86 1

1

4080 108.4 6.4 0.84 1 1 102.1 7.23 0.86 1

1 95.7 8.2 0.9 1 1 88.4 9.34 0.94 1

1

2720 105.5 6.39 0.56 0.69 0.83 98.9 7.22 0.56 0.71 0.85 91.4 8.18 0.57 0.72 0.89 83.8 9.32 0.58 0.75 0.93

67°F 3400 110.5 6.41 0.6 0.75 0.92 103.4 7.23 0.61 0.77 0.95 95.6 8.2 0.61 0.8 0.99 87.2 9.33 0.63 0.83 1

4080 113.8 6.41 0.63 0.82 0.99 106.6 7.24 0.64 0.84 1 98.5 8.21 0.66 0.88 1 89.8 9.32 0.68 0.92 1

2720 112.4 6.41 0.42 0.55 0.67 105.2 7.24 0.42 0.55 0.69 97.7 8.19 0.41 0.56 0.7 89.7 9.34 0.41 0.57 0.73

71°F 3400 117.5 6.43 0.44 0.59 0.73 110.2 7.26 0.44 0.6 0.75 102 8.22 0.43 0.61 0.78 93.4 9.34 0.43 0.62 0.81

4080 121 6.44 0.45 0.62 0.79 113.4 7.27 0.45 0.64 0.82 105.2 8.23 0.46 0.66 0.85 95.8 9.34 0.46 0.67 0.89

8.5 TON HEATING STANDARD EFFICIENCY KHA102S4 - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Indoor Coil Air Volume
70°F Dry Bulb cfm
2720 3400 4080

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

124.0

7.58

126.0

7.09

128.0

6.79

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

93.6

6.91

62.2

6.24

40.0

5.44

95.6

6.43

64.1

5.75

41.9

4.95

97.6

6.12

66.2

5.44

43.9

4.64

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

20.1

4120

22.1

3635

24.1

3325

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 19

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

10 TON COOLING STANDARD EFFICIENCY KHA120S4 (1ST STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2240 58.1 2.82 0.61 0.72 0.83 55 3.21 0.61 0.73 0.84 51.8 3.65 0.62 0.74 0.86 48.2 4.13 0.62 0.75 0.88

63°F 2800 62.4 2.85 0.64 0.77 0.9 59.1 3.25 0.65 0.78 0.92 55.5 3.68 0.65 0.8 0.94 51.6 4.16 0.66 0.82 0.97

3360 65.6 2.88 0.68 0.82 0.96 62.1 3.27 0.69 0.84 0.98 58.2 3.7 0.7 0.86 1 54.2 4.18 0.71 0.88 1

2240 62.4 2.85 0.5 0.59 0.69 59.1 3.24 0.49 0.59 0.69 55.7 3.68 0.49 0.59 0.7 52 4.17 0.48 0.59 0.71

67°F 2800 66.9 2.88 0.52 0.62 0.74 63.3 3.28 0.52 0.62 0.75 59.6 3.71 0.51 0.63 0.76 55.6 4.2 0.51 0.64 0.78

3360 70.1 2.91 0.53 0.65 0.79 66.3 3.31 0.53 0.66 0.8 62.4 3.74 0.53 0.67 0.82 58.2 4.23 0.54 0.69 0.84

2240 66.6 2.88 0.39 0.48 0.57 63.3 3.28 0.39 0.48 0.57 59.6 3.71 0.38 0.47 0.57 55.9 4.2 0.37 0.47 0.57

71°F 2800 71.3 2.92 0.4 0.5 0.6 67.6 3.32 0.4 0.5 0.6 63.5 3.75 0.39 0.5 0.61 59.6 4.24 0.38 0.5 0.61

3360 74.6 2.94 0.41 0.52 0.63 70.7 3.34 0.4 0.52 0.64 66.6 3.78 0.4 0.52 0.65 62.2 4.27 0.39 0.53 0.66

10 TON COOLING STANDARD EFFICIENCY KHA120S4 (2ND STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

105°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

3200 117.9 7.41 0.7 0.85 0.99 110 8.38 0.71 0.87 1 101.4 9.49 0.73 0.9 1 92.3 10.78 0.75 0.94 1

63°F 4000 124.8 7.47 0.76 0.93 1 116.4 8.44 0.78 0.96 1 107.2 9.55 0.8 0.99 1 98 10.83 0.83 1

1

4800 130 7.52 0.82 1 1 121.5 8.49 0.84 1

1 113.1 9.61 0.87 1 1 104.1 10.89 0.91 1

1

3200 126.6 7.48 0.55 0.68 0.82 118.3 8.46 0.55 0.69 0.84 109.1 9.57 0.55 0.71 0.86 99.4 10.85 0.55 0.73 0.9

67°F 4000 133.2 7.55 0.58 0.74 0.9 124 8.52 0.59 0.75 0.93 114.5 9.63 0.6 0.78 0.96 104.1 10.9 0.61 0.81 0.99

4800 137.8 7.6 0.62 0.8 0.97 128.3 8.57 0.63 0.82 0.99 118.1 9.67 0.64 0.85 1 107.2 10.93 0.66 0.89 1

3200 135.1 7.57 0.41 0.54 0.66 126.5 8.55 0.4 0.54 0.67 116.9 9.66 0.4 0.54 0.69 106.7 10.91 0.39 0.55 0.7

71°F 4000 141.8 7.64 0.43 0.57 0.72 132.2 8.61 0.41 0.58 0.73 122.7 9.72 0.42 0.59 0.76 111.9 10.99 0.41 0.6 0.79

4800 146.7 7.69 0.44 0.61 0.78 136.8 8.67 0.44 0.62 0.8 126.5 9.77 0.44 0.63 0.84 115.3 11.02 0.44 0.65 0.86

10 TON HEATING STANDARD EFFICIENCY KHA120S4 - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Indoor Coil Air Volume
70°F Dry Bulb cfm
3200 4000 4800

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

141.7

9.39

144.9

8.77

148.1

8.37

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

109.6

8.57

76.1

7.74

52.6

6.77

112.9

7.95

79.4

7.12

55.9

6.15

116.1

7.55

82.6

6.72

59.0

5.74

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

25.4

5130

28.7

4510

31.9

4105

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 20

RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

12.5 TON COOLING STANDARD EFFICIENCY KHA150S4 (1ST STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Entering Wet Bulb
Temperature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2560 67.8 3.46 0.59 0.7 0.82 64.1 3.87 0.59 0.71 0.83 60.1 4.31 0.59 0.71 0.85 55.6 4.79 0.59 0.72 0.87

63°F 3200 73.1 3.48 0.62 0.76 0.89 69 3.88 0.62 0.76 0.91 64.9 4.32 0.63 0.78 0.93 60.1 4.8 0.63 0.8 0.96

3840 77.2 3.49 0.66 0.81 0.96 73 3.89 0.66 0.83 0.98 68.3 4.32 0.67 0.84 1 63.4 4.8 0.68 0.87 1

