Jeri Lee Jodice

Installation Instructions February 2014 Evaporator Coil

Carrier Furnace: Carrier Furnace Dripping Water

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 8 Pages, 872.53KB

Document DEVICE REPORTArmstrong EUL1P Install
Installation Instructions
Evaporator Coil

I February 2014

These instructions must be read and understood completely before attempting installation.

TABLE OF CONTENTS

PAGE

General ........................................................... 1 Inspection of Shipment .................................. 2 Vertical ............................................................ 2 Horizontal........................................................ 2 Multi-Position ............................................... 3-5 Metering Device .............................................. 6 Condensate Drain ........................................... 7 Refrigerant Line Installation ............................ 8 Refrigerant Charging Instructions ................... 8

Warranty ......................................................... 9

GENERAL
Evaporator coils are designed for use with AC condensing units or heat pump units. These instructions are intended as a general guide and do not supersede local codes in any way. Consult with local authorities having jurisdiction before installation. Read this installation manual and all safety messages prior to installing the evaporator coil.
Check coil for shipping damage and verify the contents of the box containing the evaporator coil. If you should find damage, immediately contact the last carrier. Verify the efficiency performance requirements, such as SEER, EER, and/or HSPF, are appropriate with the matched condensing or heat pump units. Check outdoor unit manufacturer for proper line sizing. Coils are shipped with a 10 psi dry air holding charge. Puncture rubber plug on suction line to release charge before removing plugs. The absence of pressure does not verify a leak. Check the coil for leaks before installing or returning it to your wholesaler.
Position the coil on the outlet of the furnace using sheet metal screws. Drain pans are made of a polymer that can withstand temperatures up to 450°F. Maintain a 3" clearance on oil or drum type heat exchangers and 1½" on sectionalized heat exchangers. Coil should be level, or pitched slightly toward the drain connection. Airflow face velocity above 350 ft/min is not recommended for downflow or counterflow applications due to potential water blow-off.

SAFETY CONSIDERATIONS
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and signal word. These signals words mean the following:
DANGER: You can be killed or seriously injured if you don't immediately follow instructions.
WARNING: Indicate a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Caution may also be used to alert against unsafe practices.
NOTICE: Indicates a statement of company policy as the message relates directly or indirectly to the safety of personnel or protection of property.
IMPORTANT: More detailed information concerning the statement of company policy as the message relates directly or indirectly to the safety of personnel or protection of property.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.

40228B013/

Manufactured By Allied Air Enterprises LLC A Lennox International Inc. Company
215 Metropolitan Drive West Columbia, SC 29170

INSPECTION OF SHIPMENT

Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier's freight bill. Take special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the last carrier

immediately, preferable in writing, and should include a request for inspection by the carrier's agent.
If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT, as claim may be denied. Check the unit rating plate to confirm specifications are as ordered.

VERTICAL

Vertical A-Coils are designed for upflow and downflow applications. Vertical drain pans have drain connections on the right and left front side of the evaporator coil. Airflow face velocity above 350 ft/min is not recommended for downflow applications due to potential water blow-off.

Refer to Specification Guide for limitations. In downflow applications, aluminum foil tape must be applied to seal the top edge of the insulation to the cabinet. This tape will prevent the possibility of the insulation delaminating and blocking airflow.

HORIZONTAL
Horizontal A-Coils are designed for horizontal applications only. Horizontal A-Coils 17.5" and taller include furnace plate adaptors to facilitate proper fit with furnaces of different widths. Proper performance for Horizontal A-Coils with top connections requires that the air flows out through the side of coil where the top connections are located (Figure 1).

FIGURE 1
Air Flow Direction for Horizontal Coils with Top Connections

Airflow ONLY
top connections

Airflow ONLY
2

MULTI-POSITION

Multi-Position A-Coils come factory installed with a vertical and horizontal drain pans and can be configured for upflow,

FIGURE 3

downflow, horizontal blow-through or horizontal pull-through

installations. In the center opening of vertical drain pan, a

Multi-Position Configurations

metal Inlet Air Restrictor is factory installed and is required for

horizontal applications. It may be removed for vertical

applications. Airflow face velocity above 350 ft/min is not

recommended for downflow or counterflow applications

due to potential water blow-off. For horizontal configurations, install splashguard (included)

AIRFLOW

FURNACE

onto the coil outlet, and extend suction line insulation into the

SPLASH

A.

coil cabinet by 2" to prevent moisture from dripping onto the

GUARD

insulation (the rubber grommet may need to be moved).

