2080-SG001A-EN-P Micro800 Programmable Controllers Selection Guide

Bulletin 2080

Bulletin, 2080

Rockwell Automation

Elit.ee View guide user manual

Download link

2085-IF8 Analog Input Module Micro850, 8-ch., drawn 110mA 5VDC, TS35^panel mount, Allen-Bradley  Elit GlobalStore™ - elektritarvikud, automaatika, kontrollerid, IT komponendid

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 64 Pages, 656.33KB

Document DEVICE REPORTALBR2085ECR Spec
Micro800 Programmable Controller Family
Bulletin 2080 Selection Guide

Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

SHOCK HAZARD Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous temperatures.

Allen-Bradley, Rockwell Automation, Micro800, Micro810, Micro820, Micro830, Micro850, Connected Components Workbench, FactoryTalk, PowerFlex, CompactBlock, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Select a Micro800 Controller

Micro800TM controllers are designed for low-cost, standalone machines. These economical small-size PLCs are available in different form factors based on the number of I/O points embedded in the base, with a range of features intended to address different requirements. The Micro800 family shares programming environment, accessories and plug-ins that allow machine builders to personalize the controller for specific capabilities.
Micro810TM controllers function as a smart relay with high current relay outputs, but with the programming capabilities of a micro PLC. The Micro810 controllers come in a 12-point form factor.
Micro820TM controllers are specifically designed for smaller standalone machines and remote automation projects. It has embedded Ethernet and serial ports and a microSDTM slot for datalogging and recipe management. These controllers come as 20-point form factors that can accommodate up to two plug-in modules. It also supports the Micro800 Remote LCD (2080-REMLCD) module to allow easier configuration of such settings as IP address and functions as a simple IP65 text display.

1

Publication 2080-SG001D-EN-P - December 2013

2 Micro800 Programmable Controller Family Selection Guide

Micro830TM controllers are designed for standalone machine control applications. They have flexible communications and I/O capabilities with up to five plug-ins. They come as a 10-, 16-, 24-, or 48-point form factors.
Micro850TM expandable controllers are designed for applications that require more digital and analog I/O or higher performance analog I/O. They can support up to four expansion I/O. Micro850 controllers include additional communication connection options through an embedded 10/100 Base-T Ethernet port.
Several Micro830 and Micro850 controllers support basic positioning through embedded pulse train outputs (PTO). These controllers also allow you to configure up to six high speed counters (HSC), and choose from nine HSC operation modes. HSC is supported on all Micro830 and Micro850 catalogs, except on 2080-LCxx-xxAWB. PTO is only supported on Micro830 and Micro850 catalog numbers that end in BB or VB.
This selection guide serves to help you identify the right controller, plug-ins, expansion I/O, and accessories, based on your requirements.

Choose a Micro800 Controller 1
Select a Micro800 controller (go to page 3)

2 Select a Micro810

3

controller (go to page 9)

Select a Micro820 controller (go to page

Select a Micro830 controller (go to page 19)
Select a Micro850 controller (go to page 29)

4
Select Micro800 plug-ins and accessories (go to page 51)

Select Micro850 expansion I/O (go to page 41)

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 3

Micro800 Controllers Comparison

Features

Attribute

Micro810

Micro820

Micro830

Micro850

12-point

20-point

10-point 16-point 24-point 48-point 24-point 48-point

Communication ports, embedded

USB 2.0 (with USB adapter)

10/100 Base T Ethernet port (RJ-45)
RS232/RS485 non-isolated combo serial

USB 2.0 (non-isolated) RS232/RS485 non-isolated combo serial

USB 2.0 (non-isolated)
RS232/RS485 non-isolated combo serial
10/100 Base T Ethernet port (RJ-45)

Embedded digital I/O

12

19

10

16

24

48

24

48

points(1)

Base analog I/O channels

Four 24V DC digital inputs are shared as 0...10V analog inputs (DC input models only)

One 0...10V analog output
Four 24V DC digital inputs can be configured as 0...10V analog inputs (DC input models only) and via plug-in modules

Via plug-in modules

Via plug-in modules and expansion I/O

Number of plug-in modules 0

2

2

2

3

5

3

5

Maximum digital I/O(2)

12

35

26

32

48

88

132

Types of accessories or plug-ins supported

· LCD display with backup memory module
· USB adapter

· Micro800 Remote LCD (2080-REMLCD)
· All-plug-in modules except 2080-MEMBAKRTC (see page 51)

All plug-in modules (see page 51)

Expansion I/O supported --

--

--

All expansion I/O modules (see page 41)

Power supply

Embedded 120/240V Base unit has embedded 24V DC power supply, optional external 120/240V AC power AC and 12/24V DC supply available options

Basic instruction speed

2.5 s per basic instruction

0.30 s per basic instruction

Minimum scan/cycle time(3)

<0.25 ms

<4 ms

<0.25 ms

Software

Connected Components Workbench

(1) See Number and Types of Inputs/Outputs for Micro810, Micro820, Micro830, and Micro850 Catalogs on page 6. (2) For Micro820 and Micro830 controllers, the number of maximum digital I/O assumes 8-point digital I/O plug-ins (for example, 2080-IQ4OB4) are used on all available
plug-in slots. For Micro850 controllers, the maximum number of digital I/O supported between the base, plug-ins, and expansion I/O is 132. (3) Including reading and writing I/O, program execution, and communications overhead.

Publication 2080-SG001D-EN-P - December 2013

4 Micro800 Programmable Controller Family Selection Guide

Micro800 Controller Programming Comparison (with Connected Components Workbench)

Attribute

Micro810 12-point

Micro820 20-point

Micro830 10/16-point

Micro830 24-point

Micro830 Micro850 Micro850 48-point 24-point 48-point

Program steps(1)

2 K

10 K

4 K

10 K

10 K

10 K

10 K

Data bytes

2 KB

20 KB

8 KB

20 KB

20 KB

20 KB

20 KB

IEC 61131-3 languages

Ladder diagram, function block diagram, structured text

User defined function blocks Yes

Floating point

32-bit and 64-bit

PID Loop Control

Yes (number limited only by memory)

Embedded serial port protocols None

Modbus RTU Master/Slave, ASCII/Binary, CIP Serial

(1) Estimated Program and Data size are "typical" ­ program steps and variables are created dynamically. 1 Program Step = 12 data bytes. The number of bytes per instruction can vary greatly from program to program and from programming language to programming language.

Micro800 Communication Options

Controller
Micro810 Micro820 Micro830 Micro850

USB programming port Embedded Serial Port, Serial Port Plug-In

CIP Serial

Modbus RTU ASCII/Binary

Yes (with adapter)

No

Yes (with 2080-REMLCD) Yes

Master/Slave

Yes

Yes

Yes

Master/Slave

Yes

Yes

Yes

Master/Slave

Yes

Embedded Ethernet

EtherNet/IP

Modbus TCP

Yes

Yes

No

No

Yes

Yes

Micro800 Controllers Analog I/O and TC/RTD Comparison

Attribute

Micro810

Micro820

Micro800 (with plug-ins)

Micro850 (with expansion I/O)

Performance level

LOW

LOW

MEDIUM

HIGH

Isolation to controller

None

(increased noise immunity)

None

None

Yes

Resolution and Nominal Accuracy

Analog Input: 10-bit, 5% (2% with calibration)

Analog I/O: 12-bit, 5% (2% with calibration)

Analog I/O: 12-bit, 1% TC/RTD: ±1 °C CJC for TC: ±1.2 °C

Analog Input: 14-bit input, ±0.1% Analog Output: 12-bit output, 0.133%, current, 0.425% voltage TC: ±0.5 ... ±3.0 °C RTD: ±0.2 ... ±0.6 °C

Input update rate and filtering

Update rate only dependent on Update rate only dependent 200 ms/ch, 50/60 Hz program scan, limited filtering on program scan, limited filtering
filtering

8 ms all channels with or without 50/60 Hz filtering

Recommended maximum 10 m shielded cable length(1)

100 m

(1) These numbers are guidelines only. Maximum cable length is dependent on the application and other factors such as cable type, installation, required accuracy, sensor, and so on.

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 5

Micro800 Power Requirements(1)

Controller/Module

Power Requirement

Micro810 12-point (with or without LCD)

3 W (5V A for AC module)

Micro820 20-point(2) (without plug-ins, max)

5.62 W

Micro830 and Micro850

(without plug-in/expansion I/O)

10/16-point

5W

24-point

8W

48-point

11 W

Plug-in modules, each

1.44 W

Expansion I/O (system bus power consumption)

2085-IQ16 ­ 0.85 W 2085-IQ32T ­ 0.95 W 2085-IA8 ­ 0.75 W 2085-IM8 ­ 0.75 W 2085-OA8 ­ 0.90 W 2085-OB16 ­ 1.00 W 2085-OV16 ­ 1.00 W 2085-OW8 ­ 1.80 W 2085-OW16 ­ 3.20 W 2085-IF4 ­ 1.70 W 2085-IF8 ­ 1.75 W 2085-OF4 ­ 3.70 W 2085-IRT4 ­ 2.00 W

(1) When setting up a Micro800 system, verify that total power consumption of the controller, plug-in and expansion I/O does not exceed the output power capacity of the power supply used. See External Power Supply (2080-PS120-240VAC) on page 59 for power supply specifications.
(2) Micro820 controllers require a maximum of 8.5 W with plug-ins.

Publication 2080-SG001D-EN-P - December 2013

6 Micro800 Programmable Controller Family Selection Guide

Number and Types of Inputs/Outputs

Number and Types of Inputs/Outputs for Micro810, Micro820, Micro830, and Micro850 Catalogs

Controller Catalogs Family

Inputs
120V 120 / AC 240V
AC

24V DC/ V AC

Outputs

12V Relay 24V DC 24V

DC

Source DC

Sink

Micro810 2080-LC10-12QWB ­

­

8

­4

­

­

2080-LC10-12AWA ­

8

­

­4

­

­

2080-LC10-12QBB ­

­

8

­

4

­

2080-LC10-12DWD ­

­

­

84

­

­

Micro820 2080-LC20-20QBB ­

­

12

­

7

­

2080-LC20-20QWB ­

­

12

­7

­

­

2080-LC20-20AWB 8

­

4

­7

­

­

2080-LC20-20QBBR ­

­

12

­­

7

­

2080-LC20-20QWBR ­

­

12

­7

­

­

2080-LC20-20AWBR 8

­

4

­7

­

­

Micro830 2080-LC30-10QWB ­

­

6

­4

­

­

2080-LC30-10QVB ­

­

6

­­

­

4

2080-LC30-16AWB 10

­

­

­6

­

­

2080-LC30-16QWB ­

­

10

­6

­

­

2080-LC30-16QVB ­

­

10

­­

­

6

2080-LC30-24QWB ­

­

14

­ 10

­

­

2080-LC30-24QVB ­

­

14

­­

­

10

2080-LC30-24QBB ­

­

14

­­

10

­

2080-LC30-48AWB 28

­

­

­ 20

­

­

2080-LC30-48QWB ­

­

28

­ 20

­

­

2080-LC30-48QVB ­

­

28

­­

­

20

2080-LC30-48QBB ­

­

28

­­

20

­

Micro850 2080-LC50-24AWB 14

­

­

­ 10

­

­

2080-LC50-24QBB ­

­

14

­­

10

­

2080-LC50-24QVB ­

­

14

­­

­

10

2080-LC50-24QWB ­

­

14

­ 10

­

­

2080-LC50-48AWB 28

­

­

­ 20

­

­

2080-LC50-48QWB ­

­

28

­ 20

­

­

2080-LC50-48QBB ­

­

28

­­

20

­

2080-LC50-48QVB ­

­

28

­­

­

20

(1) For Micro830 and Micro850, you need firmware revision 6.011 or later to use PWM output.