2560 73.1 3.47 0.48 0.57 0.67 69.2 3.88 0.47 0.57 0.67 65.1 4.32 0.46 0.56 0.67 60.6 4.8 0.45 0.56 0.68

67°F 3200 78.6 3.49 0.5 0.6 0.72 74.6 3.89 0.49 0.6 0.73 70 4.32 0.49 0.6 0.74 65.4 4.8 0.48 0.61 0.75

3840 82.9 3.5 0.51 0.64 0.78 78.6 3.9 0.51 0.64 0.79 73.8 4.33 0.51 0.64 0.8 68.5 4.8 0.51 0.65 0.82

2560 78.6 3.49 0.38 0.46 0.55 74.6 3.89 0.37 0.46 0.54 70.3 4.32 0.36 0.45 0.54 65.7 4.8 0.34 0.44 0.54

71°F 3200 84.3 3.51 0.39 0.48 0.58 80.2 3.9 0.38 0.48 0.58 75.4 4.33 0.37 0.48 0.58 70.6 4.81 0.36 0.47 0.58

3840 88.6 3.52 0.39 0.5 0.61 84.2 3.91 0.39 0.5 0.61 79.3 4.33 0.38 0.5 0.62 74 4.81 0.37 0.5 0.63

12.5 TON COOLING STANDARD EFFICIENCY KHA150S4 (2ND STAGE) - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb
Temper-

Total Air Volume

ature

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

105°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

3800 138.4 8.45 0.7 0.86 1 128.4 9.38 0.71 0.88 1 117.7 10.42 0.72 0.9 1 106.5 11.6 0.74 0.94 1

63°F 4400 144 8.45 0.74 0.91 1 133.6 9.39 0.76 0.94 1 122.8 10.43 0.77 0.97 1 111.6 11.6 0.8 1

1

5000 148.6 8.45 0.78 0.96 1 138.6 9.39 0.8 0.98 1 127.6 10.43 0.82 1 1 116.8 11.61 0.85 1

1

3800 149.2 8.46 0.54 0.68 0.82 138.7 9.39 0.54 0.69 0.84 128.2 10.43 0.54 0.7 0.86 116.2 11.6 0.54 0.72 0.89

67°F 4400 155 8.47 0.57 0.72 0.87 144.3 9.39 0.57 0.73 0.89 132.8 10.42 0.57 0.75 0.93 120.4 11.59 0.58 0.77 0.96

5000 159.6 8.47 0.59 0.76 0.92 148.7 9.39 0.59 0.77 0.95 136.9 10.43 0.6 0.8 0.98 124.6 11.62 0.61 0.82 1

3800 160.3 8.47 0.4 0.53 0.66 149.9 9.39 0.39 0.53 0.67 138.9 10.44 0.38 0.53 0.68 126.5 11.61 0.37 0.54 0.69

71°F 4400 166.4 8.48 0.41 0.56 0.69 155.5 9.4 0.41 0.56 0.71 143.7 10.43 0.4 0.56 0.72 131.4 11.62 0.39 0.57 0.74

5000 171 8.49 0.42 0.58 0.74 159.7 9.4 0.41 0.58 0.75 148.1 10.44 0.41 0.59 0.77 135.5 11.62 0.41 0.6 0.8

12.5 TON HEATING STANDARD EFFICIENCY KHA150S4 - SINGLE ZONE VAV SUPPLY FAN SUPPLY AIR BLOWER

Indoor Coil Air Volume
70°F Dry Bulb cfm
3800 4400 5000

65°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

167.2

10.04

170.6

9.68

174.0

9.41

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Comp.

Heating Motor Input Heating Motor Input Heating Motor Input

Capacity

Input

Capacity

Input

Capacity

Input

kBtuh

kW

kBtuh

kW

kBtuh

kW

127.6

9.22

86.4

8.39

58.2

7.34

131.1

8.86

89.8

8.03

61.7

6.97

134.5

8.59

93.2

7.76

65.1

6.71

-15°F

Total

Comp.

Heating Motor Input

Capacity

Input

kBtuh

kW

28.6

5465

32.0

5100

35.4

4835

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 21

BLOWER DATA
092 BELT DRIVE BLOWER - BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (heat section, economizer, etc.) 3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 24 for blower motors and drives. See page 24 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 7.5 kW, 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm

Total

Total Static Pressure - in. w.g.

Air Volume

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2

2.2

2.4

2.6

cfm RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1750 583 0.09 627 0.06 673 0.09 723 0.06 777 0.45 834 0.82 892 1.13 943 1.28 990 1.38 1038 1.44 1084 1.60 1131 1.79 1179 2.25

2000 593 0.11 636 0.07 682 0.10 731 0.22 784 0.60 840 0.96 898 1.26 948 1.38 996 1.47 1045 1.57 1092 1.71 1140 1.92 1188 2.32

2250 604 0.15 645 0.11 690 0.15 739 0.39 790 0.74 846 1.08 901 1.34 953 1.48 1002 1.57 1052 1.70 1100 1.86 1149 2.09 1197 2.42

2500 615 0.19 655 0.15 699 0.20 747 0.55 797 0.89 851 1.20 906 1.44 959 1.58 1009 1.68 1059 1.83 1108 2.01 1158 2.26 1206 2.52

2750 626 0.23 666 0.19 709 0.37 755 0.71 805 1.03 858 1.32 912 1.55 966 1.70 1017 1.81 1067 1.97 1117 2.17 1166 2.44 1215 2.71

3000 637 0.27 677 0.24 719 0.55 764 0.87 813 1.18 866 1.45 920 1.67 975 1.82 1026 1.96 1076 2.13 1126 2.35 1176 2.63 1225 2.92

3250 650 0.31 688 0.43 730 0.73 775 1.04 823 1.34 875 1.60 930 1.81 985 1.97 1036 2.12 1086 2.31 1136 2.54 1186 2.83 1235 3.13

3500 663 0.35 700 0.63 741 0.92 786 1.22 834 1.50 886 1.76 942 1.96 997 2.14 1048 2.31 1097 2.51 1147 2.75 1196 3.04 1245 3.35

3750 676 0.57 714 0.84 754 1.12 798 1.41 846 1.68 899 1.93 956 2.14 1010 2.32 1060 2.51 1109 2.72 1158 2.98 1207 3.27 1255 3.58

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 22

BLOWER DATA

102, 120, 150 BELT DRIVE BLOWER - BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (heat section, economizer, etc.) 3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 24 for blower motors and drives. See page 24 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm 60 kW - 4000 cfm

Total

Total Static Pressure - in. w.g.