Splashguard installation is not required for vertical

configurations. Bottom flange of guard should rest on pan and

sides screwed to the duct flanges. See page 4, Figures 4 and

5 for splashguard instructions.

FURNACE

TRANSITION

In downflow and counter flow configurations, aluminum foil tape must be applied to seal the top edge of the insulation to

SPLASH GUARD

B.

the cabinet. This tape will prevent the possibility of the insulation delaminating and blocking airflow. In horizontal pull-

12 min

through and counter flow configurations, a minimum 12"

transition is required in front of the coil as shown in Figure 3.

TRANSITION

This is required to ensure proper airflow distribution and to

FURNACE

reduce pressure drop.

C.

Coils that are 20" or less in height and are installed in a

cabinet with a height of 25-½" or greater do not require a transition; all other coil models require this transition. Coil should be level, or pitched slightly toward the drain connection. It is recommended to add silicone caulk between drain pans to prevent water carryover. Note: Multi-Position A-Coils are also

Apply foil tape to top edge of insulation

12 min FURNACE

field convertible from left-to-right or right-to-left; see page 5 for

D.

instruc ons on field conversion for horizontal airflow.

TRANSITION

Additional pre-startup checklist for Multi-Position A-Coils.

12 min

 Install splash guard (Figure 3 configurations A and B)

 Install 12" transition as shown (non-standard horizontal
applications / Figure 3 configurations B, C and D)
 Factory installed Inlet Air Restrictor should be present
in the center opening of the drain pan (horizontal applications)
 Factory installed internal water diverter should be in
place (Figure 6, item 5)
 Extend suction line insulation into cabinet (counter flow)

A. Standard Horizontal Application Left hand shown / Right hand similar (not shown) LOWEST STATIC CONFIGURATION See Spec Guide for additional data
B. Pull-Through Right hand shown / Left hand similar (not shown)
C. Blow-Through (counter flow) Left hand shown / Right hand similar (not shown)

 Tape top edge of insulation (counter flow)

D. Pull-Through (counter flow) Left hand shown / Right hand similar (not shown)

3

MULTI-POSITION (splashguard)
FIGURE 4
Splashguard without Front Slope
Seal splashguard seams with silicone or other sealant.
Splashguard

FIGURE 5
Splashguard with Front Slope
Holes used to mount splashguard to duct flanges.
Splashguard

Open end of splashguard should rest on the horizontal drain pan.

Caution: These holes are for manufacturing purposes only. DO NOT use for installation!

Fasten splash guard to duct flanges with (4) sheet metal screws. (2) on each side. Screws can be installed from the inside or outside.

First set of mounting holes are used when horizontal drain pan is flush with housing.
Second set of mounting holes are used when horizontal drain pan is shorter than cabinet height.

4" min.

Angle splashguard to ensure proper water drainage back into horizontal drain pan.

Splashguard should overlap the horizontal drain pan by at least 4".

Fasten splash guard to duct flanges with (4) sheet metal screws. (2) on each side. Screws can be installed from the inside or outside.

4

MULTI-POSITION (field conversion)
Field Conversion Instructions from Left-to-Right or Right-to-Left Airflow
Note: This applies only to models available in multi-position; typical horizontal left-to-right conversion is shown.
FOR EACH STEP, REFER TO FIGURE 6:

 Remove front panels.
 Remove the top tie bar and pull the coil assembly from the housing.
 Remove the horizontal drain pan, and re-install it to the opposite side of the coil (Note: horizontal drain pan must have drain plugs tightly closed in the rear of the unit).
 Remove the top plate.
 Remove the water diverter, and re-install it to the opposite slab (Note: If water diverter is attached by screws, remove screws, and bend tab straight or cut tab off).
 Replace the top plate, and apply sealant to seal any air gaps.
 Before re-inserting the coil assembly, cut the front flange on the housing and fold it back to allow access to the horizontal drain connections (Note: Copy the factory cut-out on the opposite side of the housing).
 Slide the coil assembly back into the housing (Note: If unit is equipped with a sheet metal spacer, it must be moved to the opposite side of the housing).
 Re-install the top tie bar.

