Document DEVICE REPORTSD1220AU
UCV - Geothermal Condo Unit
Geothermal/Water Source Heat Pump Commercial 1.5 - 3.5 Tons
Submittal Data English Language/IP Units
SD1220AU 09/10

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Model Nomenclature

1-2 3 4-6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21-22 23 UC V 023 T L 0 0 0 C A N N 2 1 N 1 0 SS A

Model Type UC = Versatec Ultra Condo
Cabinet Configuration V = Vertical
Unit Capacity 018 023 031 041 1

Vintage A = Current
Non-Standard Option Details SS = Standard Option
Drain Pan Options 0 = Composite Drain Pan
Cabinet 0 = Unpainted, 1 in. MERV 4, Filter Rail 1 = Painted, 1 in. MERV 4, Filter Rail

Discharge Configuration T = Top

Future Use N = None

Air Configuration L = Left R = Right

Air Coil/Insulation Options 1 = FormiShield/Extended Range 4 = No Coating/Standard Range

Voltage 0 = 208-230/60/1 2 = 265/60/1
Hot Water Generation Option 0 = No Hot Water Generation 2 = Hot Water Generation w/o pump
Blower Option 0 = PSC Blower
Coax C = Copper N = Cupronickel

Controls Option 2 = Versatec Microprocessor
Water Control N = None
Future Use N = None
Sound Kit A = None B = Sound Kit

NOTE: 1 UCV041 not available in 265/60/1

All Versatec Ultra Series UCV product is safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1. The Versatec Ultra Series UCV is also Energy Star rated.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

2

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

AHRI/ISO 13256-1 Performance Ratings

PSC Motor
AHRI/ASHRAE/ISO 13256-1 English (IP) Units

Flow Rate Model

Water Loop Heat Pump

Cooling EWT 86°F

Heating EWT 68°F

Ground Water Heat Pump

Cooling EWT 59°F

Heating EWT 50°F

gpm

cfm

Capacity EER Capacity Btuh Btuh/W Btuh

COP

Capacity EER Capacity Btuh Btuh/W Btuh

COP

018 5.0 600 17,600 14.6 21,000 4.7 20,600 23.5 17,500 4.0

023 6.0 800 22,000 13.8 27,000 4.5 26,400 21.0 22,300 3.9

031 8.0 1000 29,000 14.0 34,600 4.5 32,900 20.5 28,300 3.9

041 11.0 1300 39,000 13.0 45,000 4.0 44,500 19.0 36,000 3.5

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Heating capacities based upon 68°F DB, 59°F WB entering air temperature All ratings based upon 208V operation

Ground Loop Heat Pump

Cooling EWT 77°F

Heating EWT 32°F

Capacity EER Capacity Btuh Btuh/W Btuh

COP

18,500 17.0 13,700 3.5

24,000 15.6 17,500 3.2

29,500 15.6 22,800 3.2

41,000 14.9 29,000 2.9

Energy Star Rated
yes no no no 9/2/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

3

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Dimensional Data

Legend
AP = Alternate Service Panel BP = Blower Service Panel CP = Control Access Panel CMP = Compressor Service Panel

A

N

R

Q

STANDARD FILTER RAIL FOR OPEN RETURN APPLICATIONS (ATTACHED BY HOOK METHOD)

A

S

N

AIR COIL Q

BP

PB

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz
FIELD INSTALLED DUCT FLANGES
AP

AIR COIL SIDE

AIR COIL SIDE

M FRONT TOP VIEW - RIGHT RETURN

M

FRONT

TOP VIEW - LEFT RETURN

F

G

4

3

1.00

1.00

F

4

G

3

2' (61 cm) Service Access

ISOMETRIC VIEW - LEFT RETURN

U

T

W

AIR COIL SIDE

AIR COIL SIDE

AIR COIL

AP

AP

V

C
H E

1.6in (4.1 cm)
CONDENSATE 3/4 in PVC GLUE SOCKET

5

1.6 in

(4.1 cm) 6

2

8

1

POWER SUPPLY 3/4" KNOCKOUT
LOW VOLTAGE 1/2" KNOCKOUT

LJ

LK

1.6 in (4.1 cm) CONDENSATE

1.6 in

5

(4.1 cm)

8

2

7 CMP

1

C
H E

6 8
JL

AP

8

7 L
K

D FRONT VIEW - RIGHT RETURN

D FRONT VIEW - LEFT RETURN

1.0 in (2.5 cm)

1.0 in RIGHT VIEW - RIGHT RETURN (2.5 cm)
LEFT VIEW - LEFT RETURN

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

4

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Dimensional Data cont.

Overall Cabinet

1

Vertical Models

A

B

C

D

Width Depth Height** In

in. 21.5

21.5

36.2

2.6

018-031 cm. 54.6

54.6

91.9

6.6

in. 21.5

21.5

40.2

2.6

041

cm. 54.6

54.6

102.1

6.6

Water Connections

Electrical Knockouts

2

3

4

5

6

7

8

E

F

G

H

Loop

Knockout

J

K

L

Out

HWG In

HWG Out

Cond- Water HWG 1/2 in. ensate FPT Provisions cond

1/2 in. cond

1 in. cond

7.6

3.1

6.1

10.8

3/4"

0.875

9.4

5.4

7.4

19.3

7.9

15.5

27.4 19.1 mm 22.2 mm 23.9

13.7

18.8

7.6

3.1

6.1

10.8

3/4"

0.875

9.4

5.4

7.4

19.3

7.9

15.5

27.4 19.1 mm 22.2 mm 23.9

13.7

18.8

Discharge Connection

Return Connection*

Vertical Models

M

duct flange installed (±0.10 in)

N

P

Q

R

S

Filter Rack Supply

Supply

using deluxe filter rack (±0.10 in)

T

U

V

W

Return

Return

Width

Width

Depth

Depth

Height

in.

1.2

14.0

14.0

3.8

3.5

6.7

0.6

20.2

24.0

0.6

018-031 cm.

3.0

35.6

35.6

9.7

8.9

17.0

1.5

51.3

61.0

1.5

041

in. cm.

1.2 3.0

14.0 35.6

14.0 35.6

3.8 9.7

3.5 8.9

6.7 17.0

0.6

20.2

28.0

0.6

1.5

51.3

71.1

1.5

Condensate is 3/4 in. PVC female glue socket and is switchable from side to front.

9/2/10

*Dimensions for return connections are for a standard rail design with open return application only.

The open filter rail, used in non-ducted returns, extends 1.2 in. [3.11 cm] from the unit.

**Discharge flange is field installed and extends 1 in. (25.4 mm) from top of cabinet.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

5

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Physical Data

Model

Compressor (1 each)

Factory Charge R-410A, oz [kg]

Blower Motor & Blower

Blower Motor Type/Speeds

PSC

Blower Motor- hp [W]

PSC

Blower Wheel Size (Dia x W), in [mm]

PSC

Coax and Water Piping

Water Connection Size - FPT - in [mm]

HWG Connection Size - FPT - in [mm]

Coax & Piping Water Volume - gal [l]

Vertical

Air Coil Dimensions (H x W), in. [mm]

Air Coil Total Face Area, ft2 [m2]

Air Coil Tube Size, in [mm]

Air Coil Number of rows

Filter Standard - 1 in [25mm] MERV 4 Throwaway, in [mm]

Shipping Weight- lb [kg]

018 Rotary 52 [1.47]
1/6 [134] 9 x 7 [229 x 178]
3/4 [19.1] 1/2 [12.7] 0.4 [1.49]
22 x 16 [559 x 406] 2.4 [0.220] 3/8 [9.5] 3
24 x 20 [610 x 508] 170 [77]

Single Speed

023

031

Scroll

44 [1.25]

50 [1.42]

3 speeds

1/5 [149]

1/3 [249]

9 x 7 [229 x 178]

9 x 7 [229 x 178]

3/4 [19.1] 1/2 [12.7] 0.4 [1.49]

3/4 [19.1] 1/2 [12.7] 0.75 [2.83]

22 x 16 [559 x 406] 2.4 [0.220] 3/8 [9.5] 3
24 x 20 [610 x 508] 220 [100]

22 x 16 [559 x 406] 2.4 [0.220] 3/8 [9.5] 3
24 x 20 [610 x 508] 240 [109]

041
68 [1.93]
1/3 [249] 9 x 7 [229 x 178]
3/4 [19.1] 1/2 [12.7] 0.9 [3.41]
26 x 16 [660 x 406] 2.9 [0.269] 3/8 [9.5] 3
28 x 24 [711 x 610] 275 [125] 9/2/10

Electrical Data

PSC Motor

Model

Rated Voltage

208-230/60/1 018
265/60/1

208-230/60/1 023
265/60/1

208-230/60/1 031
265/60/1

041

208-230/60/1

HACR circuit breaker in USA only

Voltage Min/Max
187/253 238/292 187/253 238/292 187/253 238/292 187/253

MCC
10.4 8.7 21.0 14.0 22.0 17.5 31.0

Compressor
RLA
6.7 5.6 13.5 9.0 14.1 11.2 20.0

LRA
33.5 28.0 58.3 54.0 73.0 60.0 115.0

Blower Motor FLA
1.1 1.0 1.2 1.1 1.5 1.5 3.5

Total Unit FLA 7.8 6.6 14.7 10.1 15.6 12.7 23.5

Min Circ Amp 9.5 8.0 18.1 12.4 19.1 15.5 28.5

Max Fuse/ HACR
15 10 30 20 30 25 45 9/2/10

Blower Performance Data

Standard PSC Motor

Model

Blower Blower

Spd

Size

Motor HP

0

0.05

0.10

0.15

Airflow (cfm) at External Static Pressure (in. wg) 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60

0.70

0.80

0.90

1.00

H

875 860 845 830 820 805 790 770 750 725 700

-

-

-

-

-

018

M

9 x 7

1/6

760 750 740 730 720 710 700 680 660 640 620

-

-

-

-

-

L

630 620 610 600 590 580 570 560 550 520 490

-

-

-

-

-

H

995 975 950 925 895 865 835 795 750 715 680 595

-

-

-

-

023

M

9 x 7

1/5

860 840 820 805 785 755 725 690 655 620 580

-

-

-

-

-

L

790 775 760 745 725 690 655 635 610 575 535

-

-

-

-

-

H

1160 1135 1110 1085 1055 1025 995 965 930 890 850 765 650

-

-

-

031

M

9 x 7

1/3

1035 1015 1000 975 955 930 905 875 845 810 780 685

-

-

-

-

L

855 845 840 830 820 800 785 760 740 710 685 610

-

-

-

-

H

1200 1170 1145 1115 1080 1035 995 955 915 875 835 765 640

-

-

-

041

M

9 x 7

1/2

1110 1085 1065 1035 1010 975 940 900 860 825 795 715 585

-

-

-

L

1040 1020 1000 975 950 920 890 860 830 795 765 683 560

-

-

-

Factory settings are in Bold

9/2/10

Air flow values are with dry coil and standard filter

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

6

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Operating Limits

Operating Limits
Air Limits Min. Ambient Air Rated Ambient Air Max. Ambient Air Min. Entering Air Rated Entering Air db/wb Max. Entering Air db/wb
Water Limits Min. Entering Water Normal Entering Water Max. Entering Water

Cooling

(°F)

(°C)

45 80 100 50 80.6/66.2 110/83

7.2 26.7 37.8 10.0 27/19 43/28.3

30 50-110
120

-1.1 10-43.3
48.9

Heating

(°F)

(°C)

45

7.2

70

21.1

85

29.4

40

4.4

68

20.0

80

26.7

20 30-70
90

-6.7 -1.1 32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.

Definitions
ABBREVIATIONS AND DEFINITIONS:
CFM = airflow, cubic feet/minute EWT = entering water temperature, Fahrenheit GPM = water flow in gallons/minute WPD = water pressure drop, PSI and feet of water EAT = entering air temperature, Fahrenheit
(dry bulb/wet bulb) HC = air heating capacity, MBTUH TC = total cooling capacity, MBTUH SC = sensible cooling capacity, MBTUH KW = total power unit input, kilowatts HR = total heat of rejection, MBTUH

HE = total heat of extraction, MBTUH HWC = hot water generator capacity, MBTUH EER = Energy Efficient Ratio
= BTU output/Watt input COP = Coefficient of Performance
= BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBTUH LC = latent cooling capacity, MBTUH S/T = sensible to total cooling ratio

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

7

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Correction Factor Tables

Cooling Capacity Corrections

Entering Air WB ºF
55 60 65 66.2 67 70 75

Total Clg Cap
0.898 0.912 0.967 0.983 1.000 1.053 1.168

60 0.723

65 0.866 0.632

Sensible Cooling Capacity Multipliers - Entering DB ºF

70

75

80

80.6

85

90

1.048 1.185

*

*

*

*

0.880 1.078 1.244 1.260

*

*

0.694 0.881 1.079 1.085 1.270

*

0.655 0.842 1.040 1.060 1.232

*

0.616 0.806 1.000 1.023 1.193 1.330

0.693 0.879 0.900 1.075 1.250

0.687 0.715 0.875 1.040

NOTE: * Sensible capacity equals total capacity at conditions shown.

95 * * * * * 1.404 1.261

100 * * * * * *
1.476

Power Input 0.985 0.994 0.997 0.999 1.000 1.003 1.007

Heat of Rejection
0.913 0.927 0.972 0.986 1.000 1.044 1.141 11/10/09

Heating Corrections

Ent Air DB °F 45 50 55 60 65 68 70 75 80

Htg Cap 1.062 1.050 1.037 1.025 1.012 1.005 1.000 0.987 0.975

Power 0.739 0.790 0.842 0.893 0.945 0.976 1.000 1.048 1.099

Heat of Ext 1.158 1.130 1.096 1.064 1.030 1.012 1.000 0.970 0.930 11/10/09

Air Flow Corrections

Airflow

CFM Per Ton of Clg

% of Nominal

240

60

275

69

300

75

325

81

350

88

375

94

400

100

425

106

450

113

475

119

500

125

520

130

Total Cap
0.922 0.944 0.959 0.971 0.982 0.992 1.000 1.007 1.012 1.017 1.019 1.020

Cooling

Sens Cap

Power

0.786 0.827 0.860 0.894 0.929 0.965 1.000 1.034 1.065 1.093 1.117 1.132

0.910 0.924 0.937 0.950 0.964 0.982 1.000 1.020 1.042 1.066 1.092 1.113

Heat of Rej
0.920 0.940 0.955 0.967 0.978 0.990 1.000 1.010 1.018 1.026 1.033 1.038

Htg Cap
0.943 0.958 0.968 0.977 0.985 0.993 1.000 1.007 1.013 1.018 1.023 1.026

Heating
Power
1.150 1.105 1.078 1.053 1.031 1.014 1.000 0.990 0.983 0.980 0.978 0.975

Heat of Ext
0.893 0.922 0.942 0.959 0.973 0.988 1.000 1.011 1.020 1.028 1.034 1.038
11/10/09

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

8

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Antifreeze Corrections
Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.

Antifreeze Type

Antifreeze % by wt

Cooling Capacity

Heating Capacity

Pressure Drop

EWT - degF [DegC]

90 [32.2]

30 [-1.1]

30 [-1.1]

Water

0

1.000

1.000

1.000

Ethylene Glycol Propylene Glycol Ethanol Methanol

10

0.991

20

0.979

30

0.965

40

0.955

50

0.943

10

0.981

20

0.969

30

0.950

40

0.937

50

0.922

10

0.991

20

0.972

30

0.947

40

0.930

50

0.911

10

0.986

20

0.970

30

0.951

40

0.936

50

0.920

0.973 0.943 0.917 0.890 0.865 0.958 0.913 0.854 0.813 0.770 0.927 0.887 0.856 0.815 0.779 0.957 0.924 0.895 0.863 0.833

1.075 1.163 1.225 1.324 1.419 1.130 1.270 1.433 1.614 1.816 1.242 1.343 1.383 1.523 1.639 1.127 1.197 1.235 1.323 1.399

Warning: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent.

Antifreeze Correction Example
Antifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F and 90°F respectively as well as pressure drop at 30°F for a Versatec Ultra Series UCV023 PSC.
The corrected cooling capacity at 90°F would be: 23,500 MBtuh x 0.969 = 22,772 MBtuh
The corrected heating capacity at 30°F would be: 16,000 MBtuh x 0.913 = 14,608 MBtuh
The corrected pressure drop at 30°F and 6 GPM would be: 10.5 feet of head x 1.270 = 13.34 feet of head

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

9

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Pressure Drop

Model 018 023 031 041

GPM
3.0 4.0 5.0 6.0 3.0 4.5 6.0 8.0 4.0 6.0 8.0 10.0 5.0 8.0 11.0 14.0

30°F 1.1 1.9 3.3 4.5 1.1 2.4 4.5 6.7 0.9 1.9 3.7 4.8 1.5 3.4 7.9 9.1

Pressure Drop (psi)

50°F

70°F

90°F

1.0

0.8

0.7

1.8

1.6

1.5

3.2

3.0

2.9

4.4

4.3

4.1

1.0

0.9

0.8

2.2

2.1

2.0

4.4

4.3

4.1

6.6

6.5

6.3

0.8

0.7

0.6

1.8

1.7

1.6

3.6

3.5

3.4

4.7

4.6

4.5

1.2

0.9

0.5

3.1

2.8

2.5

7.5

7.2

6.9

8.8

8.5

8.2

110°F 0.5 1.3 2.7 4.0 0.6 1.9 4.0 6.2 0.5 1.5 3.3 4.4 0.4 2.1 6.6 7.9 9/2/10

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

10

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

UCV018 - Performance Data

Single Speed PSC (600 CFM)

EWT Flow

°F

gpm

3.0

20

4.0

5.0

3.0

30

4.0

5.0

3.0

40

4.0

5.0

3.0

50

4.0

5.0

3.0

60

4.0

5.0

3.0

70

4.0

5.0

3.0

80

4.0

5.0

3.0

90

4.0

5.0

3.0

100

4.0

5.0

3.0

110

4.0

5.0

3.0

120

4.0

5.0

WPD

PSI

FT

1.2

2.8

2.0

4.6

3.4

7.8

1.1

2.6

1.9

4.4

3.3

7.6

1.1

2.5

1.8

4.3

3.2

7.5

1.0

2.3

1.8

4.1

3.2

7.3

0.9

2.1

1.7

3.9

3.1

7.1

0.8

1.9

1.6

3.7

3.0

6.9

0.8

1.8

1.5

3.6

2.9

6.8

0.7

1.6

1.5

3.4

2.9

6.6

0.6

1.4

1.4

3.2

2.8

6.4

0.5

1.2

1.3

3.0

2.7

6.2

0.5

1.1

1.2

2.9

2.6

6.1

HEATING - EAT 70°F

HC Power HE

LAT

kBtuh kW kBtuh °F

COP

Operation not recommended

13.0
14.5 14.9
15.7 16.5 16.0 17.0 18.0 17.5 18.5 19.5 19.0 20.0 21.0 21.9 22.6 23.3 24.7 25.1 25.5

1.21

8.9

88.1 3.15

Operation not recommended

1.29

10.1

90.3 3.29

1.31 10.4 91.0 3.33

Operation not recommended

1.34

11.1

92.2 3.43

1.37

11.8 93.4 3.52

1.36

11.4

92.7 3.45

1.40 12.2 94.2 3.57

1.43

13.1

95.8 3.69

1.43 12.6 95.0 3.60

1.45 13.5 96.5 3.73

1.48 14.5 98.1 3.86

1.49 13.9 97.3 3.74

1.51

14.8 98.9 3.88

1.53 15.8 100.4 4.02

1.56 16.5 101.7 4.10

1.58 17.2 102.8 4.17

1.61

17.8 103.9 4.25

1.64

19.1 106.2 4.43

1.66 19.5 106.8 4.44

1.68 19.8 107.4 4.45

Operation not recommended

HWC kBtuh

TC kBtuh

COOLING - EAT 80/67°F

SC

S/T Power HR

kBtuh Ratio kW kBtuh

EER

Operation not recommended

1.4

Operation not recommended

1.5

18.2

11.8

0.65 0.86

21.1

21.0

1.5

18.4 12.0 0.65 0.81 21.2 22.7

Operation not recommended

1.6

19.1

12.4 0.65 0.92 22.2 20.8

1.6

19.4 12.6 0.65 0.89 22.4 21.9

1.7

19.7 12.8 0.65 0.98 23.0 20.1

1.7

20.0 13.0 0.65 0.97 23.3 20.6

1.8

20.3

13.1 0.65 0.96 23.6

21.1

1.9

18.7 12.4 0.66 1.07 22.3 17.6

1.9

18.9 12.6 0.67 1.06 22.5 17.9

2.0

19.2

12.8 0.67 1.05 22.7 18.3

2.1

17.7

12.0 0.68 1.15

21.6 15.4

2.1

17.9

12.3 0.69 1.14

21.7

15.7

2.2

18.0 12.5 0.69 1.13

21.9 15.9

2.4

16.6

11.4 0.69 1.36

21.2

12.2

2.4

16.8

11.7 0.70 1.30 21.2

12.9

2.5

17.0 12.0 0.70 1.26 21.3

13.5

2.8

15.4 10.8 0.70 1.49 20.5 10.3

2.8

15.7

11.1

0.71 1.43 20.5 11.0

2.8

16.0

11.4

0.71

1.38 20.7

11.6

Operation not recommended

14.9

11.0 0.74 1.52

20.1

9.8

15.1

11.1

0.73 1.47

20.1 10.3

Operation not recommended

13.9 10.5 0.76 1.60 19.4

8.7

14.2 10.7 0.75 1.56 19.5

9.1

Operation not recommended

13.2

10.1 0.76 1.76 19.2

7.5

13.5 10.2 0.76 1.71

19.3

7.9

HWC kBtuh
-----
----0.9 0.9 0.9 1.1 1.1 1.0 1.3 1.3 1.2 1.7 1.6 1.5 2.2 2.0 1.9
2.5 2.3
3.2 3.0
4.0 3.6 9/2/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

11

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

UCV023 - Performance Data

Single Speed PSC (700 CFM)

EWT °F 20 30 40 50 60 70 80 90 100 110 120

Flow gpm
3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0 3.0 4.5 6.0

WPD

PSI

FT

1.2

2.8

2.4

5.6

4.6

10.6

1.1

2.6

2.4

5.5

4.5

10.5

1.1

2.5

2.3

5.3

4.5

10.3

1.0

2.3

2.2

5.2

4.4

10.2

1.0

2.2

2.2

5.0

4.3

10.0

0.9

2.0

2.1

4.9

4.3

9.9

0.8

1.9

2.1

4.7

4.2

9.7

0.8

1.7

2.0

4.6

4.1

9.6

0.7

1.6

1.9

4.4

4.1

9.4

0.6

1.4

1.9

4.3

4.0

9.3

0.6

1.3

1.8

4.1

3.9

9.1

HC kBtuh

HEATING - EAT 70°F

Power

HE

LAT

kW kBtuh

°F

COP

Operation not recommended

15.0
17.9 18.2
19.6 20.3 20.8 21.6 22.3 23.0 23.8 24.6 25.2 26.0 26.9 27.9 28.5 29.2 30.6 31.0 31.5

1.68

9.2

85.3

Operation not recommended

1.74

11.9

88.7

1.76

12.2

89.1

Operation not recommended

1.78

13.6

90.7

1.80

14.1

91.4

1.79

14.7

92.1

1.82

15.4

92.9

1.84

16.0

93.8

1.83

16.7

94.6

1.85

17.5

95.5

1.88

18.2

96.4

1.87

18.8

97.1

1.89

19.6

98.1

1.91

20.4

99.1

1.88

21.5

100.2

1.90

22.0

101.0

1.92

22.6

101.8

1.88

24.1

103.4

1.91

24.5 103.9

1.93

24.9 104.5

2.61
3.01 3.04
3.24 3.30 3.41 3.48 3.55 3.68 3.76 3.84 3.94 4.03 4.12 4.35 4.40 4.46 4.76 4.77 4.78

Operation not recommended

TC kBtuh

COOLING - EAT 80/67°F

SC kBtuh

S/T Ratio

Power HR kW kBtuh

EER

Operation not recommended

26.3 26.7
26.5 26.8 26.4 26.6 26.9 25.7 25.9 26.2 25.0 25.3 25.5 23.8 24.1 24.5 22.7 23.0 23.5
21.7 22.1
20.2 20.6
18.4 18.8

Operation not recommended

16.7

0.63

1.11

30.1

17.0

0.64

1.04

30.2

Operation not recommended

17.0

0.64

1.20

30.6

17.3

0.64

1.14

30.7

17.3

0.66

1.37

31.1

17.4

0.65

1.30

31.1

17.5

0.65

1.23

31.1

17.0

0.66

1.52

30.9

17.1

0.66

1.44

30.9

17.2

0.66

1.36

30.8

16.7

0.67

1.67

30.7

16.8

0.67

1.58

30.6

16.9

0.66

1.49

30.6

16.1

0.68

1.81

30.0

16.3

0.68

1.73

30.0

16.5

0.67

1.68

30.2

15.6

0.69

2.01

29.6

15.8

0.69

1.92

29.6

16.0

0.68

1.86

29.8

Operation not recommended

15.1

0.69

2.20

29.2

15.2

0.69

2.13

29.3

Operation not recommended

14.2

0.70

2.46

28.6

14.4

0.70

2.39

28.8

Operation not recommended

14.2

0.77

2.85

28.2

14.4

0.77

2.77

28.3

23.8 25.7
22.0 23.6 19.3 20.5 21.9 16.9 18.0 19.3 15.0 16.0 17.1 13.1 13.9 14.6 11.3 12.0 12.6
9.9 10.4
8.2 8.6
6.5 6.8 9/2/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

12

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

UCV031 - Performance Data

Single Speed PSC (1000 CFM)

EWT Flow

°F

gpm

4.0

20

6.0

8.0

4.0

30

6.0

8.0

4.0

40

6.0

8.0

4.0

50

6.0

8.0

4.0

60

6.0

8.0

4.0

70

6.0

8.0

4.0

80

6.0

8.0

4.0

90

6.0

8.0

4.0

100

6.0

8.0

4.0

110

6.0

8.0

4.0

120

6.0

8.0

WPD

PSI

FT

1.0

2.2

1.9

4.5

3.8

8.7

0.9

2.1

1.9

4.4

3.7

8.5

0.9

2.0

1.8

4.3

3.7

8.4

0.8

1.9

1.8

4.1

3.6

8.3

0.8

1.8

1.7

4.0

3.6

8.2

0.7

1.6

1.7

3.9

3.5

8.1

0.7

1.5

1.6

3.8

3.5

8.0

0.6

1.4

1.6

3.7

3.4

7.9

0.6

1.3

1.6

3.6

3.4

7.8

0.5

1.2

1.5

3.5

3.3

7.6

0.5

1.1

1.5

3.3

3.3

7.5

HEATING - EAT 70°F

HC Power HE

LAT

kBtuh kW kBtuh °F

COP

HWC kBtuh

TC kBtuh

COOLING - EAT 80/67°F

SC

S/T Power HR

kBtuh Ratio kW kBtuh

EER

HWC kBtuh

Operation not recommended

Operation not recommended

20.7 2.10 13.5 87.2 2.89

1.9

Operation not recommended

Operation not recommended

24.6 2.10 17.4 90.8 3.43

2.1

30.4 20.8 0.68 1.24 34.6 24.6

---

24.0 2.12 16.8 90.2 3.32

2.1

30.8 21.2 0.69 1.16 34.8 26.6

---

Operation not recommended

Operation not recommended

27.2 2.17 19.8 93.2 3.68

2.3 32.0 22.5 0.70 1.35 36.6 23.7

---

27.6 2.19

20.1 93.5 3.69

2.4

32.5 23.1

0.71 1.28 36.8 25.4

---

29.0 2.21 21.5 94.9 3.85 2.5

33.1 23.5 0.71 1.54 38.4 21.5

1.4

30.1 2.24 22.4 95.8 3.94

2.6

33.6 24.3 0.72 1.47 38.6 22.9

1.3

31.1 2.26 23.4 96.8 4.03 2.7

34.1 25.0 0.73 1.40 38.9 24.4

1.3

32.3 2.28 24.5 97.9 4.15

2.9

31.9 23.1 0.72 1.70 37.7 18.8

1.6

33.4 2.31 25.6 98.9 4.25 2.9 32.5 23.5 0.72 1.63 38.0 19.9

1.5

34.6 2.34 26.6 100.0 4.34 3.0

33.1 24.0 0.72 1.56 38.4 21.2

1.4

35.6 2.35 27.6 101.0 4.44

3.2

30.7 22.6 0.74 1.86 37.0 16.5

2.0

36.8 2.38 28.7 102.1 4.53

3.3

31.4 22.8 0.73 1.79 37.5

17.5

1.9

38.0 2.41 29.8 103.2 4.62 3.4 32.0 22.9 0.72 1.72 37.9 18.6

1.8

39.3 2.46 30.9 104.4 4.68

3.6

28.8 20.8 0.72 2.07 35.9 13.9

2.5

40.2 2.49 31.7 105.2 4.73

3.7

29.6 21.4 0.72 1.97 36.3 15.0

2.4

41.2 2.53 32.5 106.1 4.78

3.8

30.2 22.3 0.74 1.91

36.7 15.8

2.3

43.0 2.57 34.2 107.8 4.89

4.1

27.0 19.0 0.70 2.27 34.7 11.9

3.3

43.6 2.61 34.7 108.4 4.90

4.2

27.8 20.0 0.72 2.17 35.2 12.8

3.1

44.3 2.64 35.3 109.0 4.92

4.3 28.4 21.6 0.76 2.10 35.6 13.5

3.0

Operation not recommended

26.3 20.7 0.78 2.43 34.7 10.8

3.9

26.8 20.9 0.78 2.36 34.8 11.4

3.7

Operation not recommended

Operation not recommended

24.6 19.8 0.81 2.68 33.8 9.2

4.9

25.1 20.1 0.80 2.61 34.0 9.6

4.5

Operation not recommended

22.5 19.1 0.85 3.03 32.8 7.4

5.7

23.0 19.4 0.84 2.94 33.0 7.8

5.4

9/2/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

13

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

UCV041 - Performance Data

Single Speed PSC (1200 CFM)

EWT Flow

°F

gpm

5.0

20

8.0

11.0

5.0

30

8.0

11.0

5.0

40

8.0

11.0

5.0

50

8.0

11.0

5.0

60

8.0

11.0

5.0

70

8.0

11.0

5.0

80

8.0

11.0

5.0

90

8.0

11.0

5.0

100

8.0

11.0

5.0

110

8.0

11.0

5.0

120

8.0

11.0

WPD

PSI

FT

1.6

3.8

3.6

8.2

8.0

18.5

1.5

3.4

3.4

7.8

7.9

18.1

1.3

3.0

3.2

7.5

7.7

17.8

1.2

2.7

3.1

7.1

7.5

17.4

1.0

2.3

2.9

6.7

7.4

17.0

0.9

2.0

2.8

6.4

7.2

16.7

0.7

1.6

2.6

6.0

7.1

16.3

0.5

1.2

2.5

5.7

6.9

16.0

0.4

0.9

2.3

5.3

6.8

15.6

0.4

0.9

2.1

4.9

6.6

15.2

0.4

0.9

2.0

4.6

6.5

14.9

HEATING - EAT 70°F

HC Power HE

LAT

kBtuh kW kBtuh °F

COP

Operation not recommended

26.3
31.9 32.0
35.3 36.2 37.5 39.0 40.4 41.6 43.3 45.0 45.7 47.7 49.6 51.5 52.9 54.3 57.2 58.1 59.0

2.40 18.1 88.3 3.21 Operation not recommended 2.86 22.1 92.6 3.27 2.90 22.1 92.7 3.23 Operation not recommended 2.96 25.2 95.2 3.50 3.00 26.0 95.9 3.54 3.00 27.3 96.9 3.66 3.05 28.5 98.1 3.74 3.10 29.8 99.2 3.82 3.10 31.0 100.1 3.93 3.15 32.6 101.4 4.03 3.20 34.1 102.7 4.12 3.20 34.8 103.3 4.19 3.25 36.6 104.8 4.30 3.30 38.3 106.3 4.41 3.31 40.2 107.7 4.56 3.35 41.4 108.8 4.62 3.40 42.7 109.9 4.68 3.41 45.6 112.2 4.92 3.46 46.3 112.8 4.93 3.50 47.1 113.5 4.94

Operation not recommended

HWC kBtuh

TC kBtuh

COOLING - EAT 80/67°F

SC

S/T Power HR

kBtuh Ratio kW kBtuh

EER

HWC kBtuh

Operation not recommended

1.9

Operation not recommended

2.1

43.3 25.6 0.59 1.81 49.5 23.9

---

2.1

43.9 26.1 0.59 1.70 49.7 25.8

---

Operation not recommended

2.3

44.7 27.7 0.62 1.96 51.4 22.9

---

2.4

45.3 27.9 0.62 1.85

51.6 24.5

---

2.5

45.7 30.0 0.66 2.20 53.2 20.8

1.4

2.6

46.2 29.8 0.65 2.10 53.3 22.0

1.3

2.7 46.6 29.6 0.64 2.00 53.4 23.3

1.3

2.9 44.3 29.1 0.66 2.45 52.7 18.1

1.6

2.9 44.6 29.1 0.65 2.33 52.5 19.2

1.5

3.0

44.9 29.1 0.65 2.20 52.4 20.4

1.4

3.2

42.9 28.1 0.66 2.70 52.1

15.9

2.0

3.3

43.1 28.3 0.66 2.55 51.8 16.9

1.9

3.4 43.2 28.5 0.66 2.40 51.4 18.0

1.8

3.6

40.1 26.5 0.66 2.92 50.1

13.7

2.5

3.7

40.8 24.2 0.59 2.79 50.3 14.6

2.4

3.8

41.3 26.8 0.65 2.70 50.5 15.3

2.3

4.1

37.3 24.9 0.67 3.25 48.4 11.5

3.3

4.2 38.5 20.0 0.52 3.10 49.1 12.4

3.1

4.3 39.3 25.1 0.64 3.00 49.5 13.1

3.0

Operation not recommended

36.8 24.1 0.66 3.46 48.6 10.6

3.9

37.4 24.4 0.65 3.35 48.8 11.2

3.7

Operation not recommended

34.8 23.3 0.67 3.80 47.8

9.1

4.9

35.5 23.6 0.66 3.70 48.1

9.6

4.5

Operation not recommended

32.4 22.3 0.69 4.22 46.8

7.7

5.7

33.1 22.6 0.68 4.10 47.1

8.1

5.4

9/2/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

14

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Wiring Schematic

Versatec Microprocessor 208-230/60/1 PSC

PSC Blower Motor Grn
Brn Wht
Cap 3 Airflow Settings
HM L
White

Compressor S
Blue Cap
Tan

C

R Red

Black

T2

T1

CC

L2

L1

Note 2 Green (93)

Ground
Neutral Disconnect

Black (95)

L1

L1

Black

RB

3

1

Black

Red (97)

L2

L2

L3

L3

Unit Power Supply 208-230-265/60/1
G

P3 P3 P1
R C Y O G/Y2 LO ES NS LS

Note 2

Red 208V

Blue

230V

Black

265V

Transformer

RB Violet Black/White

Yellow

Legend

Factory Low Voltage Wiring

Factory Line Voltage Wiring

T

Field Low Voltage Wiring

Field Line Voltage Wiring

Optional Block

DC Voltage PCB Traces

Field Zone Sensor Wiring

Internal Junction

Quick Connect Terminal

L1

Field Wiring Lug

Ground
Relay Contacts­ N.O., N.C.
CC ­ Compressor Contactor CO ­ Condensate Overflow Sensor ES ­ Emergency Shutdown HP ­ High Pressure Switch LP ­ Low Pressure Switch FD ­ Freeze Detection Sensor RB ­ Blower Relay RV ­ Reversing Valve Coil

1 2 3

Thermistor Relay Coil Switch - Condensate Overflow Switch - High pressure Switch - Low pressure
Polarized connector
Capacitor

LED Display Mode Table

Status Display Mode

LED SW1-4 On , SW2 Off

Drain Drain Pan Overflow Lockout

Water Flow Freeze Detection Lockout(Loop <= 15°F, Well <= 30°F)

High Press. High Pressure Lockout

Low Press. Low Pressure Lockout

Air Flow Not Used

Status Microprocessor Malfunction*

DHW Limit Not Used

DHW SW2 Status(Off =Down Position, On=Up Position)

Diagnostic Display Modes

Current Fault Display Mode

Inputs Display Mode

LED

SW1-4 On, SW2 On

SW1-4 Off, SW2 Off

Drain Drain Pan Overflow Lockout

Y

Water Flow Freeze Detection Lockout

G

High Press. High Pressure Lockout

O

Low Press. Low Pressure Lockout

ES

Air Flow Not Used

NS

Status Not Used

LS

DHW Limit Not Used

Not Used

HWD SW2 = On

SW2 = Off

* Flashing Status Light Indicates the Board is Functioning Prope.rly A Solid "On" Indicates a Board Malfunctio. n

Outputs Display Mode SW1-4 Off, SW2 On Compressor Blower Reversing Valve ES NS LS Not Used SW2 = On

Black/White

CC Violet Violet
Green (000)

Fan

Fan COM

CC CCG
C C R R

SW1 On

Test Loop Comm. T-Stat Inputs/Outputs Split Mode

Normal Well Normal Status Normal

P2 1-HP 6-HP 2-LP 7-LP
3 8-CO 4-RV 9-RV 5-FP 10-FP

HP Black Black
LP Blue Blue

CO Brown

Orange RV

Orange

Yellow

T

FD

Yellow

Black Black
Black

Drain

R

Water Flow R

High Press. R

Low Press. R

Air Flow R

Status

G

DHW Limit Y

HWD

R

OFF

SW2

ON

Mode Htg Clg Blower Only

Operational Logic Table

Single-Speed

Inputs

Blower

Comp

Y

Auto

ON

Y,O

Auto

ON

G

ON

OFF

Notes:
1 ­ Optional, factory installed unit mounted disconnect. 2 ­ Swap blue and red leads for 208V operation

Control Timing Table

Event

Normal Mode

Test Mode

Power On Delay

5 minutes

15 seconds

Compressor On Delay

10 seconds

2 seconds

Compressor Minimum On Time

2 minutes

5 seconds

Compressor Short Cycle Delay

5 minutes

15 seconds

Blower Off Delay

30 seconds

5 seconds

Fault Recognition Delay ­ High Pressure

Less than 1 second Less than 1 second

Start-Up Bypass­ Low Pressure

2 minutes

0 seconds

RV

Fault Recognition Delay ­ Low Pressure

30 seconds

30 seconds

OFF

Start-Up Bypass­ Freeze Detection

2 minutes

0 seconds

ON

Fault Recognition Delay ­ Freeze Detection

30 seconds

30 seconds

OFF

Fault Recognition Delay ­ Condensate Overflow 30 seconds

30 seconds

Factory Setup DIP Switches(SW1)

DIP Switch Number

Description

SW1- 1

Service Test Mode On the contro,l allows field selection of"NORMAL" or "TEST" operational modes, Test mode accelerates most timing function1s6 times to allow faster troubleshootin.gTest mode also allows viewing the"CURRENT" status of the fault inputs on the LED display.

"OFF" Position

"ON" Position

Test Mode

Normal Speed Operation

SW1- 2 SW1- 3 SW1- 4

Freeze Detection Setting This DIP switch allows field selection of low source water thermistor fault sensing for "WELL" water (30°F) or "LOOP" (15°F)for anti-freeze protected earth loop.s
Not Available I/O Display Mode This DIP switch enables Input/Output Display or Status/Current Fault on LED Boar.d Refer to SW2 for operation and positioning.

"LOOP" (15°F)
N/A

"WELL" (30°F)
Normal Operation

Input/Output Status/Current Display Mode Fault Display Mode

SW1- 5 SW2

Not Available

N/A Normal Operation

Page 1 LED Display(On LED Board)

This DIP switch enables Normal Status or Input display mode in the "OFF" position and Status or Inputs

Current Fault or Output display mode in the "ON" position.

Display Mode

Current Fault or Output Display
Mode

97P800-02 09/02/10

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

15

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Engineering Guide Specifications

General
Furnish and install WaterFurnace Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow. The reverse cycle heating/ cooling units shall be vertical upflow air discharge. Units shall be AHRI/ISO 13256-1 certified and listed by a nationally recognized safety-testing laboratory or agency, such as ETL Testing Laboratory. Each unit shall be computer runtested at the factory with conditioned water and operation verified to catalog data. Each unit shall be mounted on a pallet and shipped in a corrugated box or stretch-wrapped. The units shall be designed to operate with entering liquid temperature between 20°F and 120°F [-6.7°C and 48.9°C].
Casing and Cabinet
The cabinet shall be fabricated from heavy-gauge galvanized steel and finished with optional corrosionresistant powder coating. This corrosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117. The interior shall be insulated with 1/2 in. thick, multi-density, cleanable aluminum foil coated glass fiber with edges sealed or tucked under flanges to prevent the introduction of glass fibers into the discharge air. Standard cabinet panel insulation must meet NFPA 90A requirements, air erosion and mold growth limits of UL-181, stringent fungal resistance test per ASTM-C1071 and ASTM G21, and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not be accepted.
One (horizontal) to two (vertical) blower and two compressor compartment access panels shall be `lift-out' removable with supply and return ductwork in place.
A duct collar shall be provided on the supply air opening. Standard size 1 in. [2.54 cm] MERV 4 filters shall be provided with each unit. Units shall have a return air filter rack that is field convertible from 1 in. [2.54 cm] to 2 in. [5.1 cm]. The upflow vertical units shall have a removable insulated divider panel between the air handling section and the compressor section to minimize the transmission of compressor noise and to permit operational service testing without air bypass. Vertical units shall be supplied with left or right horizontal air inlet and top vertical air discharge.
The compressor shall be mounted using selected durometer grommets to provide vibration free compressor mounting.

Refrigerant Circuit
All units shall utilize the non-ozone depleting and low global warming potential refrigerant R-410A. All units shall contain a sealed refrigerant circuit including a hermetic motorcompressor, bidirectional thermostatic expansion valve, finned tube air-to-refrigerant heat exchanger, reversing valve, coaxial tube water-to-refrigerant heat exchanger, optional hot water generator coil, and service ports.
Compressors shall be high-efficiency single speed rotary or scroll type designed for heat pump duty and mounted on vibration isolators. Compressor motors shall be single-phase PSC with overload protection.
The air coil shall be sized for low-face velocity and constructed of lanced aluminum fins bonded to rifled copper tubes in a staggered pattern not less than three rows deep for enhanced performance.
Option: FormiShield electro-coated air coil for maximum protection against formicary corrosion.
The coaxial water-to-refrigerant heat exchanger shall be designed for low water pressure drop and constructed of a convoluted copper (cupronickel option) inner tube and a steel outer tube. Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled copper tube construction rated to withstand 600 PSIG (4135 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG (4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure. The thermostatic expansion valve shall provide proper superheat over the entire liquid temperature range with minimal "hunting." The valve shall operate bidirectionally without the use of check valves.
Option: Cupronickel refrigerant to water heat exchanger shall be of copper-nickel inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG (4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure. Water lines shall also be of cupronickel construction.
Option: Hot water generator - Internal double wall vented hot water generator coil refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tube design, rated to withstand 600 PSIG (4135 kPa) working refrigerant pressure and 450 PSIG (3101 kPa) working water pressure.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

16

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

Engineering Guide Specifications cont.

Option: ThermaShield coated water-to-refrigerant heat exchanger, water lines and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures below 50°F.
Blower motor and Assembly
The blower shall be a direct drive centrifugal type with a dynamically balanced wheel. The housing and wheel shall be designed for quiet low outlet velocity operation. The blower housing shall be removable from the unit without disconnecting the supply air ductwork for servicing of the blower motor. The blower motor shall be isolated from the housing by rubber grommets. The motor shall be permanently lubricated and have thermostatic overload protection.
Option: PSC blower motor shall be a three-speed PSC type.
Electrical
A control box shall be located within the unit compressor compartment and shall contain a 75VA transformer, 24 volt activated, 2 pole compressor contactor, terminal block for thermostat wiring and solid-state controller for complete unit operation. Electromechanical operation WILL NOT be accepted. Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be 24 volt and provide heating or cooling as required by the remote thermostat/sensor.
A Versatec microprocessor-based controller that interfaces with a multi-stage electronic thermostat to monitor and control unit operation shall be provided. The control shall provide operational sequencing, blower speed control, high and low pressure switch monitoring, freeze detection, condensate overflow sensing, lockout mode control, LED status and fault indicators, fault memory, field selectable options and accessory output. The control shall provide fault retry three times before locking out to limit nuisance trips.
A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal.

Piping
Supply and return water connections shall be FPT copper fittings fixed to the corner post, which eliminate the need for backup pipe wrenches.
With vertical units, the condensate connection shall be a 3/4 in. [19.1 mm] PVC socket with internally-trapped hose that can be routed to front or side corner post locations.
Accessories
Thermostat (field-installed) A multi-stage auto-changeover electronic digital thermostat shall be provided. The thermostat shall offer two heating stages and one cooling stage with precise temperature control. An OFF-HEAT-AUTO-COOL-EMERG system switch, OFF-AUTO blower switch, and indicating LEDs shall be provided. The thermostat shall display in °F or °C.
Hose Kits ­ Ball Valves (field-installed) A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A full port ball valve shall be provided with integral P/T (pressure/temperature) port on supply hose. Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C]. · Max. working pressure of 400 psi [2757 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi [kPa] for 1 in. and 1-1/4 in. hose kits.
Hose Kits ­ Automatic Balancing and Ball Valves (field-installed) A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A full port ball valve shall be provided with integral P/T (pressure/temperature) port on supply hose and automatic balancing valve with integral P/T ports and full port ball valve on return hose.

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

17

Page _____ of _____

Contractor: Engineer: Project Name:

P.O.: Unit Tag:

Engineering Guide Specifications cont.
Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C] · Max. working pressure of 400 psi [2757 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi [2413 kPa] for 1 in. and 1-1/4 in. hose kits · Minimum burst pressure of four times working pressure
Hose Kits ­ Automatic Balancing and Ball Valves with `Y' strainer (field-installed) A flexible steel braid hose featuring Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid and fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). Ball valve at one end; swivel connector with adapter at the other end (swivel to adapter connection via fiber or EPDM gasket). Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules. A "y" strainer is provided on one end for fluid straining and integral "blowdown" valve. A full port ball valve shall be provided with integral P/T (pressure/temperature) port on supply hose and automatic balancing valve with integral P/T ports and full port ball valve on return hose.
Specifications: · Temperature range of 35°F [2°C] to 180°F [82°C] · Max. working pressure of 400 psi [2756 kPa] for 1/2 in.
and 3/4 in. hose kits; max. working pressure of 350 psi [2413 kPa] for 1 in. and 1-1/4 in. hose kits · Minimum burst pressure of four times working pressure

Versatec Ultra Series UCV Commercial 1.5 - 3.5 Tons 60Hz

WaterFurnace works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifications. Purchaser's approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace's opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

SD1220AU 09/10

18