Air Volume

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2

2.2

2.4

2.6

cfm RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1750 480 0.19 548 0.39 618 0.57 689 0.70 758 0.81 824 0.92 885 1.07 941 1.23 992 1.40 1039 1.55 1084 1.70 1128 1.85 1156 2.08

2000 492 0.27 560 0.47 629 0.64 700 0.77 768 0.88 832 1.00 892 1.16 946 1.32 995 1.48 1041 1.65 1085 1.81 1127 1.97 1160 2.13

2250 505 0.35 573 0.55 643 0.72 713 0.85 780 0.97 842 1.10 900 1.25 952 1.42 999 1.59 1044 1.76 1087 1.93 1127 2.10 1164 2.27

2500 520 0.45 588 0.64 658 0.81 727 0.94 793 1.07 853 1.21 909 1.37 959 1.54 1005 1.71 1048 1.89 1089 2.07 1127 2.25 1166 2.42

2750 536 0.55 604 0.74 674 0.91 743 1.05 806 1.19 865 1.34 919 1.50 968 1.67 1012 1.86 1053 2.04 1092 2.23 1129 2.41 1167 2.60

3000 553 0.66 622 0.85 692 1.02 760 1.17 821 1.32 878 1.48 930 1.64 977 1.83 1020 2.02 1059 2.21 1096 2.41 1133 2.60 1170 2.79

3250 572 0.77 641 0.98 712 1.15 778 1.32 837 1.48 892 1.64 942 1.81 988 2.00 1028 2.20 1066 2.41 1102 2.61 1138 2.81 1174 3.01

3500 592 0.90 663 1.12 733 1.31 798 1.48 854 1.65 907 1.82 955 1.99 999 2.19 1038 2.41 1074 2.63 1109 2.84 1144 3.04 1180 3.24

3750 614 1.04 687 1.28 756 1.48 818 1.66 872 1.83 922 2.01 969 2.19 1010 2.41 1048 2.64 1084 2.87 1118 3.09 1152 3.29 1188 3.50

4000 639 1.22 712 1.47 780 1.67 838 1.85 890 2.03 939 2.22 983 2.42 1023 2.65 1060 2.90 1095 3.14 1128 3.36 1162 3.57 1198 3.77

4250 666 1.42 740 1.68 804 1.88 859 2.06 909 2.25 956 2.45 998 2.67 1036 2.92 1072 3.18 1106 3.42 1139 3.65 1172 3.86 1208 4.07

4500 697 1.65 769 1.91 829 2.10 881 2.28 929 2.48 973 2.71 1013 2.95 1050 3.22 1085 3.48 1118 3.73 1151 3.96 1184 4.17 1221 4.39

4750 729 1.91 798 2.15 854 2.34 903 2.53 948 2.75 991 3.00 1030 3.27 1065 3.55 1099 3.81 1132 4.06 1164 4.29 1198 4.51 1235 4.74

5000 763 2.18 826 2.41 878 2.60 925 2.81 968 3.05 1009 3.33 1046 3.61 1081 3.90 1114 4.17 1146 4.42 1178 4.65 1212 4.87 1250 5.09

5250 797 2.47 854 2.69 903 2.90 947 3.12 989 3.39 1028 3.69 1064 3.99 1098 4.28 1130 4.55 1162 4.80 1194 5.02 1228 5.24 1266 5.47

5500 830 2.78 882 3.00 927 3.22 969 3.48 1010 3.77 1047 4.09 1083 4.40 1116 4.69 1147 4.96 1179 5.20 1211 5.42 1246 5.63 - - - - - -

5750 861 3.11 908 3.34 951 3.58 992 3.87 1031 4.19 1068 4.52 1102 4.84 1134 5.12 1165 5.38 1196 5.61 - - - - - - - - - - - - - - - - - -

6000 890 3.45 935 3.71 976 3.98 1016 4.31 1053 4.65 1089 4.99 1122 5.30 1153 5.58 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6250 918 3.84 961 4.12 1001 4.43 1040 4.79 1076 5.14 1110 5.48 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 23

BLOWER DATA

FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS

Nominal hp

Maximum hp

Drive Kit Number

RPM Range

2

2.3

1

590 - 890

2

2.3

2

800 - 1105

2

2.3

3

795 - 1195

3

3.45

4

730 - 970

3

3.45

5

940 - 1200

3

3.45

6

1015 - 1300

5

5.75

10

900 - 1135

5

5.75

11

1040 - 1315

5

5.75

12

1125 - 1425

NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
NOTE ­ Units equipped with Single Zone VAV Supply Fan option are limited to a motor service factor of 1.0.

POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure in. w.g. 0 0.05 0.10 0.15 0.20 0.25 0.30 0.35

Air Volume Exhausted cfm 3175 2955 2685 2410 2165 1920 1420 1200

FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.

Air Volume cfm

Wet Indoor Coil

092

102, 120, 150

Electric Heat

Economizer

Filters

MERV 8

MERV 13

1750

0.03

0.04

0.03

0.05

0.01

0.03

2000

0.04

0.05

0.03

0.06

0.01

0.03

2250

0.05

0.06

0.04

0.08

0.01

0.04

2500

0.05

0.07

0.04

0.11

0.01

0.05

2750

0.06

0.08

0.05

0.12

0.02

0.05

3000

0.07

0.10

0.06

0.13

0.02

0.06

3250

0.08

0.11

0.06

0.15

0.02

0.06

3500

0.09

0.12

0.09

0.15

0.03

0.07

3750

0.10

0.14

0.09

0.15

0.03

0.08

4000

0.11

0.15

0.09

0.19

0.04

0.08

4250

0.13

0.17

0.13

0.19

0.04

0.09

4500

0.14

0.19

0.14

0.22

0.04

0.09

4750

0.15

0.20

0.17

0.25

0.05

0.10

5000

0.16

0.22

0.20

0.29

0.06

0.10

5250

0.17

0.24

0.22

0.32

0.06

0.11

5500

0.19

0.25

0.25

0.34

0.07

0.12

5750

0.20

0.27

0.31

0.45

0.07

0.12

6000

0.22

0.29

0.33

0.52

0.08

0.13

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 24

BLOWER DATA

CEILING DIFFUSERS AIR RESISTANCE - in. w.g.

RTD11 Step-Down Diffuser

Unit Size

Air Volume cfm

2 Ends Open

1 Side, 2 Ends Open

2400

0.21

0.18

2600

0.24

0.21

2800

0.27

0.24

092 Models

3000 3200

0.32 0.41

0.29 0.37

3400

0.50

0.45

3600

0.61

0.54

3800

0.73

0.63

3600

0.36

0.28

3800

0.40

0.32

4000

0.44

0.36

4200

0.49

0.40

102 & 120 Models

4400

0.54

0.44

4600

0.60

0.49

4800

0.65

0.53

5000

0.69

0.58

5200

0.75

0.62

4200

0.22

0.19

4400

0.28

0.24

4600

0.34

0.29

4800

0.40

0.34

150 Models

5000

0.46

0.39

5200

0.52

0.44

5400

0.58

0.49

5600

0.64

0.54

5800

0.70

0.59

All Ends & Sides Open 0.15 0.18 0.21 0.25 0.32 0.39 0.48 0.57 0.23 0.26 0.29 0.33 0.37 0.42 0.46 0.50 0.54 0.16 0.20 0.24 0.29 0.34 0.39 0.43 0.47 0.51

FD11 Flush Diffuser
0.14 0.17 0.20 0.25 0.31 0.37 0.44 0.51 0.15 0.18 0.21 0.24 0.27 0.31 0.35 0.39 0.43 0.10 0.12 0.15 0.19 0.23 0.27 0.31 0.35 0.39

CEILING DIFFUSER AIR THROW DATA

Model No.