 Re-install the piping panel to the housing.
 Cut a hole in the access panel to allow access to the horizontal drain connections, and re-install the access panel to the housing (Note: Access panel may need to be notched to allow access to suction header).
 Seal unused condensate drain connection cutout holes in the front panel to prevent air leakage.

FIGURE 6

Multi-Position Field Conversion

4

6

5

8 3

2 & 9

Note: Access panel may need to be notched to allow access to suction header

1
10 11
7 12

5

METERING DEVICE

Coils are suited for R-22 and R-410A refrigerants and can be used with a piston or a TXV. Replacement TXV part numbers are listed below; see kit instructions for change out or installation. Place a wet rag around the suction line at the cabinet during brazing to prevent overheating and damaging the sensing bulb.
For optimum performance, reattach and insulate the bulb at a 10 to 2 o'clock position outside of the cabinet to the main suction line no more than one foot from the suction line connection. When changing a system from AC to heat pump or heat pump to AC, check the current TXV specifications to determine if a TXV replacement is required. If the evaporator coil contains a non-bleed TXV and is used with a condensing unit containing a reciprocating compressor, a hard start kit will be required on the condensing unit.
Bulb must be insulated from ambient air ( e.g. Foam insulation)
IMPORTANT
When changing the metering device, ensure the metering device matches the refrigerant type and capacity of the condensing unit. Failure to do so will result in poor performance and possible compressor damage. All coils must be matched properly as listed in the AHRI directory.

Cased coils with a piston metering device are shipped with a cap and hex nut over the threaded fitting. Remove the cap and nut slowly, allowing charge to escape, and secure the liquid line stub (attached to cabinet) to the distributor assembly with hex nut. Discard cap.
For optimum performance, the piston should be sized to match the recommendation from the outdoor unit manufacturer. If the outdoor unit manufacturer does not recommend a piston size, refer to the piston size chart. When changing pistons, refer to Figure 7 and use the following procedure:
 Loosen hex nut located on liquid line and separate from distributor assembly.
 Remove the existing piston from inside the distributor assembly.
 Insert the desired piston into the distributor assembly.
 Inspect Teflon O-Ring and replace if damaged. Ensure Teflon O-Ring is in place.
 Re-install hex nut to body and torque to 10 ft-lbs.

FIGURE 7

Piston Assembly

Liquid Line Hex Nut

Teflon O-Ring Seal Piston
Distributor Assembly Coil Cabinet

REFRIGERANT LINE INSTALLATION

It is recommended to install a filter drier in the liquid line. While brazing, purge the system with Nitrogen to prevent contamination. Evacuate the system to 500 microns to ensure proper air and moisture removal (Note: Deep evacuation or triple evacuation method recommended). Open the suction

service valve slowly and allow the refrigerant to bleed into the system before opening the liquid service valve.

REFRIGERANT CHARGING INSTRUCTIONS
The system must be charged per the outdoor unit instruction manual

6

CONDENSATE DRAIN
Coils are equipped with multiple drain connections. Determine the drain connections to be used and note the difference between the primary (green) and secondary (red) openings. Drain plugs are provided for all openings; remove and discard the appropriate plugs with ½" drive ratchet and verify that remaining plugs are tight (2.5 ft-lbs). Attach drain line to pan with ¾" male pipe thread PVC fittings. Hand tight is adequate ­ do not over tighten & do not reduce drain line size!
Route drain(s) line so they will not be exposed to freezing temperatures and do not interfere with accessibility to the coil, air handling system or filter. The drain should be pitched downward 1" per 10' with a 2" trap as close to the coil as possible. If line makes a second trap, or has an extended run before termination, a vent tee should be installed after the trap closest to the pan. See Figure 8.
If the coil is located in or above a living space where damage may result from condensate overflow, a separate ¾" drain must be provided from the secondary drain connection. Run this drain to a place in compliance with local installation codes where it will be noticed when unit is operational. Condensate flowing from the secondary drain indicates a plugged primary drain. Prime the trap with water. Test line for leaks. Test water flow with unit in operation. An auxiliary drain pan should also be installed under the unit as specified by most local building codes.