(2) Maximum number of embedded HSC supported.

Analog Out 0...10V DC
­ ­ ­ ­ 1 1 1 1 1 1 ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­

Analog In 0...10V (shared with DC In)
4 ­ 4 4 4 4 4 4 4 4 ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­

PTO/PWM Support(1)
­ ­ ­ ­ 1 (PWM) ­ ­ 1 (PWM) ­ ­ ­ 1 (PTO/PWM) ­ ­ 1 (PTO/PWM)
2 (PTO/PWM) 2 (PTO/PWM) ­ ­ 3 (PTO/PWM) 3 (PTO/PWM)
2 (PTO/PWM) 2 (PTO/PWM)
­ ­ 3 (PTO/PWM) 3 (PTO/PWM)

Embedded HSC Support(2)
­ ­ ­ ­ ­ ­ ­ ­ ­ ­ 2 2 ­ 2 2 4 4 4 ­ 6 6 6
4 4 4 ­ 6 6 6

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 7

Micro800 Catalog Number Details

2080 - LC 30- 24 Q V B
Bulletin Number Base Unit
LC10 = Micro810 LC20 = Micro820 LC30 = Micro830 LC50 = Micro850
Number of I/O 10, 12, 16, 20, 24, 48
(1) Available for Micro810 only.

Power Supply A(1) = 120/240V AC B = 24V DC D(1) = 12V DC
Output Type B = 24V DC Source V = 24V DC Sink W = Relay
Input Type A = 110V AC or 110/220V AC Q = 24V AC/DC D(1) = 12V DC

Connected Components Workbench Software

Connected Components WorkbenchTM is the programming and configuration software environment for the Micro800 controllers and our Connected Components products offering. It simplifies setup and usage, enabling applications ranging from simple Smart Relay up to Standalone Machine control.
Visit the website for the most up-to-date product information, downloads and tools: http://ab.rockwellautomation.com/Programmable-Controllers/Connected-Co mponents-Workbench-Software.

Attribute Delivery
Packaging options
Features

Standard Edition
Basic Download Connected Components Workbench Standard Edition for FREE at http://ab.rockwellautomation.com/Programmable-Controllers/Connected-Components-Workbench-Software. Available on DVD, orderable from Connected Components Workbench web page at http://ab.rockwellautomation.com/Programmable-Controllers/Connected-Components-Workbench-Software. · LD, FBD and ST editors · user-defined function blocks · No activation needed · Optional registration during installation (for product updates and notices)

Publication 2080-SG001D-EN-P - December 2013

8 Micro800 Programmable Controller Family Selection Guide
Developer Edition
The Developer Edition offers the following additional programming features: User-defined Structures
· You can combine different data types to create structures and then assign them to user-defined variables.
· Structures are useful when you want a single variable to hold several related pieces of information. For example, you might want to define a structure to keep temperature ranges and alarm levels for a device rather than creating multiple variables.
Spy Lists You can define spy lists to monitor changes in variables and function block instances in Connected Components Workbench programs. The Developer Edition installs the following additional software:
· FactoryTalk® Activation Manager v3.60.00 (CPR 9 SR 6) · FactoryTalk Diagnostics v2.60.00 (CPR 9 SR 6) · Microsoft Help Viewer 1.1 Note: The Developer Edition requires an activation key. See the FactoryTalk Activation help for additional information on activating Rockwell Automation software products.
Publication 2080-SG001D-EN-P - December 2013

Select a Micro810 Controller

As the smallest of the Micro800 family, the Micro810 controller is available in a 12-point version, with two 8 A and two 4 A outputs that eliminate the need for external relays. The Micro810 features embedded smart relay function blocks that can be configured from a 1.5" LCD and keypad. The function blocks include Delay OFF/ON Timer, Time of Day, Time of Week and Time of Year for applications requiring a programmable timer and lighting control. Programming can also be done through a program download via USB programming port, using Connected Components Workbench Software.
To help you select a Micro810 controller, consult the specifications for each catalog in the next section.

Number and Types of Inputs/Outputs

Catalog Number

Power

2080-LC10-12QWB 2080-LC10-12AWA 2080-LC10-12QBB 2080-LC10-12DWD

24V DC 120...240V AC 12...24V DC 12V DC

Inputs 120V AC
8

240V AC

Outputs

Analog In 0...10V

12...24V DC /V AC Relay 24 V DC SRC (shared with DC In)

8

4

4

4

8

4

4

8

4

4

9

Publication 2080-SG001D-EN-P - December 2013

10 Micro800 Programmable Controller Family Selection Guide

Specifications(1)

Attribute

2080-LC10-12AWA

2080-LC10-12QWB

2080-LC10-12DWD 2080-LC10-12QBB

Number of I/O

8 Input (4 digital, 4 analog/digital, configurable) 4 Output

Dimensions HxWxD

91 x 75 x 59 mm (3.58 x 2.95 x 2.32 in.)

Supply voltage range

85...263V DC

20.4...26.4V DC

10.8V...13.2V DC

11.4V..26.4V DC

Supply frequency range

47...63 Hz

­

(AC supply)

Voltage range

100...240V AC, 50/60 Hz 24V DC Class 2

12V DC Class 2

12/24V DC Class 2

Power consumption

5V A

3 W

I/O rating

Input: 120...240V AC

Input: 24V DC, 8 mA

Input: 12V DC, 8 mA Input: 24V DC, 8 mA

Output: Relay 00 & 01: 8 A @ 240V AC, B300, R300, General Use Relay 02 & 03: 4 A @ 240V AC, C300, R150, General Use

Output: 24V DC 1A, 25 °C, 24V DC 0.5A 55 °C

Operating temperature

0...55 °C (32...131 °F)

Shipping weight, approx.

0.203 kg (0.448 lb)

Wire size

0.32...2.1 mm² (22...14 AWG) solid copper wire or 0.32...1.3 mm² (22...16 AWG) stranded copper wire rated @ 90 °C (194 °F ) insulation max.

Wiring category

2 ­ on signal ports 2 ­ on power ports

Wiring torque

1.085 Nm (8 lb-in.)

Wire type

use Copper Conductors only

Fuse, type

Rated 250V 3.15 A-RADIAL

Enclosure type rating

Meets IP20

North American temp code T5

Insulation stripping length 7 mm (0.28 in.)

Isolation voltage

250V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs. Type tested for 60 s 3250V DC, I/O to Aux and Network, Inputs to Outputs

250V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, Inputs to Aux and Network, 3250V DC Outputs to Aux and Network, Inputs to Outputs

50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to Outputs

AC input filter setting

16 ms for all embedded inputs (In Connected Components Workbench, go to the Embedded I/O configuration window to re-configure the filter setting for each input group)

(1) See the Micro810 User Manual, publication 2080-UM001, for more Micro810 controller specifications.

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 11

Environmental

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0...55 °C (32...131 °F)

Temperature, surrounding air, max

55 °C (131 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock): -40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g (DIN Rail Mounted) 30 g (Panel Mounted)

Emissions

CISPR 11 Group 1, Class A

ESD immunity

IEC 61000-4-2: 4 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports ±2 kV line-earth(CM) on shielded ports

Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Voltage variation

IEC 61000-4-11: 60% dip for 5 and 50 periods on AC supply ports 30% dip for 0.5 period at 0° and 180° on AC supply ports 100% dip for 0.5 period at 0° and 180° on AC supply ports ±10% fluctuations for 15 min on AC supply ports > 95% interruptions for 250 periods on AC supply ports

Publication 2080-SG001D-EN-P - December 2013

12 Micro800 Programmable Controller Family Selection Guide

Certifications

Certification (when Value product is marked)(1)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and other certification details.

For relay life chart, see the Specifications section of the Micro810 User Manual, publication 2080-UM001.

Publication 2080-SG001D-EN-P - December 2013

Select a Micro820 Controller

As one of the smaller controllers in the Micro800 family, the Micro820 controller comes as a 20-point form factor, with six catalogs available for selection. The Micro820 controller is designed for smaller standalone machines and remote automation projects.
It has the following features: · Two plug-in module slots · microSD card slot for project backup and restore, datalogging and recipe · Embedded 10/100 Base-t Ethernet port(RJ-45) · Support for Remote LCD module (2080-REMLCD) for configuration · Embedded non-isolated RS232/RS485 combo serial port · Modbus RTU protocol (serial port) · Modbus TCP support · EtherNet/IP support · CIP Serial support
To help you select a Micro820 controller, consult the specifications for each catalog in the next section.

13

Publication 2080-SG001D-EN-P - December 2013

14 Micro800 Programmable Controller Family Selection Guide

Number and Types of Inputs/Outputs for Micro820 Controllers

Controller Catalogs Family

Inputs 120V AC

120 /240V AC

24V DC

Outputs
Relay 24V DC Source

24V DC Sink

Analog Out 0...10V DC

Analog In 0...10V (shared with DC In)

PWM Support

Micro820 2080-LC20-20QBB ­

­

12

7

­

1

4

1

2080-LC20-20QWB ­

­

12

7

­

­

1

4

­

2080-LC20-20AWB 8

­

4

7

­

­

1

4

­

2080-LC20-20QBBR ­

­

12

­

7

­

1

4

1

2080-LC20-20QWBR ­

­

12

7

­

­

1

4

­

2080-LC20-20AWBR 8

­

4

7

­

1

4

­

General Specifications Attribute Number of I/O Dimension, HxWxD Shipping weight, approx. Wire size
Wiring category(1) Wire type

Specifications

2080-LC20-20AWB(R) 12 inputs, 8 outputs 90 x 104 x 75 mm (3.54 x 4.09 x 2.95 in.) 0.38 kg (0.83 lb) For fixed terminal blocks:

2080-LC20-20QBB(R)

2080-LC20-20QWB(R)

Solid Stranded

Min 0.14 mm2 (26 AWG) 0.14 mm2 (26 AWG)

Max
2.5 mm2 (14 AWG) rated @ 90 °C (194 °F) insulation 1.5 mm2 (16 AWG) max

For removable terminal blocks:

Solid and Stranded

Min 0.2 mm2 (24 AWG)

Max 2.5 mm2 (14 AWG)

rated @ 90 °C (194 °F) insulation max

For RS232/RS485 serial port:

Solid Stranded

Min 0.14 mm2 (26 AWG) 0.14 mm2 (26 AWG)

Max 1.5 mm2 (16 AWG) 1.0 mm2 (18 AWG)

rated @ 90 °C (194 °F) insulation max

2 ­ on signal ports 2 ­ on power ports 2 ­ on communication ports
Use copper conductors or shielded cables

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 15

General Specifications Attribute Terminal screw torque

2080-LC20-20AWB(R)

2080-LC20-20QBB(R)

2080-LC20-20QWB(R)

For removable and fixed terminal blocks:
0.5...0.6 Nm (4.4...5.3 lb-in.) using a 0.6 x 3.5 mm flat-blade screwdriver. Note: Use a handheld screwdriver to hold down the screws at the side.

For RS232/RS485 serial port: 0.22...0.25 Nm (1.95...2.21 lb-in.) using 0.4 x 2.5 x 80 mm 2-component grip with non-slip grip screwdriver.

Input circuit type

24V DC sink/source (standard) ­ for 2080-LC20-20QWB(R), 2080-LC20-20QBB(R) 120V AC ­ for 2080-LC20-20AWB(R) for Inputs 4...11 only

Output circuit type

Relay

24V DC source (standard and high-speed)

Relay

Power input

24V DC

Power consumption

5.62 W (without plug-ins, max)...8.5 W (with plug-ins, max)

Power dissipation

6W

Power supply voltage range

20.4...26.4 V DC, Class 2

Auxiliary power supply output for

10V

thermistor

I/O rating

Input: 120V AC 16 mA Output: 2 A, 240 V AC 2A, 24V DC

Input: 24V DC, 8.8 mA

Output:24V DC,1Aperpoint

(Surrounding air temperature

30°C)

24 V DC, 0.3

A per point (Surrounding air

temperature 65 °C)

Input: 24V DC, 8.8 mA Output: 2 A, 240 V AC, 2A, 24V DC

Isolation voltage

250V (continuous), Reinforced Insulation Type, Output to Aux and Network, Inputs to Outputs. 150V (continuous), Reinforced Insulation Type, Input to Aux and Network. Type tested for 60 s @ 3250 V DC Output to Aux and Network, Inputs to Outputs.
Type tested for 60 s @ 1950 V DC Input to Aux and Network.

50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs. Type tested for 60 s @ 720 V DC, I/O to Aux and Network, Inputs to Outputs.

250V (continuous), Reinforced Insulation Type, Output to Aux and Network, Inputs to Outputs. 50V (continuous), Reinforced Insulation Type, Input to Aux and Network. Type tested for 60 s @ 720 V DC, Inputs to Aux and Network, 3250 V DC Outputs to Aux and Network, Inputs to Outputs.

Pilot duty rating

C300, R150

­

C300, R150

Insulation stripping length

· 7 mm for the removable and fixed terminal blocks · 5 mm for the RS232/RS485 serial port

Enclosure type rating

Meets IP20

North American temp code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 2080-SG001D-EN-P - December 2013

16 Micro800 Programmable Controller Family Selection Guide

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)

Temperature, surrounding air, max

65 °C (149 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): DIN mount: 25 g PANEL mount: 45 g

Emissions

CISPR 11 Group 1, Class A

ESD immunity

IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports ±1 kV @ 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports ±1 kV line-earth(CM) on communication ports

Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 17

Certifications

Certification (when product is marked)(1)
c-UL-us

Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:

Article 58-2 of Radio Waves Act, Clause 3

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification for Declaration of Conformity, Certificates, and other certification details.

For more information, see the Micro820 Programmable Controllers User Manual, publication 2080-UM005.

Publication 2080-SG001D-EN-P - December 2013

18 Micro800 Programmable Controller Family Selection Guide
Notes:
Publication 2080-SG001D-EN-P - December 2013

Select a Micro830 Controller
The Micro830 controller allows integration of as many as five plug-in modules. The plug-in modules enable machine builders to personalize the controllers to increase functionality. Most models offer removable terminal blocks and simplified communication via serial port. The controllers include:
· up to six embedded High-Speed Counter inputs (HSC)(1) · 100 kHz speed HSC available on 24V DC models · up to three embedded Pulse Train Outputs (PTO) for basic positioning(2) · High speed input interrupts · Modbus RTU protocol (serial port) · CIP Serial to allow tighter integration with PanelView Component · Embedded USB programming and serial port (RS232/RS485) · Plug-in slots to customize according to needs To help you select a Micro830 controller, check out the specifications for each catalog in the next section.
(1) Embedded HSC is supported on all Micro830 catalog numbers, except on 2080-LC30-xxAWB. (2) PTO is supported on Micro830 catalog numbers ending in BB or VB only.
19Publication 2080-SG001D-EN-P - December 2013

20 Micro800 Programmable Controller Selection Guide

Inputs and Outputs

Micro830 Controllers ­ Number and Type of Inputs/Outputs

Catalog Number

Inputs

120V AC

2080-LC30-10QWB

2080-LC30-10QVB

2080-LC30-16AWB

10

2080-LC30-16QWB

2080-LC30-16QVB

2080-LC30-24QBB

2080-LC30-24QVB

2080-LC30-24QWB

2080-LC30-48AWB

28

2080-LC30-48QBB

2080-LC30-48QVB

2080-LC30-48QWB

(1) Maximum number of HSC supported.

Outputs

24V DC/V AC Relay

6

4

6

6

10

6

10

14

14

14

10

20

28

28

28

20

24V Sink 4 6 10
20

PTO/PWM Support 24V Source
1

HSC Support(1)
2 2

2

1

2

10

2

4

2

4

4

20

3

6

3

6

6

Micro830 Controllers General Features

Attribute

10-point 2080-LC30-10QWB 2080-LC30-10QVB

16-point 2080-LC30-16AWB 2080-LC30-16QWB 2080-LC30-16QVB

24-point 2080-LC30-24QWB 2080-LC30-24QVB 2080-LC30-24QBB

48-point 2080-LC30-48AWB 2080-LC30-48QWB 2080-LC30-48QVB 2080-LC30-48QBB

Number of I/O

10 (6 inputs, 4 outputs) 16 (10 inputs, 6 outputs) 24 (14 inputs, 10 outputs) 48 (28 inputs, 20 outputs)

Dimensions, HxWxD

90 x 100 x 80 mm (3.54 x 3.94 x 3.15 in.)

90 x 100 x 80 mm (3.54 x 3.94 x 3.15 in.)

90 x 150 x 80 mm (3.54 x 5.91 x 3.15 in.)

90 x 230 x 80 mm (3.54 x 9.06 x 3.15 in.)

Shipping weight, approx.

0.302 kg (0.666 lb)

0.302 kg (0.666 lb)

0.423 kg (0.933 lb)

0.725 kg (1.60 lb)

Operating temperature Wire size
Wiring category(1)

-20...65 °C (-4...149 °F) 0.14...2.5 mm2 (26...14 AWG) solid copper wire or 0.14...1.5 mm2 (26...16 AWG) stranded copper wire rated @ 90 °C (194 °F) insulation max
2 ­ on signal ports; 2 ­ on power ports

0.2...2.5 mm2 (24...14 AWG) solid copper wire or 0.2...2.5 mm2 (24...14 AWG) stranded copper wire rated @ 90 °C (194 °F) insulation max

Wire type

Use copper conductors only

Terminal screw torque, max 0.6 Nm (4.4 lb-in.) (using a 2.5 mm (0.10 in.) flat-blade screwdriver)

Power consumption

7.88 W

12.32 W

18.2 W

Power supply voltage range 20.4...26.4V DC Class 2

Insulation stripping length 7 mm (0.28 in.)

Enclosure type rating

Meets IP20

North American temp code T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Selection Guide 21
Micro830 Controllers 10- and 16-Point Controllers

General Specifications ­ 10-point controllers

Attribute

2080-LC30-10QWB

2080-LC30-10QVB

Input circuit type

12/24V sink/source (standard) 24V sink/source (high-speed)

Output circuit type

Relay

24V DC sink transistor standard and high-speed

Event input interrupt support Yes

I/O rating

Input 24V DC, 8.8 mA Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA Output 2 A, 24V DC, 1 A per point (Surrounding air temperature 30 °C) 24V DC, 0.3 A per point (Surrounding air temperature 65 °C)

Isolation voltage

250V (continuous), Reinforced Insulation Type, Outputs to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, Inputs to Aux and Network, 3250V DC Outputs to Aux and Network, Inputs to Outputs

50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to Outputs

Pilot duty rating

C300, R150

--

General Specifications ­ 16-point controllers

Attribute Input circuit type

2080-LC30-16AWB 120V AC

Output circuit type

Relay

Event input interrupt

Yes

support

2080-LC30-16QWB
12/24V sink/source (standard) 24V sink/source (high-speed)

2080-LC30-16QVB
12/24V DC sink transistor standard and high-speed

Publication 2080-SG001D-EN-P - December 2013

22 Micro800 Programmable Controller Selection Guide

General Specifications ­ 16-point controllers

Attribute I/O rating Isolation voltage
Pilot duty rating

2080-LC30-16AWB

2080-LC30-16QWB

2080-LC30-16QVB

Input 120V AC, 16 mA Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA Output 24V DC, 1 A per point (Surrounding air temperature 30 °C) 24 V DC, 0.3 A per point (Surrounding air temperature 65 °C)

250V (continuous), Reinforced Insulation Type, Outputs to Aux and Network, Inputs to Outputs
2080-LC30-16AWB: Type tested for 60 s @ 3250V DC I/O to Aux and Network, Inputs to Outputs 2080-LC30-16QWB: Type tested for 60 s @ 720V DC, Inputs to Aux and Network, 3250V DC Outputs to Aux and Network, Inputs to Outputs

50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs Type tested for 60s @ 720V DC, I/O to Aux and Network, Inputs to Outputs

C300, R150

--

Environmental Specifications

Attribute Temperature, operating
Temperature, surrounding air, max Temperature, non-operating
Relative humidity Vibration Shock, operating Shock, non-operating Emissions ESD immunity Radiated RF immunity
EFT/B immunity Surge transient immunity

Value
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)
65 °C (149 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing
IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): DIN mount: 25 g PANEL mount: 45 g
CISPR 11 Group 1, Class A
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4: ±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports
IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Selection Guide 23

Environmental Specifications

Attribute Conducted RF immunity

Value
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Certifications

Certification (when Value product is marked)(1)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and other certification details.

Publication 2080-SG001D-EN-P - December 2013

24 Micro800 Programmable Controller Selection Guide
Micro830 24-Point Controllers

General Specifications ­ 24-point controllers

Attribute Input circuit type Output circuit type Event input interrupt support I/O rating
Isolation voltage
Pilot duty rating

2080-LC30-24QWB 24V DC sink/source standard and high-speed Relay
Yes

2080-LC30-24QVB
24V DC sink standard and high-speed

2080-LC30-24QBB
24V DC source standard and high-speed

Input 24V DC, 8.8 mA Output 2 A, 240 V AC, general use
250V (continuous), Reinforced Insulation Type, Outputs to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, Inputs to Aux and Network, 3250V DC Outputs to Aux and Network, Inputs to Outputs
C300, R150 (2080-LC30-24QWB only)

Input 24V DC, 8.8 mA Output 24V DC, Class 2, 1 A per point (Surrounding air temperature 30 °C) 24V DC, Class 2, 0.3 A per point (Surrounding air temperature 65 °C)
50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to Outputs
--

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)

Temperature, surrounding 65 °C (149 °F) air, max

Temperature, non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Selection Guide 25

Environmental Specifications

Attribute Vibration Shock, operating Shock, non-operating Emissions ESD immunity Radiated RF immunity
EFT/B immunity Surge transient immunity Conducted RF immunity

Value
IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): DIN mount: 25 g PANEL mount: 35 g
CISPR 11 Group 1, Class A
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4: ±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports
IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Certifications

Certification (when product is marked)(1) c-UL-us

Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and other certification details.

Publication 2080-SG001D-EN-P - December 2013

26 Micro800 Programmable Controller Selection Guide
Micro830 48-Point Controllers

General Specifications ­ 48-point controllers

Attribute

2080-LC30-48AWB

2080-LC30-48QWB

2080-LC30-48QVB

2080-LC30-48QBB

Input circuit type 120V AC

24V DC sink/source standard and high-speed

Output circuit type Relay

24V DC sink standard and high-speed

24V DC source standard and high-speed

Event input interrupt Yes, inputs 0...15 only support

I/O rating

Input 120V AC, 16 mA Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA Output 2 A, 240V AC, general use

Input 24V DC, 8.8 mA Output 24V DC, 1 A per point (Surrounding air temperature 30 °C) 24 V DC, 0.3 A per point (Surrounding air temperature 65 °C)

Pilot duty rating

C300, R150

­

Isolation voltage

250V (continuous), Reinforced Insulation Type, Outputs to Aux and Network, Inputs to Outputs Type tested for 60 s @ 3250V DC I/O to Aux and Network, Inputs to Outputs

250V (continuous), Reinforced Insulation Type, Outputs to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, Inputs to Aux and Network, 3250V DC Outputs to Aux and Network, Inputs to Outputs

50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to Outputs

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Selection Guide 27

Environmental Specifications

Attribute Temperature, operating
Temperature, surrounding air, max Temperature, non-operating
Relative humidity Vibration Shock, operating Shock, non-operating Emissions ESD immunity Radiated RF immunity
EFT/B immunity Surge transient immunity Conducted RF immunity

Value
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)
65 °C (149 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing
IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): DIN mount: 25 g PANEL mount: 35 g
CISPR 11 Group 1, Class A
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports
IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Publication 2080-SG001D-EN-P - December 2013

28 Micro800 Programmable Controller Selection Guide

Certifications Certification (when product is marked)(1) c-UL-us

Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and other certification details.

For relay life chart, see the Specifications section of the Micro830 and Micro850 User Manual, publication 2080-UM002.

Embedded Serial Port Cables
Embedded Serial Port Cable Selection Chart

Connectors 8-pin Mini DIN to 8-pin Mini DIN 8-pin Mini DIN to 8-pin Mini DIN

Length

Cat. No.

0.5 m (1.5 ft) 1761-CBL-AM00(1)

2 m (6.5 ft) 1761-CBL-HM02(1)

(1) Series C or later for Class 1 Div 2 applications.

Connectors 8-pin Mini DIN to 9-pin D Shell
8-pin Mini DIN to 9-pin D Shell
8-pin Mini DIN to 6-pin RS-485 terminal block

Length

Cat. No.

0.5 m (1.5 ft) 1761-CBL-AP00(1)

2 m (6.5 ft) 1761-CBL-PM02(1)

30 cm (11.8 in.)

1763-NC01 series A

Publication 2080-SG001D-EN-P - December 2013

Select a Micro850 Controller

A Micro850 controller with a power supply, plug-in modules, and four expansion I/O modules attached
Micro850 controllers are suitable for applications that require more digital and analog I/O or higher performance analog I/O. These controllers can support up to four expansion I/O. It comes in a 24-point and 48-point form factor with an embedded Ethernet port.
Micro850 controllers include: · Expansion I/O support · up to six embedded High-Speed Counter inputs (HSC)(1) · 100 kHz speed HSC available on 24V DC models · up to three embedded Pulse Train Outputs (PTO)(2) for basic positioning · High speed input interrupts · Modbus RTU protocol (serial port) · Modbus/TCP support · EtherNet/IP support · CIP Serial support · Embedded USB programming and serial port (RS232/485) · Embedded 10/100 Base-T Ethernet port (RJ45) · Plug-in slots to customize according to needs
To help you select a Micro850 controller, see the following specifications.

(1) Embedded HSC is supported on all Micro850 catalog numbers, except on 2080-LC50-xxAWB. (2) PTO is supported on Micro850 catalog numbers ending in BB or VB.

29

Publication 2080-SG001D-EN-P - December 2013

30 Micro800 Programmable Controller Family Selection Guide

Micro850 Controllers ­ Number and Types of Inputs and Outputs

Catalog Number Inputs

120V 24V AC DC/
V AC

2080-LC50-24AWB 14

2080-LC50-24QBB

14

2080-LC50-24QVB

14

2080-LC50-24QWB

14

2080-LC50-48AWB 28

2080-LC50-48QBB

28

2080-LC50-48QVB

28

2080-LC50-48QWB

28

(1) Maximum number of HSC supported.

Outputs Relay 24V
Sink
10
10 10 20
20 20

PTO/

PWM

24V

Support

Source

HSC Support(1)

10

2

4

2

4

4

20

3

6

3

6

6

Micro850 24-Point Controllers

General Specifications ­ 2080-LC50-24AWB, 2080-LC50-24QWB, 2080-LC50-24QVB, 2080-LC50-24QBB

Attribute Number of I/O Dimensions, HxWxD Shipping weight, approx.

2080-LC50-24AWB

2080-LC50-24QWB

24 (14 inputs, 10 outputs)

90 x 158 x 80 mm (3.54 x 6.22 x 3.15 in.)

0.423 kg (0.933 lb)

2080-LC50-24QVB

2080-LC50-24QBB

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 31

General Specifications ­ 2080-LC50-24AWB, 2080-LC50-24QWB, 2080-LC50-24QVB, 2080-LC50-24QBB

Attribute Wire size

2080-LC50-24AWB

2080-LC50-24QWB

Solid Stranded

Min 0.2 mm2 (24 AWG) 0.2 mm2 (24 AWG)

Max 2.5 mm2 (14 AWG) 2.5 mm2 (14 AWG)

2080-LC50-24QVB

2080-LC50-24QBB

rated @ 90 °C (194 °F) insulation max

Wiring category(1)

2 ­ on signal ports 2 ­ on power ports 2 ­ on communication ports

Wire type

Use copper conductors only

Terminal screw torque

0.6 Nm (4.4 lb-in.) max (using a 2.5 mm (0.10 in.) flat-blade screwdriver)

Input circuit type

120V AC

24V DC sink/source standard and high-speed

Output circuit type

Relay

24V DC sink standard and high-speed

24V DC source standard and high-speed

Power consumption

28 W

Power supply voltage range

20.4...26.4V DC Class 2

I/O rating

Input 120V AC 16 mA Output 2 A, 240 V AC, 24V DC

Input 24V, 8.8 mA Output 2 A, 240 V AC, 24V DC

Input 24V, 8.8 mA Output 24V DC, Class 2, 1 A per point (surrounding air temperature 30 °C) 24 V DC, Class 2, 0.3 A per point (surrounding air temperature 65 °C)

Isolation voltage

250V (continuous), Reinforced Insulation Type, Output to Aux and Network, Inputs to Outputs. Type tested for 60 s @ 3250V DC Output to Aux and Network, Inputs to Outputs
150V (continuous), Reinforced Insulation Type, Input to Aux and Network. Type tested for 60 s @ 1950V DC Input to Aux and Network

250V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs. Type tested for 60 s @ 3250V DC Output to Aux and Network, Inputs to Outputs.
50V (continuous), Reinforced Insulation Type, Input to Aux and Network Type tested for 60 s @ 720V DC, Inputs to Aux and Network.

50V (continuous), Reinforced Insulation Type, I/O to Aux and Network, Inputs to Outputs. Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to Outputs.

Pilot duty rating

C300, R150

--

Insulation stripping length

7 mm (0.28 in.)

Enclosure type rating

Meets IP20

North American temp code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 2080-SG001D-EN-P - December 2013

32 Micro800 Programmable Controller Family Selection Guide

DC Input Specifications ­2080-LC50-24QBB, 2080-LC50-24QVB, 2080-LC50-24QWB

Attribute
Number of Inputs Voltage category Input group to backplane isolation On-state voltage range
Off-state voltage, max Off-state current, max On-state current, min On-state current, nom On-state current, max Nominal impedance IEC input compatibility

High-Speed DC Input (Inputs 0...7)

Standard DC Input (Inputs 8 and higher)

8

6

24V sink/source

Verified by one of the following dielectric tests: 720V DC for 2 s 50V DC working voltage (IEC Class 2 reinforced insulation)

16.8...26.4V DC @ 65 °C (149 °F) 10...26.4V DC @ 65 °C (149°F) 16.8...30.0V DC @ 30 °C (86 °F) 10...30.0V DC @ 30 °C (86°F)

5V DC

1.5 mA

5.0 mA @ 16.8V DC, min

1.8 mA @ 10V DC, min

7.6 mA @ 24V DC, nom

6.15 mA @ 24V DC, nom

12.0 mA @ 30V DC, max

12.0 mA @ 30V DC, max

3 k

3.74 k

Type 3

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 33

AC Input Specifications ­ 2080-LC50-24AWB

Attribute Number of inputs On-state voltage, min On-state voltage, max On-state current, min On-state current, max Input frequency, nom Input frequency, min Input frequency, max Off-state voltage, max Off-state current, max Inrush current, max Inrush delay time constant max IEC input compatibility

Value 14 79V AC, min 132V AC, max 5 mA 16 mA 50/60 Hz 47 Hz 63 Hz, max 20V AC @ 120V AC 2.5 mA @ 120V AC 250 mA @ 120V AC 22 ms Type 3

Output Specifications

Attribute

2080-LC50-24QWB, 2080-LC50-24AWB 2080-LC50-24QVB, 2080-LC50-24QBB

Relay Output

Hi-Speed Output (Outputs 0...1)

Standard Output (Outputs 2 and higher)

Number of outputs

10

2

8

Output voltage, min

5V DC, 5V AC

10.8V DC

10V DC

Output voltage, max

125V DC, 265V AC

26.4V DC

26.4V DC

Load current, min

10 mA

Load current, continuous, max

Refer to Relay Contacts Ratings on page 33

100 mA (high-speed operation)

1.0 A @ 30 °C

1.0 A @ 30 °C

0.3 A @ 65 °C (standard operation)

0.3 A @ 65 °C (standard operation)

Surge current, per point

Refer to Relay Contacts Ratings on page 33 4.0 A for 10 ms every 1 s @ 30 °C; every 2 s @ 65 °C(1)

Current, per common, max 5 A

--

--

Turn on time/ Turn off time, max

10 ms

2.5 s

0.1 ms 1 ms

(1) Applies for general purpose operation only; does not apply for high-speed operation.

Relay Contacts Ratings

Maximum Volts
120V AC 240V AC 24V DC 125V DC

Amperes Make 15 A 7.5 A 1.0 A 0.22 A

Break 1.5 A 0.75 A

Amperes Continuous 2.0 A
1.0 A

Volt-Amperes Make Break 1800V A 180V A
28V A

Publication 2080-SG001D-EN-P - December 2013

34 Micro800 Programmable Controller Family Selection Guide

For relay life chart, see the Specifications section of the Micro830 and Micro850 User Manual, publication 2080-UM002.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)

Temperature, surrounding 65 °C (149 °F) air, max

Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): DIN mount: 25 g PANEL mount: 35 g

Emissions

CISPR 11 Group 1, Class A

ESD immunity

IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports ±1 kV @ 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on AC power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports ±1 kV line-earth(CM) on communication ports

Conducted RF immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 35

Certifications

Certification (when product is marked)(1) c-UL-us

Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:

Article 58-2 of Radio Waves Act, Clause 3

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification for Declaration of Conformity, Certificates, and other certification details.

Micro850 48-Point Controllers

General Specifications ­ 2080-LC50-48AWB, 2080-LC50-48QWB, 2080-LC50-48QVB, 2080-LC50-48QBB

Attribute Number of I/O Dimensions, HxWxD Shipping weight, approx.

2080-LC50-48AWB

2080-LC50-48QWB

48 (28 inputs, 20 outputs)

90 x 238 x 80 mm (3.54 x 9.37 x 3.15 in.)

0.725 kg (1.60 lb)

2080-LC50-48QVB 2080-LC50-48QBB

Publication 2080-SG001D-EN-P - December 2013

36 Micro800 Programmable Controller Family Selection Guide

General Specifications ­ 2080-LC50-48AWB, 2080-LC50-48QWB, 2080-LC50-48QVB, 2080-LC50-48QBB

Attribute Wire size

2080-LC50-48AWB Min

2080-LC50-48QWB Max

2080-LC50-48QVB 2080-LC50-48QBB

Solid

0.2 mm2 (24 AWG) 2.5 mm2 (14 AWG) rated @ 90°C (194 °F), insulation max.

Stranded 0.2 mm2 (24 AWG) 2.5 mm2 (14 AWG)

Wiring category(1)

2 ­ on signal ports 2 ­ on power ports 2 ­ on communication ports

Wire type

Use copper conductors only

Terminal screw torque

0.4...0.5 Nm (3.5...4.4 lb-in.) (using a 0.6 x 3.5 mm flat-blade screwdriver)

Input circuit type

120V AC

24V DC sink/source standard and high-speed

Output circuit type

Relay

24V DC sink standard 24V DC source standard and

and high-speed

high-speed

Power consumption

33 W

Power supply voltage range

20.4...26.4V DC Class 2

I/O rating

Input 120V AC, 16 mA Output 2 A, 240V AC, 2 A, 24V DC

Input 24V DC, 8.8 mA Output 2 A, 240V AC, 2 A, 24V DC

Input 24V DC, 8.8 mA Output 24V DC, 1 A per point (Surrounding air temperature 30 °C) 24V DC, 0.3 A per point (Surrounding air temperature 65 °C)

Insulation stripping length 7 mm (0.28 in.)

Enclosure type rating

Meets IP20

Pilot duty rating

C300, R150

--

Isolation voltage

250V (continuous), Reinforced Insulation Type, Output to Aux and Network, Inputs to Outputs Type tested for 60 s @ 3250V DC Output to Aux and Network, Inputs to Outputs.

250V (continuous), Reinforced 50V (continuous), Reinforced Insulation Type, I/O to

Insulation Type, I/O to Aux and Aux and Network, Inputs to Outputs

Network, Inputs to Outputs

Type tested for 60 s @ 720V DC, I/O to Aux and

Type tested for 60 s @ 3250V DC Network, Inputs to Outputs.

Output to Aux and Network, Inputs

to Outputs.

150V (continuous), Reinforced Insulation Type, Input to Aux and Network Type tested for 60 s @ 1950V DC Input to Aux and Network

50V (continuous), Reinforced Insulation Type, Input to Aux and Network Type tested for 60 s @ 720V DC, Inputs to Aux and Network

North American temp code T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Input Specifications Attribute
Number of Inputs Input group to backplane isolation
Voltage category Operating voltage range

2080-LC50-48AWB
120V AC Input
28
Verified by the following dielectric tests: 1950V AC for 2 s 150V working voltage (IEC Class 2 reinforced insulation)
110V AC
132V, 60Hz AC max

2080-LC50-48QWB / 2080-LC50-48QVB / 2080-LC50-48QBB

High-Speed DC Input (Inputs 0...11)

Standard DC Input (Inputs 12 and higher)

12

16

Verified by the following dielectric tests: 720V DC for 2 s 50V DC working voltage (IEC Class 2 reinforced insulation)

24V DC sink/source
16.8...26.4V DC @ 65 °C (149 °F) 16.8...30.0V DC @ 30 °C (86 °F)

10...26.4V DC @ 65 °C (149 °F) 10...30.0V DC @ 30 °C (86 °F)

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 37

Input Specifications Attribute
Off-state voltage, max Off-state current, max On-state current, min On-state current, nom On-state current, max Nominal impedance
IEC input compatibility Inrush current, max Input frequency, max

2080-LC50-48AWB 120V AC Input
20V AC 1.5 mA 5 mA @ 79V AC 12 mA @ 120V AC 16 mA @ 132V AC 12 k @ 50 Hz 10 k @ 60 Hz Type 3 250 mA @ 120V AC 63 Hz

2080-LC50-48QWB / 2080-LC50-48QVB / 2080-LC50-48QBB

High-Speed DC Input (Inputs 0...11)

Standard DC Input (Inputs 12 and higher)

5V DC

1.5 mA

5.0 mA @ 16.8V DC

1.8 mA @ 10V DC

7.6 mA @ 24V DC

6.15 mA @ 24V DC

12.0 mA @ 30V DC

3 k

3.74 k

-- --

Output Specifications

Attribute

2080-LC50-48AWB / 2080-LC50-48QWB 2080-LC50-48QVB / 2080-LC50-48QBB

Relay Output

Hi-Speed Output (Outputs 0 through 3)

Standard Output (Outputs 4 and higher)

Number of outputs

20

4

16

Output voltage, min

5V DC, 5V AC

10.8V DC

10V DC

Output voltage, max

125V DC, 265V AC

26.4V DC

26.4V DC

Load current, min

10 mA

Load current, max

2.0 A

100 mA (high-speed operation)

1.0 A @ 30 °C

1.0 A @ 30 °C

0.3 A @ 65 °C (standard operation)

0.3 A @ 65 °C (standard operation)

Surge current, per point See Relay Contacts Ratings on page 33

4.0 A for 10 ms every 1 s @ 30 °C; every 2 s @ 65 °C(1)

Current, per common, max 5 A

--

--

Turn on time/ Turn off time, max

10 ms

2.5 s

0.1 ms 1 ms

(1) Applies for general purpose operation only. Does not apply for high-speed operation.

Relay Contacts Ratings

Maximum Volts
120V AC 240V AC 24V DC 125V DC

Amperes Make 15 A 7.5 A 1.0 A 0.22 A

Break 1.5 A 0.75 A

Amperes Continuous 2.0 A
1.0 A

Volt-Amperes Make Break 1800V A 180V A
28V A

For relay life chart, see the Specifications section of the Micro830 and Micro850 User Manual, publication 2080-UM002.

Publication 2080-SG001D-EN-P - December 2013

38 Micro800 Programmable Controller Family Selection Guide

Environmental Specifications

Attribute

Value

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)

Temperature, surrounding air, max

65 °C (149 °F)

Temperature, non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): DIN mount: 25 g PANEL mount: 35 g

Emissions

CISPR 11 Group 1, Class A

ESD immunity

IEC 61000-4-2: 4 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @5 kHz on signal ports ±1 kV @ 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports ±1 kV line-earth(CM) on communication ports

Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 39

Certifications

Certification (when product is marked)(1) c-UL-us

Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications.

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:

Article 58-2 of Radio Waves Act, Clause 3.

(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification for Declaration of Conformity, Certificates, and other certification details.

Publication 2080-SG001D-EN-P - December 2013

40 Micro800 Programmable Controller Family Selection Guide
Notes:
Publication 2080-SG001D-EN-P - December 2013

Select Micro850 Expansion I/O

The 2085 I/O expansion modules provide superior functionality in a small-sized low-cost package. A variety of digital and analog modules complement and extend the capabilities of Micro850 controllers by maximizing the flexibility of I/O count and type.
Micro850 expansion I/O modules include high density discrete and analog I/O modules, including a high accuracy RTD and Thermocouple module.

There are available solid state output modules which are recommended to reduce switching noise and for applications which require more switching cycles, than relays. Triac outputs are available for AC loads. Sink and source transistor outputs are available for DC loads.
The following section provides the list of available Micro850 expansion I/O modules and their specifications.

Micro850 Expansion I/O Modules

Catalog Number 2085-IA8 2085-IM8 2085-OA8 2085-IQ16 2085-IQ32T 2085-OV16 2085-OB16 2085-OW8 2085-OW16

Type Discrete Discrete Discrete Discrete Discrete Discrete Discrete Discrete Discrete

Description 8-point, 120V AC input 8-point, 240V AC input 8-point, 120/240V AC Triac Output 16-point, 12/24V DC Sink/Source Input 32-point, 12/24V DC Sink/Source Input 16-point, 12/24V DC Sink Transistor Output 16-point, 12/24V DC Source Transistor Output 8-point, AC/DC Relay Output 16-point, AC/DC Relay Output

41Publication 2080-SG001D-EN-P - December 2013

42 Micro800 Programmable Controller Family Selection Guide

Micro850 Expansion I/O Modules

Catalog Number Type

Description

2085-IF4

Analog

4-channel, 14-bit isolated(2) voltage/current input

2085-IF8

Analog

8-channel, 14-bit isolated(2) voltage/current input

2085-OF4

Analog

4-channel, 12-bit isolated(2) voltage/current output

2085-IRT4

Specialty

4-channel, 16-bit RTD and TC isolated(2) input module

2085-ECR(1)

Terminator

2085 bus terminator

(1) The 2085-ECR bus terminator should always be the last module on the system, if any expansion I/O module is attached to the system.
(2) Refers to isolation from field side wiring to controller, not channel-to-channel isolation.

Discrete Expansion I/O

2085-IQ16 and 2085-IQ32T DC Sink/Source Input Modules(1)

Attribute

2085-IQ16

2085-IQ32T

Number of inputs

16 sink/source

32 sink/source

Dimensions, HxWxD

44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)

Shipping weight, approx.

220 g (7.76 oz)

Bus current draw, max Wire size
Wiring category(2)

170 mA @ 5V DC

190 mA @ 5V DC

0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max

2 ­ on signal ports

Terminal screw torque, 0.5...0.6 Nm

max

(4.4...5.3 lb-in.)(3)

Input circuit type

24V AC/DC sink/source

Power dissipation, total 4.5 W

7 W

Power supply

24V DC

Status indicators

16 yellow indicators

32 yellow indicators

Isolation voltage

50V (continuous), Reinforced Insulation Type, channel to system Type tested @ 720V DC for 60 s

Enclosure type rating Meets IP20

North American temp T4 code

Operating voltage range 10...30V DC, Class 2 21.6...26.4V AC, Class 2 See Derating Curve for 2085-IQ16 and Derating Curve for 2085-IQ32T on page 43

Off-state voltage, max 5V DC

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 43

2085-IQ16 and 2085-IQ32T DC Sink/Source Input Modules(1)

Attribute

2085-IQ16

2085-IQ32T

Off-state current, max 1.5 mA

1.2 mA

On-state current, min 1.8 mA @ 10V DC

On-state current, nom 6.0 mA @ 24V DC

5.2 mA @ 24V DC

On-state current, max 8.0 mA @ 30V DC

7.0 mA @ 30V DC

Input impedance, max 3.9 k

4.6 k

IEC input compatibility Type 3

Type 1

(1) Meets IEC Type 1 24V DC Input Specifications. (2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1. (3) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Derating Curve for 2085-IQ16
Input voltage (V)

30 26.4

30°C

65°C

Temp

45302

Derating Curve for 2085-IQ32T
Input voltage (V)

30

26.4

30°C

24 65°C

18

24

Number of inputs
32 45301

2085-OV16 Sink and 2085-OB16 Source DC Output Module

Attribute Number of outputs Operating voltage range On-state voltage, min On-state voltage, nom On-state voltage, max On-state current, max
Dimensions, HxWxD

2085-OV16
16 sinking
10...30V DC
10V DC
24V DC
30V DC
0.5 A @ 30V DC, per output 8 A, per module
44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)

2085-OB16 16 sourcing

Publication 2080-SG001D-EN-P - December 2013

44 Micro800 Programmable Controller Family Selection Guide

2085-OV16 Sink and 2085-OB16 Source DC Output Module

Attribute

2085-OV16

2085-OB16

Shipping weight, approx. 220 g (7.76 oz)

Bus current draw, max Wire size
Wiring category(1)

200 mA @ 5V DC 0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max
2 ­ on signal ports

Terminal screw torque, max 0.5...0.6 Nm (4.4...5.3 lb-in.)(2)

Output circuit type

24V DC sink

24V DC source

Power dissipation, total

5 W

Power supply

24V DC, Class 2

Status indicators

16 Yellow channel indicators

Isolation voltage

50V (continuous), Reinforced Insulation Type, channel to system Type tested @ 720V AC for 60 s

Enclosure type rating

Meets IP20

North American temp code T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

2085-IA8, 2085-IM8, 2085-OA8 AC Input/Output Modules

Attribute

2085-IA8

2085-IM8

2085-OA8

Number of inputs

8

Dimensions, HxWxD

28 x 90 x 87 mm (1.10 x 3.54 x 3.42 in.)

Shipping weight, approx. 140 g (4.93 oz)

Bus current draw, max Wire size

5V DC, 150 mA

5V DC, 180 mA

0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max

Insulation stripping length 10 mm (0.39 in.)

Wiring category(1)

2 ­ on signal ports

Wire type

Copper

Terminal screw torque, max 0.5...0.6 Nm (4.4...5.3 lb-in.)(2)

Input/output circuit type 120V AC input

240V AC input

120V/240V AC output

Power supply

120V AC

240V AC

120V/240V AC

Power dissipation, total 2.36 W

2.34 W

5.19 W

Enclosure type rating

Meets IP20

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 45

2085-IA8, 2085-IM8, 2085-OA8 AC Input/Output Modules

Attribute

2085-IA8

2085-IM8

2085-OA8

Status indicators

8 yellow indicators

Isolation voltage

150V (continuous), Reinforced Insulation Type, channel to system Type tested @ 1950V DC for 60 s

240V (continuous), Reinforced Insulation Type, channel to system Type tested @ 3250V DC for 60 s

North American temp code T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Input Specifications ­ 2005-IA8 and 2085-IM8

Attribute Number of Inputs Voltage category Operating voltage range Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Inrush current, max Input filter time Off to On On to Off IEC type compliance

2085-IA8 8 120V AC 74...120V AC 20V AC 2.5 mA 5.0 mA @ 74V AC 12.5 mA @ 120V AC 22.2 k 450 mA < 20 ms
Type 3

2085-IM8
240V AC 159...240V AC 40V AC
4.0 mA @ 159V AC 7.0 mA @ 240V AC

Output Specifications ­ 2085-OA8

Attribute Number of Inputs Voltage category Operating voltage range Output voltage, min Output voltage, max Off-state current, max On-state current, min On-state current, max On-state current, per module, max Off-state voltage drop, max
Fusing

2085-OA8 8 120V/230V AC 120...240V AC 85V AC 240V AC 2.5 mA 10 mA per output 0.5 A per output 4 A 1.5V AC @ 0.5 A 2.5V AC @10 mA Not protected. A suitable rating fuse is recommended to protect outputs.

Publication 2080-SG001D-EN-P - December 2013

46 Micro800 Programmable Controller Family Selection Guide

Output Specifications ­ 2085-OA8

Attribute
Output signal delay Off to On On to Off
Surge current, max

2085-OA8
9.3 ms for 60 Hz, 11 ms for 50 Hz 9.3 ms for 60 Hz, 11 ms for 50 Hz 5 A

2085-OW8 and 2085-OW16 Relay Output Module

Attribute

2085-OW8

2085-OW16

Number of outputs 8, relay

16, relay

Dimensions, HxWxD 28 x 90 x 87 mm (1.10 x 3.54 x 3.42 in.)

44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)

Shipping weight, approx.
Wire size

140 g (4.93 oz)

220 g (7.76 oz)

0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max

Insulation strip length 10 mm (0.39 in.)

Wiring category(1)

2 ­ on signal ports

Wire type

Copper

Terminal screw torque. max

0.5...0.6 Nm (4.4...5.3 lb-in.)(2)

Bus current draw, max 5V DC, 120 mA 24V DC, 50 mA

5V DC, 160 mA 24V DC, 100 mA

Load current, max

2 A

Power dissipation, total

2.72 W

5.14 W

Relay contact, (0.35 power factor)

Max Volts
120V AC 240V AC 24V DC 125V DC

Amperes Make Break 15 A 1.5 A 7.5 A 0.75 A 1.0 A 0.22 A

Amperes Volt Amperes

Continuous Make Break

2.0 A

1800V A 180V A

1.0 A

28V A

Minimum load, per point

10 mA per point

Off-state leakage, max 1.5 mA

Status indicators

8 yellow indicators

16 yellow indicators

Isolation voltage

240V (continuous), Reinforced Insulation Type, channel to system Type tested @ 3250V DC for 60 s

Pilot duty rating

C300, R150

Enclosure type rating Meets IP20

North American temp T4 code

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 47

Analog Expansion I/O

2085-IF4, 2085-IF8, 2085-OF4 Analog Input and Output Modules

Attribute

2085-IF4

2085-OF4

2085-IF8

Number of I/O

4

8

Dimensions, HxWxD

28 x 90 x 87 mm (1.1 x 3.54 x 3.42 in.)

44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)

Shipping weight, approx.

140 g (4.93 oz)

220 g (7.76 oz)

Bus current draw, max Wire size Wiring category(1)

5V DC, 100 mA 24V DC, 50 mA

5V DC, 160 mA 24V DC, 120 mA

5V DC, 110 mA 24V DC, 50 mA

0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max

2 ­ on signal ports

Wire type

Shielded

Terminal screw torque 0.5...0.6 Nm (4.4...5.3 lb-in.)(2)

Power dissipation, total 1.7 W

3.7 W

1.75 W

Enclosure type rating Meets IP20

Status indicators

1 green health indicator

1 green health indicator

1 green health indicator 8 red error indicators

Isolation voltage

50V (continuous), Reinforced Insulation Type, channel to system and channel to channel. Type tested @ 720V DC for 60 s

North American temp T4 code

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Input Specifications ­ 2085-IF4 and 2085-IF8

Attribute Number of inputs Resolution Voltage Current Data format Conversion type Update rate
Step response time up to 63%
Input current terminal, user configurable Input voltage terminal, user configurable

2085-IF4

2085-IF8

4

8

14 bits (13 bits plus sign bit)
1.28 mV/cnt unipolar; 1.28 mV/cnt bipolar 1.28 A/cnt

Left justified, 16 bit 2s complement

SAR

< 2 ms per enabled channel without 50 Hz/60 Hz rejection, < 8 ms for all channel 8 ms with 50 Hz/60 Hz rejection

4...60 ms without 50Hz/60 Hz rejection ­ depends on number of enabled channel and filter setting 600 ms with 50 Hz/60 Hz rejection

4...20 mA (default) 0...20 mA

±10V 0...10V

Publication 2080-SG001D-EN-P - December 2013

48 Micro800 Programmable Controller Family Selection Guide

Input Specifications ­ 2085-IF4 and 2085-IF8

Attribute Input impedance
Absolute accuracy Accuracy drift with temp
Calibration required Overload, max.
Channel diagnostics

2085-IF4

2085-IF8

Voltage terminal >1 M Current terminal <100 

±0.10% Full Scale @ 25 ° C

Voltage terminal ­ 0.00428 % Full Scale/° C Current terminal ­ 0.00407 % Full Scale/° C

Factory calibrated. No customer calibration supported.

30V continuous or 32 mA continuous, one channel at a time.

Over and under range or open circuit condition by bit reporting

Output Specifications ­ 2085-OF4

Attribute

2085-OF4

Number of outputs

4

Resolution Voltage Current

12 bits unipolar; 11 bits plus sign bipolar
2.56 mV/cnt unipolar; 5.13 mV/cnt bipolar 5.13 A/cnt

Data format

Left justified, 16 bit 2s complement

Step response time up to 63%

2 ms

Conversion rate, max

2 ms per channel

Output current terminal, user configurable

0 mA output until module is configured 4...20 mA (default) 0...20 mA

Output voltage terminal, user configurable

±10V 0...10V

Current load on voltage output, max 3 mA

Absolute accuracy Voltage terminal Current terminal

0.133 % Full Scale @ 25 ° C or better 0.425 % Full Scale @ 25 ° C or better

Accuracy drift with temp

Voltage terminal ­ 0.0045 % Full Scale/° C Current terminal ­ 0.0069 % Full Scale/° C

Resistive load on mA output

15...500 ohm @ 24V DC

Specialty Expansion I/O

2085-IRT4 Temperature Input Module

Attribute Number of inputs Dimensions, HxWxD
Shipping weight, approx. Bus current draw, max

2085-IRT4
4
44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)
220 g (7.76 oz)
5V DC, 160 mA 24V DC, 50 mA

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 49

2085-IRT4 Temperature Input Module

Attribute Wire size
Wiring category(1)

2085-IRT4 0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max
2 ­ on signal ports

Terminal screw torque

0.5...0.6 Nm (4.4...5.3 lb-in.)(2)

Input type

Thermocouple type: B, C, E, J, K, TXK/XK (L), N, R, S, T
RTD type:
100  Pt  = 0.00385 Euro 200  Pt  = 0.00385 Euro 100  Pt  = 0.003916 U.S 200  Pt  = 0.003916 U.S. 100  Nickel 618 200  Nickel 618 120  Nickel 672 10  Copper 427
mV range: 0...100 mV Ohm input: 0...500 

Resolution

16 bits

Channel update time, typical 12...500 ms per enabled channel

Input impedance

> 10 M 

Accuracy

±0.5...±3.0 °C accuracy for Thermocouple inputs ±0.2...±0.6 °C accuracy for RTD inputs

Power dissipation, total

2 W

Enclosure type rating

Meets IP20

Status indicators

1 green health indicator

Isolation voltage

50V (continuous), Reinforced Insulation Type, channel to system. Type tested @ 720V DC for 60 s

North American temp code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Environment Specifications

Environment Specifications for All Micro850 Expansion I/O Modules

Attribute

Value

Temperature, operating

IEC60068-2-1 (Test Ad, Operating Cold), IEC60068-2-2, (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...65 °C (-4...149 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85 °C (-40...185 °F)

Temperature, surrounding air, max. 65 °C (149 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5...95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10...500 Hz

Publication 2080-SG001D-EN-P - December 2013

50 Micro800 Programmable Controller Family Selection Guide

Environment Specifications for All Micro850 Expansion I/O Modules

Attribute Shock, operating Shock, nonoperating Emissions ESD Immunity Radiated RF Immunity
EFT/B Immunity Surge Transient Immunity Conducted RF Immunity

Value
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g for DIN Rail Mounting 35 g for Panel Mounting
CISPR 11: Group 1, Class A
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4: ±2 kV @ 5 kHz on signal ports
IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±2 kV line-earth(CM) on shielded ports
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Certifications ­ All Micro800 Expansion I/O Modules

Certification (when product is marked)(1) c-UL-us

Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:

Article 58-2 of Radio Waves Act, Clause 3

(1) See the Product Certification link athttp://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and other certification details.

Publication 2080-SG001D-EN-P - December 2013

Select Micro800 Plug-in Modules and Accessories
Micro800 plug-in modules extend the functionality of embedded I/O without increasing the footprint of the controller. It improves performance by adding additional processing power or capabilities and adds additional communication functionality. Micro820, Micro830 and Micro850 controllers support plug-in modules. Micro800 accessories consist of a Remote LCD (compatible with Micro820 only), an LCD with keypad (compatible with Micro810 only), a USB adapter (compatible with Micro810 only), and an expansion power supply.
51Publication 2080-SG001D-EN-P - December 2013

52 Micro800 Programmable Controller Family Selection Guide

Micro800 Plug-in Modules and Accessories ­ Features and Compatibility

Plug-in / Accessory

Supported by Supported by Supported by

Feature

Micro810 Micro820 Micro830/Micro850

1.5" LCD and Keypad 2080-LCD

Yes

No

No

· backup module for Micro810 controllers · configure Smart Relay Function Blocks

Micro810 USB Adapter 2080-USBADAPTER

Yes

No

No

USB programming access

External Power Supply 2080-PS120-240VAC

Yes

Yes

Yes

optional controller power supply

RS232/485 Isolated Serial Port

No

2080-SERIALISOL

Yes

Yes

· adds additional serial communications with Modbus RTU and ASCII protocols

· isolated for increased noise immunity

Digital Input, Output, Relay, and

No

Yes

Yes

Combination Modules

2080-IQ4, 2080-IQ4OB4, 2080-IQ4OV4,

2080-OB4, 2080-OV4, 2080-OW4I

· 4-channel inputs/outputs or combination modules
· configurable as voltage and current inputs

· sink or source output

· 4-channel relay outputs

High Speed Counter 2080-MOT-HSC

No

Yes

Yes

· Up to a minimum of 250 KHz differential line driver for improved noise immunity and additional dedicated I/O

· One Quadrature (ABZ) differential inputs alternately configurable for pulse internal, pulse with external direction, A-up and B-down input configurations, and quadrature mode

· User-configurable minimum and maximum values, preset, and Z operation

DeviceNet Scanner 2080-DNET20

No

Yes

Yes

· Scanner mode ­ scan devices such as CompactBlockTM LDX, PowerFlex® drives, overloads and sensors

Remote LCD 2080-REMLCD

No

Yes

No

· Operator interface for configuring such settings as IP address on Micro820 controller

· With RS232 and USB ports

Non-isolated Unipolar Analog

No

Input/Output

2080-IF2, 2080-IF4, 2080-OF2

Yes

Yes

· adds up to 20 embedded analog I/O with 12-bit resolution (with 48-point controllers)
· 2 channels for 2080-IF2, 2080-OF2

· 4 channels for 2080-IF4

Non-isolated Thermocouple

No

2080-TC2

Non-isolated RTD

No

2080-RTD2

Yes

Yes

Yes

Yes

· for temperature control, when used with PID · 2 channels for 2080-TC2 and 2080-RTD2

Memory Module with RTC 2080-MEMBAK-RTC

No

No

Yes

· backup project data and application code · high accuracy real-time clock

6-Channel Trim Potentiometer

No

Analog Input

2080-TRIMPOT6

Yes

Yes

adds six analog presets for speed, position and temperature control

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 53
Micro800 Plug-In Modules

Digital Input, Output, Relay, and Combination Plug-Ins

Specifications (2080-IQ4, 2080-IQ4OB4, 2080-IQ4OV4, 2080-OB4, 2080-OV4)

Catalog 2080-IQ4
2080-IQ4OB4 2080-IQ4OV4
2080-OB4 2080-OV4

Input / Output

On-state voltage On-state current

4 inputs

DC 9.0V DC, min 30V DC, max
AC 10.25V AC (rms), min 30V AC (rms), max

DC 2.0 mA @ 9V DC, min 3.0 mA @ 24V DC, nom 5.0 mA, max
AC 2.0 mA @ 9V AC (rms), min 5.0 mA, max

4 channel inputs/source outputs combination
4 channel inputs/sink outputs combination

DC Input 9.0V DC, min 30V DC, max
AC Input 10.25V AC (rms), min 30V AC (rms), max
Output 10V DC, min 24V DC, nom 30V DC, max

DC Input 2.0 mA @ 9V DC, min 3.0 mA @ 24V DC, nom 5.0 mA, max
AC Input 2.0 mA @ 9V AC (rms), min 5.0 mA, max
Output 5.0 mA @ 10V DC, min 0.5 A max, steady state 2 A surge, 2 s min

4 source outputs 4 sink outputs

10V DC, min 24V DC, nom 30V DC, max

5.0 mA @ 10V DC, min 0.5 A max, steady state 2 A surge, 2 s min

Publication 2080-SG001D-EN-P - December 2013

54 Micro800 Programmable Controller Family Selection Guide

Specifications (2080-IQ4, 2080-IQ4OB4, 2080-IQ4OV4, 2080-OB4, 2080-OV4)

Catalog

Off-state voltage

2080-IQ4 2080-IQ4OB4 2080-IQ4OV4 2080-OB4, 2080-OV4

DC 5V DC, max AC 3.5V AC (rms)
­

Off-state current DC 1.5 mA, max
­

Power supply voltage
10.8V DC, min 30V DC, max

Mounting torque
0.2 Nm (1.48 lb-in.)

Status indicators 4 yellow 8 yellow
4 yellow

North American temp code
T4

Catalog 2080-IQ4
2080-IQ4OB4 2080-IQ4OV4 2080-OB4 2080-OV4

Terminal base screw torque
0.22...0.25 Nm (1.95...2.21 lb-in.) using a 2.5 mm (0.10 in.) flat-blade screwdriver

Isolation voltage
50V (continuous), Basic Insulation Type, Inputs to Backplane Type tested for 60 s @ 720V DC, Inputs to Backplane
50V (continuous), Basic Insulation Type, Inputs to Outputs, I/Os to Backplane Type tested for 60 s @ 720V DC, I/Os to Backplane

Wire size
0.2... 2.5 mm2 (24...12 AWG) solid or stranded copper wire rated @ 90 °C (194 °F), or greater, insulation max

Catalog
2080-IQ4 2080-IQ4OB4 2080-IQ4OV4 2080-OB4 2080-OV4

Operating temperature
-20...65 °C (-4...149 °F)

Non-operating temperature
-40...85 °C (-40...185 °F)

Surrounding air, max
65 °C (149 °F)

Relative humidity

Vibration

5...95%

2 g @ 10...500 Hz

noncondensing

Shock, operating
25 g

Shock, non-operating
25 g

Specifications (2080-OW4I)

Catalog 2080-OW4I

Input/Output
4-channel relay output

Inrush current Backplan e power
<120 mA @ 3.3V 3.3 VDC, <120 mA @ 24V 38 mA

Output current, Output current,

resistive

inductive

Output power, resistive, max

2 A @ 5...30V DC 0.5 A @ 48V DC 0.22 A @ 125V DC 2 A @ 125V AC 2 A @ 240V AC

1.0 A steady state @ 5...28V DC
0.93 A steady state @ 30V DC
0.5 A steady state @ 48V DC
0.22 A steady state @ 125V DC
2.0 A steady state, 15 A make @ 125V AC, PF ­ cos  = 0.4
2.0 A steady state, 7.5 A make @ 240V AC, PF ­ cos  = 0.4

250V A for 125V AC resistive loads 480V A for 240V AC resistive loads 60V A for 30V DC resistive loads 24V A for 48V DC resistive loads 27.5V A for 125V DC resistive loads

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 55

Catalog

Output power, inductive break, max Pilot duty rating

2080-OW4I

180 VA for 125V AC inductive loads 180 VA for 240V AC inductive loads 28 VA for 28.8V DC inductive loads 28 VA for 48V DC inductive loads 28 VA for 125V DC inductive loads

C300, R150

Minimum load, per point
10 mA

Initial contact resistance of relay, max
30 m

Output delay time, max
10 ms ON or OFF

Catalog 2080-OW4I

Relay contact, (0.35 power factor)

Volts, max

Amperes

Make

Break

120V AC

15 A

1.5 A

240V AC

7.5 A

0.75 A

24V DC

1.0 A

125V DC

0.22 A

Amperes Continuous 2.0 A
1.0 A

Volt-Amperes Make 1800V A

Break 180V A

28V A

Catalog 2080-OW4I

Operating temperature
-20...65 °C (-4...149 °F)

Non-operating temperature
-40...85 °C (-40...185 °F)

Surrounding air, max
65 °C (149 °F)

Relative humidity

Vibration

5...95%

2 g @ 10...500 Hz

noncondensing

Shock, operating
10 g

Shock, non-operating
DIN rail mounting: 25 g Panel mounting: 35 g

Analog Input and Output Plug-ins

Specifications (2080-IF2, 2080-IF4, 2080-OF2)

Catalog
2080-IF2 2080-IF4 2080-OF2

Number of inputs/ outputs

Voltage Current Power

Input impedance Voltage

range range consumption

resistive load

2 inputs, unipolar non-isolated
4 inputs, unipolar non-isolated

0...10V 0...20 mA <60 mA @ 3.3V

>100 k for voltage mode 250  for current mode

2 outputs, unipolar non-isolated

<60 mA @ 24V ­

1 k, min

Catalog
2080-IF2 2080-IF4 2080-OF2

Current Mounting Terminal screw Wire size resistive torque torque load

Operating temp.

­ 500 

0.2 Nm (1.48 lb-in.)

0.22...0.25 Nm (1.95...2.21 lb-in.) using a 2.5 mm (0.10 in.) flat-blade screwdriver

Solid: 0.14 mm2 (26 AWG), min 1.5 mm2 (16 AWG), max
Stranded: 0.14 mm2 (26 AWG), min 1.0 mm2 (18 AWG), max
rated @ 90 °C (194 °F ) insulation max

-20...65 °C (-4...149 °F)

Non-operating temp.
-40...85 °C (-40...185 °F)

Surrounding North

air, max

American

temp code

65 °C (149 °F) T4

Publication 2080-SG001D-EN-P - December 2013

56 Micro800 Programmable Controller Family Selection Guide

Thermocouple and RTD (2080-TC2, 2080-RTD2)

Specifications (2080-RTD2, 2080-TC2) Catalog Type
2080-RTD2 2-channel non-isolated RTD 2080-TC2 2-channel non-isolated Thermocouple

Common mode rejection ratio
100 dB @ 50/60Hz

Normal mode rejection ratio
70 dB @ 50/60 Hz

Catalog 2080-RTD2

Type

Common mode

rejection ratio

2-channel

100 dB @

non-isolated RTD 50/60Hz

2080-TC2

2-channel non-isolated Thermocouple

Normal mode RTD types rejection ratio supported

Thermocouple types supported

70 dB @ 50/60 Hz 100  Platinum 385, ­ 200  Platinum 385, 500  Platinum 385,
1000 Platinum 385,
100  Platinum 392, 200  Platinum 392, 500  Platinum 392, 1000  Platinum 392, 10  Copper 427, 120  Nickel 672, 604  Nickel-Iron 518

­

J, K, N, T, E, R, S, B

Terminal screw torque
0.22...0.25 Nm (1.95...2.21 lb-in.) using a 2.5 mm (0.10 in.) flat-blade screwdriver

Catalog

Wire size

2080-RTD2 2080-TC2

Solid: 0.14 mm2 (26 AWG), min 1.5 mm2 (16 AWG), max Stranded: 0.14 mm2 (26 AWG), min 1.0 mm2 (18 AWG), max rated @ 90 °C (194 °F ) insulation max

Operating temperature
-20...65 °C (-4...149 °F)

Non-operating temperature
-40...85 °C (-40...185 °F)

Surrounding air, max 65 °C (149 °F)

North American temp code
T4

Trimpot Analog Input (2080-TRIMPOT6)

Specifications (2080-TRIMPOT6)

Numberof Mounting Operating Non-operating Surrounding

inputs

torque

temperature temperature air, max

6-channel, Trimpot

0.2 Nm

-20...65 °C -40...85 °C

(1.48 lb-in.) (-4...149 °F) (-40...185 °F)

65 °C (149 °F)

North American temp code
T4

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 57

Memory Backup and High Accuracy RTC Plug-In (2080-MEMBAK-RTC)

Specifications (2080-MEMBAK-RTC)

Mounting torque
0.2 Nm (1.48 lb-in)

Terminal

Operating

screw torque temperature

0.22....0.25 Nm (1.95...2.21 lb-in.) using a 2.5 mm (0.10 in.) flat-blade screwdriver

-20...65 °C (-4...149 °F)

Non-operating temperature
-40...85 °C (-40...185 °F)

Surrounding North

air, max

American

temp code

65 °C

T4

(149 °F)

RS232/485 Serial Port Plug-in (2080-SERIALISOL)

Specifications (2080-SERIALISOL)

Mounting Terminal screw torque torque

0.2 Nm (1.48 lb-in)

0.22...0.25 Nm (1.95...2.21 lb-in) using a 2.5 mm (0.10 in.) flat-blade screwdriver

Wire size
Solid: 0.14...1.5 mm2 (26...16 AWG) Stranded: 0.14...1.0 mm2 (26...18 AWG) rated @ 90 °C (194 °F ) insulation max

Isolation voltage
500V AC

Operating temperature -20...65 °C (-4...149 °F)

Non-operating temperature
-40...85 °C (-40...185 °F)

Surrounding air, max 65 °C (149 °F)

North American temp code
T4

Publication 2080-SG001D-EN-P - December 2013

58 Micro800 Programmable Controller Family Selection Guide

DeviceNet (2080-DNET20)

Specifications (2080-DNET20)

DeviceNet Communication Rate, max
125 Kbps ­ 420 m (1378 ft.) 250 Kbps ­ 200 m (656 ft.) 500 Kbps ­ 75 m (246 ft.)

DeviceNet current 24V DC, 300 mA Class 2

Wire size
0.25... 2.5 mm2 (22...14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F ), or greater, 1.2 mm (3/64 in.) insulation max

Network protocol
I/O Slave Messaging: Poll Command

Backplane power consumption
50 mA @ 24V DC

Power dissipation
1.44 W

Number of nodes, max 20 nodes for I/O operation

High Speed Counter (2080-MOT-HSC)

Specifications (2080-MOT-HSC)

Input Frequency, max
250 kHz (50% duty)

Wire size
Solid: 0.14...1.5 mm2 (26...16 AWG) Stranded: 0.14...1.0 mm2 (26...18 AWG) rated @ 90 °C (194 °F ) insulation max

Number of inputs
1 Quadrature (ABZ) differential input

Input impedance Pulse width, min

3580 

2 s

All supply power and/or current ratings

Isolation voltage

Input/Output: 24V DC

Input module: 50V (continuous), Basic Insulation Type, Inputs/Outputs to Backplane. Type tested for 60s @ 720V DC, Inputs/Outputs to Backplane

Micro800 Accessories

Micro810 LCD (2080-LCD)

Operating temperature

Temperature, surrounding air, max

-20..55 °C (-4...131 °F)

55 °C (131 °F)

Temperature, nonoperating
-40...85 °C (-40...185 °F)

North American temp code
T5

Micro810 USB Adapter (2080-USBADAPTER)

USB cable

Temperature, Temperature,

Temperature,

connector type operating surrounding air, max non-operating

USB Type A-B Male-Male

-20...55 °C 55 °C (131 °F) (-4...131 °F)

-40...85 °C (-40...185 °F)

North American temp code
T5

Publication 2080-SG001D-EN-P - December 2013

Micro800 Programmable Controller Family Selection Guide 59

External Power Supply (2080-PS120-240VAC)

Attribute

Value

Dimensions, HxWxD

90 x 45 x 80 mm (3.55 x 1.78 x 3.15 in)

Shipping weight Supply voltage range(1)

0.34 kg (0.75 lb)
100V...120V AC, 1A 200...240V AC, 0.5A

Supply frequency

47...63 Hz

Supply power

24V DC, 1.6 A

Inrush current, max
Power consumption(2) (Output power)

24 A @ 132V for 10 ms 40 A @ 263V for 10 ms
38.4 W @ 100V AC, 38.4 W @ 240V AC

Power dissipation (Input power)

45.1 W @ 100V AC, 44.0W @ 240V AC

Isolation voltage

250V (continuous), Primary to Secondary: Reinforced Insulation Type Type tested for 60s @ 2300V AC primary to secondary and 1480V AC primary to earth ground.

Output ratings

24V DC, 1.6 A, 38.4 W max.

(1) Any fluctuation in voltage source must be within 85V...264V. Do not connect the adapter to a power source that has fluctuations outside of this range.
(2) When setting up a Micro800 system, verify that total power consumption of the controller, plug-in and expansion I/O does not exceed the output power capacity of the power supply used.

Remote LCD (2080-REMLCD)

Attribute

Value

Dimensions, HxWxD

97 x 130 x 35.5 mm (3.82 x 5.12 x 1.40 in.)

Display type

192 x 64 pixel monochrome

Display size

48 x 106.5 mm (1.89 x 4.19 in.)

Backlight

25000 hrs @ 25 °C LED; tricolor backlight (RGB)

Operator input

Tactile keys (function keys, arrow keys, ESC and OK keys)

Programming port

USB to serial converter for programming the controller

Input supply voltage

12V/24V DC (±10%)

Input supply current, max 90 mA @ 12V and 60 mA @ 24V

Power consumption, max 1.5 W

Weight, approx.

405 g (0.89 lb) ­ includes packaging weight

Wire size

Single-wire gauge: 0.14...1.5 mm2 (26...16 AWG) rated @ 90 °C (194 °F) Dual-wire gauge: 0.14...0.75 mm2 (26...18 AWG) rated @ 90 °C (194 °F)

Wire type Wiring category(1)

Copper 3 ­ on power ports; 3 ­ on communication port

Enclosure type ratings

Meets IP65 (when front panel mounted)

North American temp code T4

(1) Use this conductor category information.

Publication 2080-SG001D-EN-P - December 2013

60 Micro800 Programmable Controller Family Selection Guide

For More Information

Visit the Micro800 website at http://ab.rockwellautomation.com/Programmable-Controllers/Micro800 to learn more about Micro800 products and download Connected Component Workbench software and Micro800 firmware updates.
If you would like a manual, you can: · download a free electronic version from the Internet: http://rockwellautomation.com/literature. · purchase a printed manual by contacting your local Allen-Bradley distributor or Rockwell Automation representative.
You can also visit the following websites for additional technical information:
· Sample Code Library http://samplecode.rockwellautomation.com/idc/groups/public/docume nts/webassets/sc_home_page.hcst
· Technical Forums http://www.rockwellautomation.com/forums/
· Connected Component Accelerator Toolkit http://www.rockwellautomation.com/components/connected/ccat.html

Additional Resources

These documents contain additional information concerning related Rockwell Automation products.

Resource

Description

Micro810 Programmable Controllers User Manual, publication 2080-UM001 xxxxx

A more detailed description of how to install and use your Micro810 programmable controller.

Micro820 Programmable Controllers User Manual, publication 2080-UM005

A more detailed description of how to install and use your Micro820 programmable controllers.

Micro830 and Micro850 Programmable Controllers User Manual, publication 2080-UM002 xxxxxxx

A more detailed description of how to install and use your Micro830 and Micro850 programmable controller.

Micro800 Plug-in Modules User Manual, publication 2080-UM004

Description of features, installation, wiring, and specifications for the Micro800 plug-in modules.

Micro800 Discrete and Analog Expansion I/O Description of features, installation, wiring, and

Modules User Manual, publication

specifications for the Micro800 expansion I/O

2080-UM003

modules and accessories.

Industrial Automation Wiring and Grounding Provides general guidelines for installing a Rockwell

Guidelines, publication

Automation industrial system.

1770-4.1

Product Certifications website,

Provides declarations of conformity, certificates, and

http://www.rockwellautomation.com/produ other certification details.

cts/certification/

Publication 2080-SG001D-EN-P - December 2013

Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance

If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.

United States or Canada
Outside United States or Canada

1.440.646.3434
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States Outside United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Otomasyon Ticaret A.., Kar Plaza  Merkezi E Blok Kat:6 34752 çerenköy, stanbul, Tel: +90 (216) 5698400

Publication 2080-SG001D-EN-P - December 2013 62
Supersedes Publication 2080-SG001C-EN-P ­ September 2012

Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.


Acrobat Distiller 11.0 (Windows)