Air Volume

1 Effective Throw Range

RTD11 Step-Down

FD11 Flush

cfm

ft.

ft.

2600

24 - 29

19 - 24

2800

25 - 30

20 - 28

092 Models

3000

27 - 33

21 - 29

3200

28 - 35

22 - 29

3400

30 - 37

22 - 30

3600

25 - 33

22 - 29

102, 120 Models

3800 4000 4200

27 - 35 29- 37 32 - 40

22 - 30 24 - 33 26 - 35

4400

34 - 42

28 - 37

5600

39 - 49

28 - 37

5800

42 - 51

29 - 38

150 Models

6000 6200

44 - 54 45 - 55

40 - 50 42 - 51

6400

46 - 55

43 - 52

6600

47 - 56

45 - 56

1 Throw is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 25

ELECTRICAL/ELECTRIC HEAT DATA

7.5 TON

7.5 TON STANDARD EFFICIENCY (R-410A)

kHa092s4

1 Voltage - 60hz Compressor 1
Compressor 2
Outdoor Fan Motors (2) Power Exhaust (1) 0.33 HP

Rated Load Amps Locked Rotor Amps
Rated Load Amps Locked Rotor Amps
Full Load Amps (total)
Full Load Amps

208/230V - 3 Ph 13.1 83.1 13.1 83.1 2.4 (4.8) 2.4

460V - 3 Ph 6.1 41 6.1 41 1.3 (2.6) 1.3

575V - 3 Ph 4.4 33 4.4 33 1 (2) 1

Service Outlet 115V GFI (amps)

Indoor Blower Motor

Horsepower

2

Full Load Amps

7.5

2 Maximum Overcurrent Protection

Unit Only

50

With (1) 0.33 HP

50

Power Exhaust

3 Minimum Circuit Ampacity

Unit Only

42

With (1) 0.33 HP

45

Power Exhaust

15

15

20

3

5

2

3

5

2

3

5

10.6

16.7

3.4 4.8 7.6 2.7 3.9 6.1

50

60

25 25 30 15 20 20

60

70

25 25 30 20 20 25

45

52

20 22 25 15 16 19

48

55

22 23 26 16 17 20

ELECTRIC HEAT DATA

Electric Heat Voltage

2 Maximum Overcurrent Protection

Unit+ 7.5 kW Electric Heat 15 kW
22.5 kW

30 kW

45 kW

3 Minimum Circuit Ampacity

Unit+ 7.5 kW Electric Heat 15 kW
22.5 kW

30 kW

45 kW

2 Maximum Overcurrent Protection

Unit+ 7.5 kW

Electric Heat 15 kW

and (1) 0.33 HP Power Exhaust

22.5 kW

30 kW

45 kW

3 Minimum Circuit Ampacity

Unit+ 7.5 kW

Electric Heat 15 kW

and (1) 0.33 HP Power Exhaust

22.5 kW

30 kW

45 kW

ELECTRICAL ACCESSORIES

Disconnect

7.5 kW

15 kW

22.5 kW

30 kW

45 kW

208V 70 90 110 125 175 62 81 101 120 160 70 90 110 125 175 64 84 103 123 162

240V 70 90 110 150 200 65 87 110 132 178 70 90 125 150 200 67 90 112 135 180

208V 70 90 110 125 175 65 84 104 124 163 70 90 110 150 175 67 87 106 126 165

240V 70 90 125 150 200 68 90 113 136 181 70 100 125 150 200 70 93 115 138 183

208V 80 100 125 150 175 72 91 111 131 170 80 100 125 150 175 74 94 113 133 172

54W56 54W57 54W57 54W57 Not Available

240V 80 100 125 150 200 75 97 120 143 188 80 100 125 150 200 77 100 122 145 190

480V 35 45 60 70 90 32 43 54 65 88 35 45 60 70 90 33 44 55 67 89

480V 35 45 60 70 90 33 44 55 67 89 35 45 60 70 100 34 45 57 68 91

480V 40 50 60 70 100 36 47 59 70 92 40 50 60 80 100 37 49 60 71 94

54W56 54W56 54W56 54W56 54W57

600V 25 35 45 60 70 24 33 42 51 69 25 35 45 60 70 25 34 43 52 70

600V 25 35 45 60 70 25 34 43 52 70 30 35 45 60 80 26 35 44 53 71

600V 30 40 50 60 80 28 37 46 55 73 30 40 50 60 80 29 38 47 56 74

54W56 54W56 54W56 54W56 54W56

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 26

ELECTRICAL/ELECTRIC HEAT DATA

8.5 TON

8.5 TON STANDARD EFFICIENCY (R-410A)

kHa102s4

1 Voltage - 60hz Compressor 1
Compressor 2
Outdoor Fan Motors (2) Power Exhaust (1) 0.33 HP

Rated Load Amps Locked Rotor Amps
Rated Load Amps Locked Rotor Amps
Full Load Amps (total)
Full Load Amps

208/230V - 3 Ph 14.5 98 14.5 98 3 (6) 2.4

460V - 3 Ph 6.3 55 6.3 55 1.5 (3) 1.3

575V - 3 Ph 6 41 6 41 1.2
(2.4) 1

Service Outlet 115V GFI (amps)

Indoor Blower Motor

Horsepower

2

Full Load Amps

7.5

2 Maximum Overcurrent Protection

Unit Only

60

With (1) 0.33 HP

60

Power Exhaust

3 Minimum Circuit Ampacity

Unit Only

47

With (1) 0.33 HP

49

Power Exhaust

15

15

20

3

5

2

3

5

2

3

5

10.6

16.7

3.4 4.8 7.6 2.7 3.9 6.1

60

70

25 25 30 20 25 25

60

70

25 25 30 25 25 25

50

56

21 22 26 19 20 23

52

59

22 24 27 20 21 24

ELECTRIC HEAT DATA

Electric Heat Voltage

208V 240V 208V 240V 208V 240V 480V 480V 480V

2 Maximum Overcurrent Protection

Unit+ 7.5 kW 70 70 70 80 80 90 35 35 40 Electric Heat 15 kW 90 100 90 100 100 110 45 45 50
22.5 kW 110 125 110 125 125 125 60 60 60

30 kW 125 150 150 150 150 150 70 70 80

45 kW 175 200 175 200 175 200 90 90 100

3 Minimum Circuit Ampacity

Unit+ 7.5 kW 66 69 69 72 76 79 32 34 37 Electric Heat 15 kW 86 92 89 95 95 101 44 45 48
22.5 kW 105 114 108 117 115 124 55 56 59