FIGURE 8

Condensate Drain

Vent in this location (before trap) is acceptable as long as proper drainage is achieved

Vent must extend a minimum of 2" above the drain pan

Drain Pan

2" Min.

3/4" MPT Connector

2" Min. 2" Min.

Vent "T"

WARNING
This product may contain fiberglass wool insulation. Glass wool fibers are known to the State of California to cause cancer. Disturbing insulation during installation, maintenance, or repair may expose you to glass wool fibers and may cause respiratory, skin or eye irritation. For further information on risks associated with fiberglass wool, consult Material Safety Data Sheet available from OEM.

IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC's and HFC's). Approved methods of reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance.

INSTALLATION CHECKLIST

Downflow:

Metering Device:

 <350 ft/min

 Verify and/or install correct TXV or piston

 Tape top edge of insulation

TXV Installation Only:

Multi-Position:

 Place TXV bulb at 10 to 2 o'clock position

 Complete additional checklist on page 3

 Insulate bulb

 Connect equalizer line

Drains:  Install and trap primary and secondary condensate drains  If over a finished space, install secondary drain pan
Air Path:  Cover any unused knockouts
Charging:  Charge per charging instructions

7

ALLIED AIR ENTERPRISES EQUIPMENT LIMITED WARRANTY APPLIES IN U.S.A. AND CANADA ONLY FAILURE TO MAINTAIN YOUR EQUIPMENT WILL VOID THIS WARRANTY
COVERED EQUIPMENT
The following Allied Air Enterprises heating and cooling equipment is covered by the Limited Warranty,
Condensing Units: 4SCU13, 4SCU14, 4SCU16, 4SCU18, 4AC13, 4AC14, 4AC16, 4AC18 Heat Pumps: 4SHP13, 4SHP14, 4SHP16, 4SHP18, 4HP13, 4HP14, 4HP16, 4HP18 Gas Furnaces: FPBB, A97, A96, A95, A93, A80, 92G, 95G1, 80G Oil Furnace: L83UF, L83BR, L83BF, L83HR, L83HF, L85UF, L85BR, L85BF, L85HR, L85HR Electric Furnace: EFC, EFV Evaporator Coils: EC, EU, EH, EM Air handlers: BCS2, BCS3, BCE3 Package Equipment: 4PCE13, 4PCE15, 4PGE13, 4PGE15, 4PHP13, 4PHP15, RGE13, RPGE13, RHP13, RPHP13, RCE13, RPCE13 Unit Heaters: LF24, (30,000 to 75,000 Btuh units)
PARTS and COMPRESSOR COVERAGE
The covered equipment and covered parts and compressor are warranted by Allied Air for a period of five (5) years from the date of the original installation, when installed in a residential application (which includes homes, duplexes, apartments and condominiums). The covered equipment and covered parts are warranted for a period of one (1) year and compressor is warranted for five (5) years by Allied Air from the date of the original installation, when installed in non-residential applications. If, during this period, a covered component fails because of a manufacturing defect, Allied Air will provide a free replacement part to the owner through a licensed service contractor utilizing an Allied Air distributor. You must pay shipping charges and all other costs of warranty service. Allied Air will not pay labor involved in diagnostic calls or in removing, repairing, servicing or replacing parts. Such cost may be covered by a separate warranty provided by the installer.
HEAT EXCHANGER EXTENDED COVERAGE
All covered heat exchangers are warranted by Allied Air for a period of twenty (20) years from the date of original installation in a residential application. Heat exchangers in all non-residential applications are warranted for a period of ten (10) years.
NOTE: : In the event that a component covered by this warranty is no longer available, Allied, at its option, through a established Allied distributor, will provide a free suitable substitute component or will allow a credit toward the purchase of an equivalent new Allied Air product (at the current suggested distributor's cost). If the date of original installation cannot be verified, the warranty period will be deemed to begin six (6) months after the date of manufacture. The LF24 unit heaters are not eligible for the extended warranty coverage.
EXCLUDED COMPONENTS
The following components are not covered by this warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts, wiring, fuses, oil nozzles, unit accessories and any parts not affecting unit operation.
CARE OF EQUIPMENT