30 kW 125 137 128 140 135 147 66 68 71

45 kW 164 182 167 185 174 192 89 90 93

2 Maximum

Unit+ 7.5 kW 70 80 80 80 90 90 35 35 40

Overcurrent

Electric Heat 15 kW 90 100 100 100 100 110 45 50 50

Protection

and (1) 0.33 HP Power Exhaust

22.5 kW

110

125

125

125

125

150

60

60

70

30 kW 150 150 150 150 150 150 70 70 80

3 Minimum Circuit Ampacity

45 kW 175 200 175 200 200 200 90 100 100

Unit+ 7.5 kW 69 72 72 75 78 81 34 35 38

Electric Heat 15 kW 88 94 91 97 98 104 45 46 49

and (1) 0.33 HP Power Exhaust

22.5 kW

108

117

111

120

117

126

56

58

61

30 kW 127 139 130 142 137 149 67 69 72

45 kW 166 184 169 187 176 194 90 91 95

ELECTRICAL ACCESSORIES

Disconnect

7.5 kW

54W56

54W56

15 kW

54W57

54W56

22.5 kW

54W57

54W56

30 kW

54W57

54W56

45 kW

Not Available

54W57

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

600V 30 40 50 60 80 28 37 46 55 73 30 40 50 60 80 29 38 47 56 74

600V 30 40 50 60 80 29 38 47 56 74 30 40 50 60 80 30 39 48 57 75

600V 35 45 50 60 80 32 41 50 59 77 35 45 60 60 80 33 42 51 60 78

54W56 54W56 54W56 54W56 54W56

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 27

ELECTRICAL/ELECTRIC HEAT DATA

10 TON

10 TON STANDARD EFFICIENCY (R-410A)

1 Voltage - 60hz Compressor 1

Rated Load Amps

Locked Rotor Amps

Compressor 2

Rated Load Amps

Locked Rotor Amps

Outdoor Fan Motors (2)

Full Load Amps (total)

Power Exhaust (1) 0.33 HP

Full Load Amps

208/230V - 3 Ph 15.6 110 15.6 110 3 (6) 2.4

460V - 3 Ph 7.8 52 7.8 52 1.5 (3) 1.3

kHa120s4
575V - 3 Ph 5.8 38.9 5.8 38.9 1.2 (2.4) 1

Service Outlet 115V GFI (amps)

15

15

Indoor Blower Motor

Horsepower

2

Full Load Amps

7.5

3

5

2

3

5

10.6

16.7

3.4 4.8 7.6

2 Maximum

Unit Only

60

60

70

30 30 35

Overcurrent

With (1) 0.33 HP

60

60

70

30 30 35

Protection

Power Exhaust

3 Minimum Circuit Ampacity

Unit Only

49

52

59

24 26 29

With (1) 0.33 HP

51

55

61

26 27 30

Power Exhaust

ELECTRIC HEAT DATA

Electric Heat Voltage

2 Maximum Overcurrent Protection

Unit+ 15 kW Electric Heat 22.5 kW
30 kW

208V 90 110 150

240V 100 125 150

208V 100 125 150

240V 100 125 150

208V 100 125 150

240V 110 150 150

480V 50 60 70

480V 50 60 80

480V 60 70 80

45 kW 175 200 175 200 200 200 100 100 100

3 Minimum Circuit Ampacity

60 kW 175 200 200 200 200 225 100 100 110
Unit+ 15 kW 88 94 91 97 98 104 47 48 51 Electric Heat 22.5 kW 108 117 111 120 117 126 58 60 62
30 kW 127 139 130 142 137 149 70 71 74

45 kW 166 184 169 188 176 194 92 94 96

60 kW 174 193 177 197 184 203 97 98 101

2 Maximum

Unit+ 15 kW 100 100 100 100 100 110 50 50 60

Overcurrent

Electric Heat 22.5 kW 110 125 125 125 125 150 60 70 70

Protection

and (1) 0.33 HP Power Exhaust

30 kW 150

150

150

150

150

175

80

80

80

45 kW 175 200 175 200 200 200 100 100 100

3 Minimum Circuit Ampacity

60 kW 200 200 200 200 200 225 100 100 110

Unit+ 15 kW 91 97 94 100 100 106 48 50 53

Electric Heat 22.5 kW 110 119 113 122 120 129 60 61 64

and (1) 0.33 HP Power Exhaust

30 kW 130

142

133

145

139

151

71

72

75

45 kW 169 187 172 190 178 196 93 95 98

60 kW 177 196 180 199 186 205 98 99 102

ELECTRICAL ACCESSORIES

Disconnect

15 kW

54W57

54W56

22.5 kW

54W57

54W56

30 kW

54W57

54W56

45 kW

Not Available

54W57

60 kW

Not Available

54W57

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

20

2

3

5

2.7 3.9 6.1

20 25 25

20 25 25

19 20 22 20 21 23

600V 40 50 60 80 80 37 46 55 73 76 40 50 60 80 80 38 47 56 74 77

600V 40 50 60 80 80 38 47 56 74 78 40 50 60 80 80 39 48 57 75 79

600V 40 50 60 80 80 40 49 58 76 80 45 50 60 80 90 41 50 59 77 81

54W56 54W56 54W56 54W56 54W56

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 28

ELECTRICAL/ELECTRIC HEAT DATA

12.5 TON

12.5 TON STANDARD EFFICIENCY (R-410A)

1 Voltage - 60hz Compressor 1

Rated Load Amps

Locked Rotor Amps

Compressor 2

Rated Load Amps

Locked Rotor Amps

Outdoor Fan Motors (2)

Full Load Amps (total)

Power Exhaust (1) 0.33 HP

Full Load Amps

208/230V - 3 Ph 19 123 19 123 2.4 (7.2) 2.4

460V - 3 Ph 9.7 62 9.7 62 1.3 (3.9) 1.3

KHA150S4
575V - 3 Ph 7.4 50 7.4 50 1 (3) 1

Service Outlet 115V GFI (amps)

15

15

Indoor Blower Motor

Horsepower

2

Full Load Amps

7.5

3

5

2

3

5

10.6

16.7

3.4 4.8 7.6

2 Maximum

Unit Only

70

70

80

35 40 40

Overcurrent

With (1) 0.33 HP

70

80

80

40 40 40

Protection

Power Exhaust

3 Minimum Circuit Ampacity

Unit Only

58

61

67

30 31 34

With (1) 0.33 HP

60

63

70

31 32 35

Power Exhaust

ELECTRIC HEAT DATA

Electric Heat Voltage

2 Maximum Overcurrent Protection

Unit+ 15 kW Electric Heat 22.5 kW
30 kW

208V 100 125 150

240V 110 150 150

208V 110 125 150

240V 110 150 175

208V 110 150 150

240V 125 150 175

480V 60 70 80

480V 60 70 80

480V 60 70 80

45 kW 175 200 200 200 200 225 100 100 110

3 Minimum Circuit Ampacity

60 kW 200 225 200 225 200 225 110 110 110
Unit+ 15 kW 97 103 100 106 106 112 52 54 56 Electric Heat 22.5 kW 117 126 120 129 126 135 63 65 68
30 kW 136 148 139 151 145 157 75 76 79

45 kW 175 193 178 196 184 202 97 99 101

60 kW 183 202 186 205 192 211 102 103 106

2 Maximum

Unit+ 15 kW 110 110 110 110 110 125 60 60 60

Overcurrent

Electric Heat 22.5 kW 125 150 125 150 150 150 70 70 70

Protection

and (1) 0.33 HP Power Exhaust

30 kW 150

175

150

175

150

175

80

80

80

45 kW 200 200 200 200 200 225 100 100 110

3 Minimum Circuit Ampacity

60 kW 200 225 200 225 200 225 110 110 110

Unit+ 15 kW 99 105 103 109 109 115 53 55 58

Electric Heat 22.5 kW 119 128 122 131 128 137 65 66 69

and (1) 0.33 HP Power Exhaust

30 kW 139

151

142

154

148

160

76

77

80

45 kW 178 196 181 199 187 205 99 100 103

60 kW 185 205 189 208 195 214 103 104 107

ELECTRICAL ACCESSORIES

Disconnect

15 kW

54W57

54W56

22.5 kW

54W57

54W56

30 kW

Not Available

54W56

45 kW

Not Available

54W57

60 kW

Not Available

54W57

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

20

2

3

5

2.7 3.9 6.1

25 30 30

30 30 30

23 24 26 24 25 27

600V 45 50 60 80 90 41 50 59 77 81 45 60 60 80 90 42 51 60 78 82

600V 45 60 60 80 90 42 51 60 78 82 45 60 70 80 90 43 52 61 79 83

600V 45 60 70 80 90 44 53 62 80 84 45 60 70 90 90 45 54 63 81 85

54W56 54W56 54W56 54W57 54W57

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 29

ELECTRIC HEAT CAPACITIES

7.5 kW

15 kW

22.5 kW

30 kW

45 kW

60 kW

Volts

Input kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of

Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages

208 5.6 19,100 1 11.3 38,600 1 16.9 57,700 2 22.5 76,800 2 33.8 115,300 2 45.0 153,600 2

220 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2

230 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

240 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

440 6.9 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2

460 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

480 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

550 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2

575 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

600 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

UNIT CLEARANCES - INCHES (MM)

C

OPTIONAL OUTDOOR AIR HOOD

D

DB

A

1 Unit Clearance

A

B

in. mm in. mm in.

Service Clearance

60 1524 36

914

36

Minimum Operation Clearance

36

914

36

914

36

NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1 S ervice Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation.

C mm 914 914

D

in. mm

60 1524

36

914

Top Clearance
Unobstructed

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 30

OUTDOOR SOUND DATA

Unit Model Number

Octave Band Linear Sound Power Levels dBA, re 10-12 Watts Center Frequency - Hz

125

250

500

1000

2000

4000

8000

1 Sound Rating Number (SRN)
(dBA)

092, 102 and 120

76

79

84

83

79

73

66

88

150

77

80

85

84

79

74

66

88

Note - The octave sound power data does not include tonal corrections.
1 Sound Rating Number according to ARI Standard 270-95 or ARI Standard 370-2001 (includes pure tone penalty). "SRN" is the overall A-Weighted Sound Power Level, (Lwa), dB (100 Hz to 10,000 Hz).

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 31

WEIGHT DATA
Model Number
092 Base Unit 092 Max. Unit 102 Base Unit 102 Max. Unit 120 Base Unit 120 Max. Unit 150 Base Unit 150 Max. Unit

Net

lbs.

kg

1052

477

1209

548

1084

492

1241

563

1150

522

1314

596

1350

612

1514

687

lbs. 1137 1294 1169 1326 1235 1399 1435 1599

Shipping kg 516 587 530 601 560 635 651 725

OPTIONS / ACCESSORIES

Model Number

Shipping Weight

lbs.

kg

ECONOMIZER / OUTDOOR AIR / EXHAUST

Economizer

Economizer Dampers

60

27

Barometric Relief Dampers (downflow)

8

4

Barometric Relief Damper Hood (downflow)

25

11

Outdoor Air Hood (downflow)

23

10

Outdoor Air Dampers

Outdoor Air Damper Section (downflow) - Automatic

9

4

Outdoor Air Damper Section (downflow) - Manual

2

1

Outdoor Air Damper Hood (downflow)

9

4

Power Exhaust

31

14

ELECTRIC HEAT

7.5 kW

50

23

15 kW

50

23

22.5 kW

57

26

30 kW

57

26

45 kW

59

27

60 kW

68

31

Single Zone VAV Supply Fan SUPPLY AIR BLOWER OPTION

Variable Frequency Drive (VFD) and associated components

10

5

ROOF CURBS

Hybrid Roof Curbs, Downflow

8 in. height

60

27

14 in. height

85

39

18 in. height

100

45

24 in. height

125

57

PACKAGING

LTL Packaging (less than truck load)

105

48

CEILING DIFFUSERS

Step-Down

RTD11-95

88

40

RTD11-135

205

93

RTD11-185

392

178

Flush

FD11-95

75

34

FD11-135

174

79

FD11-185

289

131

Transitions

LASRT08/10

30

14

LASRT10/12

32

15

LASRT15

36

16

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 32

DIMENSIONS - INCHES (mm) - 092-102-120 MODELS

CORNER WEIGHTS

Model

AA

No. Base Max.

BB Base Max.

CC Base Max.

DD Base Max.

CENTER OF GRAVITY

EE

Base

Max.

FF

Base

Max.

lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm in. mm in. mm 092 264 120 310 140 237 108 271 123 258 117 290 131 293 133 339 154 46.5 1181 45.5 1156 24.5 622 25.5 648

102 272 123 318 144 244 111 278 126 266 121 297 135 302 137 348 158 46.5 1181 45.5 1156 24.5 622 25.5 648

120 284 129 333 151 264 120 298 135 288 131 320 145 315 143 363 165 46.5 1181 45.5 1156 24.5 622 25.5 648

Base Unit - The unit with NO OPTIONS. Max. Unit - The unit with ALL OPTIONS Installed (Economizer, etc.).

6-1/8 (156)
AA

5-5/8

(143) BOTTOM SUPPLY

AIR OPENING

BB

6-1/8 (156)
60-1/8 (1527) BASE
BOTTOM POWER ENTRY 5-1/2 (140) Dia.
7 (178)

24 (610)
27 (686)

10-3/4

28

(273) 20 (711)

(508)

CENTER OF GRAVITY

BOTTOM RETURN AIR OPENING

EE FF
6-5/8
(168)

DD

BOTTOM

CC

7 (178)

CONDENSATE

34-7/8

(886)

101-1/4

BASE

(2572)

TOP VIEW

58-1/8 (1476)

OPTIONAL DISCONNECT (FACTORY INSTALLED)

99-1/4 (2521)

60-1/8 (1527)
END VIEW

46-7/8 (1191)
43-3/8 (1102)
3-1/2 (89)

CONDENSATE DRAIN (FRONT)

1

5-3/8

(25)

(137)

46-7/8 (1191)

ELECTRIC INLETS
15-1/2 (394)

34-7/8 (886)

FORKLIFT SLOTS (BOTH SIDES)
101-1/4 (2572)
SIDE VIEW

LIFTING HOLES (FOR RIGGING)

15-1/2 (394)

1-5/8 (41)

HORIZONTAL SUPPLY AIR
OPENING

HORIZONTAL RETURN AIR
OPENING

30 (762)

6-1/8 (156)

31-1/2 (800)
66-3/8 (1686)

CONDENSATE DRAIN (BACK)
30 (762)

5-3/8 (137)

SIDE VIEW (Horizontal Openings)

12-1/8 (308)

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 33

DIMENSIONS - INCHES (MM) - 150 MODELS

CORNER WEIGHTS

CENTER OF GRAVITY

Model

AA

No. Base Max.

BB Base Max.

CC Base Max.

DD Base Max.

EE

Base

Max.

FF

Base

Max.

lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm in. mm in. mm

150 348 158 398 180 303 137 337 153 321 146 353 160 377 171 426 193 46.5 1181 45.5 1156 24.5 622 25.5 648

Base Unit - The unit with NO OPTIONS. Max. Unit - The unit with ALL OPTIONS Installed (Economizer, etc.).

6-1/8

5-5/8

(156)

(143) BOTTOM SUPPLY

AA

AIR OPENING

BB

6-1/8 (156)
60-1/8 (1527) BASE
BOTTOM POWER ENTRY 5-1/2 (140) Dia.
7 (178)

24 (610)
27 (686)

10-3/4 (273)

28 20 (711) (508)

CENTER OF GRAVITY

BOTTOM RETURN AIR OPENING
EE FF
6-5/8 (168)

DD

7 (178)

BOTTOM CONDENSATE

CC

34-7/8

(886)

124-3/8 BASE

(3159)

TOP VIEW

58-1/8 (1476)

OPTIONAL DISCONNECT (FACTORY INSTALLED)

123-1/8 (3127)

60-1/8 (1527)
END VIEW

46-7/8 (1191) 43-3/8 (1102)
3-1/2 (89)

CONDENSATE DRAIN (FRONT)

5/8

5-3/8

(16)

(137)

46-7/8 (1191)

ELECTRIC INLETS

34-7/8 (886)

FORKLIFT SLOTS (BOTH SIDES)
124-3/8 (3159)
SIDE VIEW

LIFTING HOLES (FOR RIGGING)

15-1/2 (394)

1-5/8 (41)

15-1/2 (394)

HORIZONTAL SUPPLY AIR
OPENING

HORIZONTAL RETURN AIR
OPENING

30 (762)

54-5/8 (1387)

6-1/8 (156)
89-1/2 (2273)

CONDENSATE DRAIN (BACK)
30 (762)

SIDE VIEW (Horizontal Openings)

5-3/8 (137)

12-1/8 (308)

ACCESSORY DIMENSIONS - INCHES (MM) UNIT ON CURB LOCATION - KHA150

UNIT BASE RAIL

ROOF CURB

DETAIL A
95-3/8 (2423)
SIDE VIEW

27 (686)

UNIT/ROOF CURB ALLIGNMENT RAIL (Furnished with KHA150 Unit)

ROOF CURB

DETAIL A

OUTDOOR AIR HOOD DETAIL
21-3/8 (543)
OUTDOOR AIR HOOD (Furnished with Economizer or
Outdoor Air Damper)
EXHAUST AIR HOOD (Furnished, Field Installed)

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 35

ACCESSORY DIMENSIONS - INCHES (MM)

HORIZONTAL ECONOMIZER APPLICATION (With Furnished Barometric Relief Dampers and Optional Horizontal Discharge Kit - Required)

ECONOMIZER DAMPERS

RETURN AIR DUCT INLET (Field Fabricated - Must be sized to accommodate Barometric Relief Hood
and Return Air Requirements)

HORIZONTAL BAROMETRIC RELIEF DAMPERS AND HOOD

SUPPLY AIR DUCT (Field Provided)

SUPPLY AIR
OUTLET

TOP VIEW

15-1/2 (394)

30 (762)
HORIZONTAL SUPPLY AIR
OPENING (On Unit)

RETURN AIR DUCT TRANSITION (Field fabricated and
installed on unit)

RETURN AIR
INLET

BAROMETRIC RELIEF HOOD DIMENSIONS
Width - 31-1/4 in. (794 mm) Height - 22-1/2 in. (572 mm)

38-3/4 (984) This opening not used in Horizontal Applications with Economizer

OUTDOOR AIR HOOD (Furnished with Economizer)

21-3/8 (543)

BAROMETRIC RELIEF DAMPERS Furnished with Economizer, detached from Economizer and field installed on
Field fabricated Return Air Duct

OUTDOOR AIR

4-1/8 (105)

HORIZONTAL RETURN AIR
OPENING

26 (660)

19-3/4 (502)

27-3/4 (705)

6-1/8 (156)

36 (914)
RETURN AIR DUCT TRANSITION (Field fabricated and
installed on unit)
BACK VIEW

EXHAUST AIR

6 (152)

RETURN AIR DUCT INLET (Field Fabricated - Must be sized to accommodate Barometric Relief Hood
and Return Air Requirements)

OPTIONAL RETURN AIR OPENING WITH ECONOMIZER AND HORIZONTAL
DISCHARGE KIT (required) (Field Installed)
END VIEW

NOTE - Return Air Duct and Transition must be supported.

BAROMETRIC RELIEF DAMPERS (Furnished with Economizer)
(Field installed in horizontal return air duct adjacent to unit)

31-3/4 (807) 129-3/4 (756)

14-1/2 (368)

24 (612)
1 23-1/8 (587)

FRONT VIEW

SIDE VIEW

1 NOTE - Opening size required in return air duct.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 36

ACCESSORY DIMENSIONS - INCHES (MM)
HORIZONTAL ECONOMIZER APPLICATION (with Optional Low Profile Horizontal Barometric Relief Dampers and Horizontal Discharge Kit - Required)
ECONOMIZER DAMPERS

HORIZONTAL LOW PROFILE BAROMETRIC RELIEF
DAMPERS AND HOOD

SUPPLY AIR DUCT (Field Provided)

SUPPLY AIR
OUTLET

TOP VIEW

15-1/2 (394)

30 (762)
HORIZONTAL SUPPLY AIR
OPENING (On Unit)

RETURN AIR DUCT TRANSITION (Field fabricated and
installed on unit)

RETURN AIR
INLET

RETURN AIR DUCT INLET (Field Fabricated - Must be sized to
accommodate Low Profile Horizontal Barometric Relief Hood and
Return Air Requirements)
HORIZONTAL RELIEF HOOD DIMENSIONS Width - 31-5/8 in. (803 mm) Height - 14-1/2 in. (368 mm)

38-3/4 (984)
This opening not used in Horizontal Applications
with Economizer

OUTDOOR AIR HOOD (Furnished with Economizer)

21-3/8 (543)

HORIZONTAL LOW PROFILE

BAROMETRIC RELIEF DAMPERS

(Optional - Must be Ordered Extra and

Field Installed on Field fabricated

Return Air Duct)

OUTDOOR AIR

4-1/8 (105)

HORIZONTAL RETURN AIR
OPENING

EXHAUST AIR

19-3/4 (502)

27-3/4 (705)

6-1/8

6

(156)

RETURN AIR

RETURN AIR DUCT INLET

(152) OPTIONAL RETURN AIR OPENING

DUCT TRANSITION (Field Fabricated - Must be sized to

WITH ECONOMIZER AND HORIZONTAL

(Field fabricated and

accommodate Low Profile

DISCHARGE KIT (required)

installed on unit)

Horizontal Barometric Relief Hood and

(Field Installed)

BACK VIEW

eturn Air Requirements)

END VIEW

NOTE - Return Air Duct and Transition must be supported.

HORIZONTAL LOW PROFILE BAROMETRIC RELIEF DAMPERS (Field installed in horizontal return air duct adjacent to unit)

31-5/8 (803) 1 29-1/2 (749)

6-1/2 (165)

14-1/2 (368)
1 13 (300)

FRONT VIEW

SIDE VIEW

1 NOTE - Opening size required in return air duct.

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 37

ACCESSORY DIMENSIONS - INCHES (MM)
HYBRID ROOF CURBS - DOUBLE DUCT OPENING

26-3/4 (679)

95-3/8 (2423)
91-7/8 (2334)
8-1/2 (216)

29-3/4 (756)

RETURN OPENING

SUPPLY OPENING

29-3/4 (756)
50-3/4 (1289)

21-3/4 (552)

54-1/4 (1378)

8 (203) 14 (356) 18 (457) 24 (610)

NOTE - Roof deck may be omitted within confines of curb.

TYPICAL FLASHING DETAIL FOR ROOF CURB

BASE BOTTOM

PACKAGED UNIT

FIBERGLASS INSULATION
(Furnished)
NAILER STRIP (Furnished)
ROOF CURB (Extends around entire
perimeter of unit)
RIGID INSULATION (Field Supplied)

COUNTER FLASHING (Field Supplied)
CANT STRIP (Field Supplied)
ROOFING MATERIAL

DETAIL ROOF CURB
1-3/4 (44)
1/2 (13)

8 (203) 14 (356) 18 (457) 24 (610)

FACTORY INSTALLED PERIMETER WOOD NAILER STRIP
1-3/4 (44)

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 38

ACCESSORY DIMENSIONS - INCHES (MM)

ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS

LASRT08/10 ROUND TRANSITIONS (for 092 models with FD11-95, RTD11-95 Diffusers)

30 (762)

1-1/2

Typ.

(38)

31 (787)

8 (203)

2 (51)

20 IN. (508 mm) Diameter

LASRT10/12 & LASRT15 RECTANGULAR TRANSITIONS (for 102 thru 150 models with FD11-135-185, RTD11-135-185 Diffusers)

30 (762)

1-1/2 Typ. (38) 31 (787)
LASRT10/12 39 (991) LASRT15

8 (203) 2 (51)

27-3/4 (705) LASRT10/12 35-3/4 (908)
LASRT15

17-3/4 (451)

RETURN AIR
OPENING

SUPPLY AIR
OPENING

30-1/2

4

(775)

(102)

30-1/2 (775)

TOP VIEW

31-1/2 (800) LASRT08/10 LASRT10/12 39-1/2 (1003) LASRT15

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 39

ACCESSORY DIMENSIONS - INCHES (MM)

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS

STEP-DOWN CEILING DIFFUSER

FLUSH CEILING DIFFUSER

E

G

F

G

H

D

H

C 2 (51)

E

G

F

G

L B
K

Model Number

A

in.

mm

B

in.

mm

C

in.

mm

D

in.

mm

E

in.

mm

F

in.

mm

G

in.

mm

H

in.

mm

J

in.

mm

K

in.

mm

L

in.

mm

Duct Size

in.

mm

A
J
RTD11-95 47-5/8 1159 29-5/8 752 14-3/8 365 27-1/2 699 45-1/2 1158 22-1/2 572 11-1/2 292 13-3/4 349 45-1/2 1156 27-1/2 699 8-1/8 206
20 round 508 round

B

Model Number

A

in.

mm

B

in.

mm

C

in.

mm

D

in.

mm

E

in.

mm

F

in.

mm

G

in.

mm

H

in.

mm

Duct Size

in.

mm

H

D

H

C 2 (51)

A

FD11-95 47-5/8 1159 29-5/8
752 16-5/8
422 27 686 45 1143 22-1/2 572 11-1/4 286 13-1/2 343 20 round 508 round

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 40

ACCESSORY DIMENSIONS - INCHES (MM)

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS

STEP-DOWN CEILING DIFFUSER

FLUSH CEILING DIFFUSER

E

F G

G

H

2 (51)
N B
M

J

D

K C

A L

E

F G

G

H

2 (51) B

J

D

K C

A

Model Number

A

in.

mm

B

in.

mm

C

in.

mm

D

in.

mm

E

in.

mm

F

in.

mm

G

in.

mm

H

in.

mm

J

in.

mm

K

in.

mm

L

in.

mm

M

in.

mm

N

in.

mm

Duct Size in.

mm

RTD11-135 47-5/8 1210 35-5/8 905 20-5/8 524 33-1/2 851 45-1/2 1156 4-1/2 114 18 457 2-1/2 64 28 711 2-3/4 70 45-1/2 1156 33-1/2 851 9-1/8 232 18 x 28
457 x 711

RTD11-185 47-5/8 1210 47-5/8 1210 24-5/8 625 45-1/2 1156 45-1/2 1156 4-1/2 114 18 457 2-1/2 64 36 914 4-3/4 121 45-1/2 1156 45-1/2 1156 10-1/8 257 18 x 36
457 x 914

Model Number

A

in.

mm

B

in.

mm

C

in.

mm

D

in.

mm

E

in.

mm

F

in.

mm

G

in.

mm

H

in.

mm

J

in.

mm

K

in.

mm

Duct Size in.

mm

FD11-135 47-5/8 1210 35-5/8 905 23-1/4 591 33 838 45 1143 4-1/2 114 18 457 2-1/4 57 28 711 2-1/2 64 18 x 28
457 x 711

FD11-185 47-5/8 1210 47-5/8 1210 29-1/4 743 45 1143 45 1143 4-1/2 114 18 457 2-1/4 57 36 914 4-1/2 114 18 x 36
457 x 914

K-Series Packaged Heat Pump 7.5 to 12.5 Ton / Page 41

REVISIONS
Section Accessory Dimensions Options/Accessories

Description
Added dimension drawing for horizontal economizer usage. Added new Hybrid Roof Curbs. Added new High Performance Economizers for Title 24 applications. Added new Hybrid Roof Curbs.

Visit us at www.allied-commercial.com For the latest technical information, visit us at www.allied-commercial.com Contact us at 1-800-448-5872
NOTE - Due to Allied Commercial ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
©2013 Allied Air Enterprises LLC, a Lennox International Inc. Company