Your new Allied Air unit must be properly installed, operated and maintained in accordance with the unit installation, operation and maintenance instructions provided with each Allied Air unit. Failure to
provide maintenance per Allied Air instructions will void this warranty.
WARRANTY PROCEDURE
When service or warranty parts are required: 1. Call your local licensed service dealer or contractor 2. If the installing dealer is unable to provide warranty service, check online at www.alliedair.com. 3. Be prepared to furnish the following information: a. Complete model and serial number b. Proof of required periodic maintenance, installation date and location. c. An accurate description of the problem
WARRANTY LIMITATIONS
1. Products purchased over the internet or through other electronic means must be installed by a qualified installer and the installation must adhere to the Quality Installation protocols of the Air Conditioning Contractors of America (ACCA), and these products must be registered with the manufacturer within 60 days of installation for the warranty to be in place.
2. This warranty is void if the covered equipment is removed from the original installation site. 3. This warranty does not cover damage or defect resulting from:
a. Flood, wind, fire, lightning, mold, or installation and operation in a corrosive atmosphere, or otherwise in contact with corrosive materials (chorine, fluorine, salt, recycled waste water, urine, fertilizers, or other damaging substances or chemicals).Accident, or neglect or unreasonable use or operation of the equipment including operation of electrical equipment at voltages other than the range specified on the unit nameplate (includes damages caused by brownouts).
b. Modification, change or alteration of the equipment, except as directed in writing by Allied Air. c. Operation with system components (indoor unit, outdoor unit and refrigerant control devices) which are not an ARI match or meet the specifications recommended by Allied Air. d. Operation of furnaces with return air temperatures of less than 60ºF (16ºC) or operation of a furnace field installed downstream from a cooling coil.
e. Use of contaminated or refrigerant not compatible with the unit.
The installation of replacement parts under the terms of this warranty does not extend the original warranty period.
Allied Air makes no express warranties other than the warranty specified above. All implied warranties, including the implied warranties of merchantability and fitness for a particular purpose, are excluded to the extent to a period legally permissible. Should such exclusion or limitation of the warranty be unenforceable, such implied warranties are in any event limited to a period of one (1) year. Liability for incidental and consequential damages is excluded. Some states do not allow limitation of incidental damages, so the limitations or exclusions may not apply to you. Allied Air will not pay electricity or fuel costs, or increases in electricity or fuel costs, for any reason whatsoever, including additional or unusual use of supplemental electric heat. This warranty does not cover lodging expenses or labor charges.
Allied Air shall not be liable for any default or delay in performance under this warranty caused by any contingency beyond its control.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
NOTE TO CUSTOMER Please complete information below and retain this warranty for your records and future reference.
Outside Unit Model Number: __________________________________________ Serial Number: _______________________________ Installed Date: _______________
Furnace / Air Handler: _____________________________ ______________ Serial Number: _______________________________ Installed Date: _______________
Indoor Coil Model Number: ___________________________________________ Serial Number: _______________________________ Installed Dare: _______________
Installing Company Name: __________________________________ _________________________________________ Phone: _________________________________
Installing Company Address: ____________________________________________ State/Province: _______________________________ Zip/Postal Code: ____________

215 Metropolitan Drive, West Columbia, SC 29170

© 2008 Allied Air Enterprises

Litho U.S.A.

FORM W-2008-2 (4/17/2013)

8


Acrobat Distiller 10.0.0 (Windows)

Search Any Device: