INSTALLATION AND SERVICE MANUAL
COMMERCIAL ELECTRIC WATER HEATERS 52, 82, 119 Gallon, 9 kW - 54kW Input Models

SHP-I&S-02

3. Water heater corrosion and component failure caused by air-borne chemical vapors is not covered under the manufacturer's warranty.

4. Corrosion damage caused by current leakage due to improper grounding of electrical systems or electronic components to the storage tank and related piping is not covered by the manufacturer's warranty.

5. Under no circumstance will the manufacturer be liable for consequential damages resulting from the installation or use of this equipment.

6. Correct installation procedure and local codes must be adhered to.

SPECIAL INSTRUCTIONS TO OWNER

FIG. 1 Front View Vertical Round Models
Installation and service must be performed by Qualified Service Personnel Only.

NOTE: Retain this manual for future reference.
This manual supplies information for the installation, operation and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation.

WARRANTY

 WARNING:

Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.

IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency or the electric utility.

1. Excessive water hardness causing a lime/scale build-up in the heater and/or on the immersion heating elements is not the fault of the equipment and is not covered under the manufacturer's warranty. (See Water Treatment and Water Chemistry)
2. Do not energize electrical system before the heater is completely filled with water. Damage caused to the immersion heating elements by dry fire is not covered under the manufacturer's warranty. Follow start up procedure in the manual.

CHECKING EQUIPMENT
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the water heater, which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on packing slip with those actually received. In case there is damage or a shortage, immediately notify carrier.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. THE POSSIBLE DAMAGE TO A FLOODED APPLIANCE CAN BE EXTENSIVE AND PRESENT NUMEROUS SAFETY HAZARDS. ANY APPLIANCE THAT HAS BEEN UNDER WATER MUST BE REPLACED.

1

CONTENTS
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Checking the Equipment . . . . . . . . . . . . . . . . . . . . . . . . .1 Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Installation Requirements Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Drain Pan Requirements . . . . . . . . . . . . . . . . . . . . . . . . .3 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Water Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Tank Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Cathodic Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Electrical Service Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Wire Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Jacket Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Standard and Optional Controls . . . . . . . . . . . . . . . . . . .7 Components and Controls Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Fuses and Fuse Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Surface Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Immersion Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Temperature Regulation . . . . . . . . . . . . . . . . . . . . . . . . .10 Risk of Scald Warnings . . . . . . . . . . . . . . . . . . . . . . . . . .10 Temperature Limit Control . . . . . . . . . . . . . . . . . . . . . .11 Immersion Heating Elements . . . . . . . . . . . . . . . . . . . .12 Start-Up Procedure Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Filling the Water Heater . . . . . . . . . . . . . . . . . . . . . . . . .12 Start-Up Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Shutdown Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Maintenance T&P Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Water Chemistry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Flushing the Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Sediment Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Scale Removal - Elements . . . . . . . . . . . . . . . . . . . . . . . .15 Trouble Shooting Not Enough Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . .16 Water Is Too Hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Water Heater Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

 WARNING:
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
 OWNER WARNING:
The information contained in this manual is intended for use by qualified professional installers, service technicians or the electric utility. Consult your local expert for proper installation or service procedures.
IMPORTANT:
Consult and follow local Electrical Codes, Building and Fire Regulations and other Safety Codes that apply to this installation. Consult local codes officials and electric utility company to authorize and inspect all field installed electrical connections.
 CAUTION
Be sure to turn off power when working on or near the electrical system of the water heater. Never touch electrical components with wet hands or when standing in water. When replacing fuses, always use the correct size for the circuit. Do not test electrical system before the water heater is completely filled with water. Follow the start-up procedure.
 WARNING:
To minimize the possibility of serious personal injury, fire or damage to your appliance, never violate the following safety rules.
1. Always keep the area around your appliance free of combustible materials, gasoline, and other flammable liquids and vapors.
2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the access to your appliance.

2

CODES
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Electrical Code, NFPA 70. When the appliance is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.
APPROVALS
This complete appliance is design certified and Listed by Underwriters Laboratories as a commercial storage electric water heater. This water heater bears the UL certification for the United States as tested under the Standard for Electric Booster and Commercial Storage Tank Water Heaters, UL1453 and C-UL in Canada as tested under the Standard for Construction and Test of Electric Storage Tank Water Heaters, CAN/CSA-C22.2 No. 110-M90.

6. The floor on which the appliance is installed must be capable of supporting the total weight of the water heater when completely filled with water. Combustible floor locations may be used. Maintain required clearances from combustible surfaces.
7. The appliance must not be installed on carpet.
8. The appliance must be installed indoors where it is protected from exposure to wind, rain and weather.
9. Locate the appliance as close as possible to the point of major hot water usage, the water piping and branch electrical circuit wiring.
10. Insulate water piping to control heat loss and possible condensation.
11. The appliance must be located in an area that is not subject to freezing. The ambient temperature of the space where the appliance is installed must not go below 32°F (0°C) or above 104°F (40°C).

INSTALLATION PROCEDURE

 CAUTION

LOCATION OF UNIT
1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit, or any of its components.

2. Insure that the appliance is located near an acceptable

drain so that the vessel can be properly drained when

performing service or maintenance. The drain must

a

l

s

o

provide adequate drainage in the event of leakage from

the tank or related piping. The drain must prevent water

damage to the adjacent area and lower floors of the

structure.

This water heater, as well as all water heaters will eventually leak. Installation of the water heater should be accomplished in such a manner that if the tank, piping or any connections should leak, the flow of water will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be avoided, a suitable drain pan must be installed under the water heater. Drain pans may be fabricated or purchased from your plumbing wholesaler. The drain pan must be piped to an adequate drain. Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater.

3. The appliance must be installed so that the electrical components are protected from water (dripping, spraying, etc.) during appliance operation and service (replacing of fuses, elements, etc.)

4. Appliances located in a garage or parking structure shall be installed so that the jacket and all piping shall be located or protected so that it is not subject to physical damage by a moving vehicle.

5. The appliance must be installed on a level floor. Shim the base as necessary if leveling is required.

3

CLEARANCES FROM COMBUSTIBLE CONSTRUCTION

MOUNTING
The water heater should be mounted to the floor following applicable architectural and local code requirements or accepted standards for the specific site and model purchased. In areas prone to seismic activity, it is recommended that the water heater be mounted to the floor according to recommended procedures for the site. In some geographic areas, additional strapping or braces may be required, consult local codes for specific requirements. Proper mounting will help to make the water heater less susceptible to seismic damage.
WATER CONNECTIONS

FIG. 2 Clearances from Combustible Construction

TABLE - A CLEARANCES FROM COMBUSTIBLE CONSTRUCTION:
Right Side - 0" Rear - 0" Left Side - 0" Front - 18" (45cm) for service access to controls and heating elements Top - 12" (30cm) suggested for service access to piping and water connection Hot Water Pipes 1" (25.4mm)
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the electrical components, water pipe connections, piping and other auxiliary equipment, as well as the appliance.
Multiple appliances may be installed in a modular water heater installation. Multiple appliances may be installed side by side with no clearance between the sides of adjacent appliance. This appliance is approved for zero clearance from side combustible surfaces and no service access is required from the sides on most models.

FIG. 3 Water Connections
NOTE:
Before making any connections to the cold water inlet or hot water outlet, insure that all piping is clean and free of material or scale. This can usually be accomplished by "blowing out the pipe." Any foreign material or scale entering the water heater can adversely affect operation and performance.
NOTE:
When using copper tubing, solder tubing to an adapter before attaching to the threaded nipple connection provided on the water heater. Soldering directly to the threaded connection may harm a lining in the nipple or damage the tank lining.

4

INLET AND OUTLET CONNECTIONS
For ease of service, install unions on the cold water inlet and hot water outlet of the water heater. The cold water inlet connection is located on the lower left front side of the water heater. A manual shutoff valve should be installed upstream on the cold water source as an isolation device. The hot water outlet connection is located on the top center of the water heater. A manual shutoff valve should be installed downstream on the hot water outlet source as an isolation device in case the water heater must be disconnected from the system.
STORAGE TANK
This appliance uses a glass lined steel storage tank to store the heated water for use. The storage tank is constructed in accordance with the requirements of the Underwriters Laboratory Listing for a commercial electric water heater. The tank is furnished with threaded connections for cold water inlet, hot water outlet, a relief valve and a drain connection. The storage tank has a hand hole for ease of inspection, cleanout and service. The interior of the storage tank is glass lined and fired to 1600°F (871°C) to insure a molecular fusing of glass and steel to protect the steel base metal against corrosion. A magnesium anode is standard to help prevent dissipation of the tank material by electrolytic action.
RELIEF VALVE
This water heater is supplied with a temperature and pressure relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV. Some water heaters may be supplied with an optional pressure only relief valve. The relief valve(s) is installed in the vertical position and mounted in the tapping provided in the storage tank. No valve is to be placed between the relief valve, and the water heater. To prevent water damage, the discharge from the relief valve must be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year. A relief valve that fails to completely reseat and continues to discharge water must be immediately replaced with a new, properly sized, temperature and pressure relief valve.

 CAUTION
Avoid contact with hot discharge water. Insure that no one is in front of or around the relief valve discharge line. Make sure that the extremely hot water manually discharged from the relief valve will not cause bodily injury or property damage.
THERMAL EXPANSION OF WATER
A relief valve that discharges periodically may be due to thermal expansion in a closed system. Many water systems are equipped with pressure reducing valves, check valves or back flow preventers which may cause the water system to be closed. As water is heated it will expand in volume due to thermal expansion. The system must make allowance for this expansion. If an expansion tank is not provided in the system, water pressure may increase to the point where the water heater's temperature and pressure relief valve opens to relieve the excess pressure. The temperature and pressure relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected. Do not plug or cap the relief valve discharge! A properly sized expansion tank is typically installed in the potable water system to relieve the pressure built up by thermal expansion of heated water. Consult your local plumbing contractor and plumbing wholesaler for assistance in properly selecting an expansion tank for your system.
As the water heater operates, there may be noises generated by the expansion and contraction of the metal parts of the water heater and related piping. These noises may occur during periods of heat up or cool down. They do not represent harmful or dangerous conditions.
CATHODIC PROTECTION
Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be open for several minutes at a sink close to the water heater before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the hot water begins to flow. There should be no smoking or open flames near the faucet at the time it is open.

5

ELECTRICAL CONNECTIONS
All installation procedures involving electric power connection should only be performed by a trained, certified electricians.

1. Use copper conductors only. All wiring between the appliance and field installed devices shall be made with copper wire suitable for at least 167°F (75°C) temperature rating. If the wiring from an old water heater installation was aluminum, replace the old wire with copper wire.

2. The factory internal wiring is attached to a terminal block inside the unit. The branch circuit is connected to the terminal block through an opening provided on the top of the water heater electrical access panel.

3. Line voltage wire exterior to the appliance must be enclosed in approved conduit or approved metal clad cable.

4. To avoid serious damage, DO NOT energize the appliance until the system is full of water. Ensure that all air is removed from the storage tank and piping before beginning initial operation. Operation of a water heater without a completely filled tank may result in serious damage to the appliance and heating element burn out.

FIG. 4 Electric Power Connections - Electrical Control Panel
 WARNING:
WATER HEATER IS EQUIPPED FOR OPERATION ON ONE VOLTAGE ONLY. Check the rating plate on the front of the control panel access for the correct voltage and phase. DO NOT use this water heater with any other voltage other than the voltage specified on the rating plate. Failure to use the correct voltage can cause problems that can result in death, serious bodily injury or property damage.
CAUTION
DO NOT CONNECT THE WATER HEATER TO AN IMPROPER SOURCE OF ELECTRICITY!
The appliance, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements, with the latest edition of the National Electrical Code, NFPA No. 70. When the appliance is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.

5. The water heater should be connected with a separate grounded branch circuit with over current protection and disconnect switch. The water heater should be grounded in accordance with national and local codes. A ground terminal is provided for ground connection only.
6. Provide the appliance with proper overload protection in the branch circuit. It is suggested that the electrician size the branch circuit at 125 percent of the heater ampere rating and further increase wire size as necessary to compensate for voltage drop in long runs. Branch circuit voltage drop should not exceed 3% at the heater.
7. Voltage applied to the heater should not vary more than +5% to -10% of the model and rating plate marking for satisfactory operation.
8. A wiring diagram is provided with the water heater for the electricians use.
CAUTION
Never turn on the electric power or attempt to use this electric water heater unless it is completely full of water. Water must flow from the hot water faucet before turning electrical power "ON." Operation of a water heater without a completely filled tank may result in serious damage to the appliance and heating element burn out.

6

JACKET ASSEMBLY
Outer Jacket - The outer jacket assembly is constructed from heavy gauge steel. The exterior surface is specially prepared and phosphate coated to allow application of a multiple coat enamel paint process. This coating process insures a long life from the jacket assembly.
STANDARD EQUIPMENT
Your commercial electric water heater is equipped with the following as standard equipment.

· Underwriter's Laboratories, Inc. listing for all models as a commercial electric water heater.
The following items are available as extra cost options.
· Immersion thermostats with magnetic contactors
COMPONENTS AND CONTROLS

· Low watt density immersion heating elements with a copper sheath and a tin plate.

· Internal fusing of all element power circuits is provided when current draw is in excess of 48 amps

· Fused power circuits provided in increments of a maximum 48 amps for additional safety.

· Fuse cartridges are rated at 1,000,000 amps interrupting capacity.

· A fully painted heavy gauge steel outer jacket and electrical control panel are provided.

· Electrical control panel is provided with a hinged door.

· A glass lined steel tank constructed to standard specifications and provided with a magnesium anode.
· ASME rated temperature and pressure relief valve provided by factory to insure safe heater operation.
· Terminal block connections are installed by the factory for safe easy wiring connection.

FIG. 5 Electrical Control Panel Component Location Drawing
TERMINAL BLOCK

· Manual reset high water temperature limit control.

· Surface mount thermostats (one per each immersion heating element).

· 180°F temperature operation is possible to provide water for sanitizing applications.

· Insulated to meet latest edition of ASHRAE 90.1 energy efficiency standards.

· 3 year limited warranty provides protection against failure of tanks due to defects in material and workmanship in commercial application.

FIG. 6 Main Power Terminal Block

7

A main power terminal block is provided for field connection of the branch power supply to the electric water heater. All internal power circuits to the immersion heating elements are connected to the load side of the main terminal block. The line side of the terminal block has individual lug type connections properly sized for the recommended copper field wire size.
FUSES AND FUSE BLOCKS

SURFACE THERMOSTATS WITH HIGH LIMIT

FIG. 8 Surface Thermostat/High Limit

 WARNING:

FIG. 7 Fuse Block with Power Circuit Fuses
The internal power circuits of a water heater with a current draw in excess of 48 amps are fused for safety. Each power circuit to an immersion element is fused at a maximum of 48 amps. Power circuits may be fused at lower current levels as needed to balance current on three phase units. The power circuit fuses are held by a spring loaded fuse block rated for the voltage specified to operate the water heater.
When the immersion thermostat and contactor option is provided, the control circuit is also fused on the primary side of the control circuit transformer.

HAZARD OF ELECTRICAL SHOCK - Before opening the electrical access panel to adjust the thermostat or servicing the water heater, make sure the electrical supply to the water heater is turned "OFF". Failure to do this could result in death, serious bodily injury or property damage.
The standard control system uses an individual surface mounted snap action thermostat with high limit for each heating element. The thermostat/high limit is mounted firmly against the tank, directly above each heating element. The surface thermostat has an adjustable temperature setting that can be varied from 110°F (43.3°C) up to 180°F (82.2°C) at the highest setting. Turn off all electrical power to the water heater before attempting to adjust the thermostats. The temperature setpoint adjustment is made on each thermostat by using a screwdriver. All surface thermostats may be set at the same temperature or they may be set a 2° to 4°F (1° to 2°C) apart to step the elements on in stages. There is a blanket of fiberglass insulation installed over the heating elements and surface thermostats. This insulation must be removed before the thermostats can be adjusted. Each thermostat has a plastic cover installed to prevent accidental contact with power wires when adjusting the set point. This cover has an opening to allow temperature adjustment and resetting of the high limit. The cover does not have to be removed. The high water temperature limit control which is part of each thermostat assembly contains a manual reset on high water temperature.

8

The limit is reset by pushing the red reset button on the limit. Operation of the limit control usually indicates a major problem with the heating elements or temperature control. Do not continue to push the reset multiple times. The problem causing the reset to function must be found and corrected to insure proper operation. The blanket of fiberglass insulation must be replaced over the surface thermostats and immersion heating elements before the power is turned on and the heater is returned to service.
CONTACTORS

CONTROL CIRCUIT TRANSFORMER

FIG. 10 Control Circuit Transformer

FIG. 9 Magnetic Contactor

When the immersion thermostat and contactor option is provided, a transformer is used to reduce the line voltage to 120 VAC for internal control operation. The transformer is fused on the primary side. The VA rating of the control circuit transformer is based on the load of the various components in the water heater control circuit.
IMMERSION THERMOSTAT(S)

When the immersion thermostat and contactor option is provided, the power to the immersion electric heating elements is switched by a definite purpose magnetic contactor. The contactor is supplied with 120 VAC from the control circuit when the immersion thermostat senses a drop in stored water temperature below the desired set point. A magnetic coil in the contactor is energized to complete the electric circuit supplying power to the immersion heating elements. When the thermostat is satisfied, the contactor coil is de-energized and power to the heating elements is turned off.

FIG. 11 Immersion Thermostat

9

 WARNING:
HAZARD OF ELECTRICAL SHOCK - Before opening the electrical access panel to adjust the thermostat or servicing the water heater, make sure the electrical supply to the water heater is turned "OFF". Failure to do this could result in death, serious bodily injury or property damage.
As a control option, the water heater may be provided with an immersion thermostat(s) to activate magnetic contactors allowing current to flow to the immersion heating elements. The immersion thermostat option may use up to one immersion thermostat for each 36kW of electric heating power in a water heater. The sensing bulb for each immersion thermostat is immersed in the stored water in the tank to provide quick, accurate response to changes in water temperature. The thermostat sensing bulb is located in the tank just above the elements it is controlling. The immersion thermostat set point is adjustable by rotating a knob on the control. Turning the knob counter clockwise decreases the temperature set point and turning the knob clockwise increases the set point. The temperature setting shown at the top of the knob is the selected set point. The immersion thermostat has a fixed 6°F (3.3°C) differential.
TEMPERATURE REGULATION

Allow a few days of operation at the setting to determine the correct temperature setting consistent with your needs.
NOTE:
(1) This water heater, when set at the lower temperature setting, is not capable of producing hot water of sufficient temperature for sanitizing purposes. (2) Higher stored water temperature increases the ability of the heater to supply desired quantities of hot water, however remember:
 CAUTION
Hotter water increases the risk of scald injury.
 CAUTION
Setting the temperature selector dial higher provides hotter water, which increases the risk of scald injury.

 WARNING:

WARNING! HAZARD OF ELECTRICAL SHOCK Before opening the electrical access panel to adjust the thermostat, make sure the electrical supply to the water heater is turned "OFF".
 DANGER
Full power is present whenever the cabinet door is opened.
Set temperature control to the lowest setting which satisfies the hot water requirements of the system. Lower water temperatures help minimize scale formation on the heating elements. See thermostat information below.
WATER TEMPERATURE SETTINGS
This water heater has an adjustable thermostat(s) to control water temperature. The thermostat is factory pre-set at approximately 125°F (51.7°C) or less. Households with small children or invalids may require a 120°F (48.9°C) or lower temperature setting to reduce risk of scald injury. Some states may require a lower temperature setting. Check with your local codes or electric utility for local requirements governing the temperature setting. Remember, no water heating system will provide exact temperatures at all times.

FIG. 12 Hot Water Danger Label
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.

APPROXIMATE TIME / TEMPERATURE RELATIONSHIPS IN SCALDS

120°F

More than 5 minutes

125°F

1 1/2 to 2 minutes

130°F

About 30 seconds

135°F 140°F 145°F 150°F 155°F

About 10 seconds Less than 5 seconds Less than 3 seconds About 1 1/2 seconds
About 1 second

10

 WARNING:
SHOULD OVERHEATING OCCUR OR THE TEMPERATURE CONTROLS FAIL TO SHUT OFF, TURN OFF OR DISCONNECT THE ELECTRICAL SUPPLY AT THE MAIN POWER DISCONNECT, EXTERNAL TO THE APPLIANCE.

HIGH WATER TEMPERATURE LIMIT CONTROL

 DANGER
· Water temperature over 125°F (51.7°C) can cause severe burns instantly or death from scald.

· Children, disabled and elderly are at highest risk of being scalded.

· See instruction manual before setting temperature at heating appliance.

· Feel water before bathing or showering.

· If this appliance is used to produce water that could scald if too hot, such as domestic hot water use, adjust the outlet control (limit) or use temperature limiting valves to obtain a maximum water temperature of 125°F (51.7°C).
Always close the electrical control panel door after making a temperature adjustment. Turn on electricity.
TEMPERATURE ADJUSTMENT
1. Turn "OFF" the electrical power to the water heater. If the power disconnect point is out of sight, lock it in the open ("OFF") position and tag to prevent unexpected application of power.
2. Open the water heater's electrical access panel.
3. Adjust each immersion thermostat to the desired temperature setting by turning the adjusting knob. Each thermostat will be factory pre-set to approximately 125°F (51.7°C) or less as shipped.
4. Close the water heater's electrical access panel.
5. Turn "ON" the electrical power to the water heater.
CAUTION
The maximum temperature setpoint that should be set for the Surface or Immersion Thermostats is 190°F (88°C).

FIG. 13 High Water Temperature Limit Control Fixed Setting
The unit is equipped with a fixed setting, manual-reset high water temperature limit control(s). The water heater temperature limit control has a fixed limit setting of 195°F (90.6°C). If water temperature exceeds the limit set point, the limit will break the control circuit and shut down the unit. The limit control can only be reset after the water temperature has cooled below the set point of the limit. The high water temperature limit control for the standard surface thermostat controls is the contained in the upper portion of the surface thermostat and mounted above each heating element. The high water temperature limit control for the immersion thermostat and contactor option is mounted on the surface of the tank, above the heating element installed at the highest point in the tank. The limit control is covered with an insulation blanket which must be removed to push the red reset button.
 CAUTION
Disconnect the main power to the heater before opening the element access panel to reset the high limit control.
NOTE:
The high limit control will not reset until the water temperature has dropped below the set point of the high limit.

11

IMMERSION HEATING ELEMENTS

START-UP PROCEDURE
Never operate the heating elements without being certain the water heater is filled with water and a temperature and pressure relief valve is installed in the relief valve opening on top of the heater.
DANGER

Full power is present whenever the cabinet door is opened.

FIG. 14 Immersion Heating Element
 WARNING:
HAZARD OF ELECTRICAL SHOCK - Before opening the access panel to remove or service the immersion heating elements, make sure the electrical supply to the water heater is turned "OFF". Failure to do this could result in death, serious bodily injury or property damage.
The heating input to this commercial electric water heater is provided by low watt density immersion heating elements. The heating elements are constructed from a copper sheath with a tin plate on the exterior surface. Individual element blades are mounted on a hex-head screw-in mounting flange. The element flange mounts into a 1" NPT threaded connection welded to the storage tank. The hex-head screw-in mounting flange seals to the tank with an "O" ring gasket at the base of the threaded portion of the flange. The tank flange has a matching recess for the "O" ring gasket to insure a proper water tight seal. The "O" ring element gasket must be replaced with a new gasket when an element is removed for inspection, cleaning or replacement.
 DANGER
HAZARD OF ELECTRICAL SHOCK - Full power is present whenever the cabinet door is opened and main power is turned "ON".

THERMAL EXPANSION
Many water systems are equipped with pressure reducing valves, check valves or back flow preventers which may cause the water system to be closed. As water is heated, it will expand in volume due to thermal expansion. The system must make allowance for this expansion. If an expansion tank is not provided in the system, water pressure may increase to the point where the water heater's temperature and pressure relief valve opens to relieve the excess pressure. The temperature and pressure relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected. A properly sized expansion tank is typically installed in the potable water system to relieve the pressure built up by thermal expansion of heated water. Consult your local plumbing contractor and plumbing wholesaler for assistance in properly selecting an expansion tank for your system.
As the water heater operates, there may be noises generated by the expansion and contraction of the metal parts of the water heater and related piping. These noises may occur during periods of heat up or cool down. They do not represent harmful or dangerous conditions.
FILLING THE WATER HEATER
1. Insure that the electrical power to the water heater is in the "OFF" position. If the power disconnect point is out of sight, lock it in the open ("OFF") position and tag to prevent unexpected application of power.
2. Close the water heater drain valve(s).
3. Open a nearby hot water faucet to allow the air in the system to escape as the tank fills.
4. Fully open the cold water inlet valve to the water heater to begin filling the heater and piping.

12

NOTE:
The cold water supply must be left in the open position when the water heater is in use.
5. Check the nearby hot water faucet to verify that air is exiting the tank as it fills with water. Allow water to run until a constant flow is obtained at the faucet. This will insure that all air is purged from the system.
 CAUTION

12. As the water heater starts heating, check the contactors for "buzzing" or "chattering" during operation. If noise is detected, turn off main power, open the control panel and clean the contact points of the magnetic contactor(s). Remove any dust, dirt or foreign matter that may have found its way into the contactor or other electrical components in the control panel during shipping, installation or service.
13. Close the electrical control panel and turn on main power.

The power supply must remain off until the water heater and all related piping are completely filled with water to insure that there will not be a possible problem with heating element burn out.
6. While the tank is filling, open the electrical control panel and set the immersion thermostat(s) to the desired water temperature. Open the element access panel to set the surface mount thermostats above each immersion heating element. If equipped with multiple thermostats, all individual thermostats may be adjusted to the same temperature set point or they may be set a 2° to 4°F (1° to 2°C) apart to step the elements on in stages.

14. The water heater is now ready for normal operation.
INITIAL START UP CHECKS
The following checks should be made by the installer when the water heater is placed into operation for the first time.
WARNING:
HAZARD OF ELECTRICAL SHOCK - Before opening the access panel to perform service on any electrical component, make sure the electrical supply to the water heater is turned "OFF". Failure to do this could result in death, serious bodily injury or property damage.

7. When a constant flow is obtained at the faucet, it may be turned off. The temperature and pressure relief valve should be manually opened to insure that there is no captive air in the storage tank. A constant stream of water must flow from the manually opened relief valve. Release the handle on the relief valve and allow it to close after water flow is observed.

1. Allow the water heater to heat for approximately thirty minutes after following the filling and start up procedures.
2 Turn off the main electrical power to the water heater. If the power disconnect point is out of sight, lock it in the open ("OFF") position and tag to prevent unexpected application of power.

8. Carefully check the tank, pipe and fittings for any sign of a water leak. Immediately repair as needed. Open the access door to the immersion heating elements and check for leaks at the element mounting flanges. If any leak is detected, tighten the screw-in element.
START UP

3. Open the electrical control panel door and feel each wire connection and fuse clip for excessive temperature. If any connection is found to be excessively hot, check the tightness of the connection. Check all factory internal wiring connections and the field made main power connections for tightness.

9. Ensure that the electrical access panel (field wiring compartment) is closed and the heating element access panel is in place before proceeding.

4. Close and lock the electrical control panel door. 5. Turn on the main electrical power to the water heater.

10. After assuring that the tank is completely filled with water and no leaks are detected, you are now ready to start operation of the water heater.

6. Temperature control and contactor operation should be checked by allowing the water heater to come up to temperature and shut off automatically.

11. Turn on the electric power at the main disconnect point. On immersion thermostat models, the contactors should be energized as the elements start to heat the water in the tank.

7. The water heater is now ready continuous normal operation.

13

SHUTDOWN PROCEDURE
1. Turn off the main electrical power to the water heater. If the power disconnect point is out of sight, lock it in the open ("OFF") position and tag to prevent unexpected application of power.
2. Turn the valve in the water heater's cold water supply to the closed or "OFF" position.

TEMPERATURE AND PRESSURE RELIEF VALVE OPERATION
The temperature and pressure relief valve(s) should be manually operated at least once a year. A relief valve that fails to completely reseat after manual operation and continues to discharge water must be immediately replaced with a new, properly sized, temperature and pressure relief valve.

3. Turn the valve in the water heater's hot water outlet to

t

h

e

closed or "OFF" position.

4. Manually open the temperature and pressure relief valve to remove any pressure from the storage tank. Caution! Any water discharged from the manually opened relief valve may be hot and cause a scald injury.

5. Allow the system to cool and then open the drain valve to empty the storage tank. It will be necessary to manually hold the temperature and pressure relief valve in the open position to break the vacuum in the tank and allow it to vent and drain. Insure that the water heater drain is routed to a properly sized floor drain to allow the water to be removed from the tank. If a floor drain is not available, a hose may be attached to the water heater drain to take the water outdoors.

6. The water heater is now shut down and ready for service or maintenance.

7. Follow the filling and start up procedure to place the water heater back into service.
MAINTENANCE
Listed below are items that must be checked to insure safe reliable operations. Verify proper operation after servicing.

 WARNING:
HAZARD OF ELECTRICAL SHOCK - Before opening the electrical access door, removing the heating element access panel or servicing the water heater, make sure the electrical supply to the water heater is turned "OFF". Failure to do this could result in death, serious bodily injury or property damage.
 CAUTION

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

The relief valve(s) should be installed in the vertical position and mounted in the tapping provided in the storage tank. No valve should be placed between the relief valve, and the water heater. To prevent water damage, the discharge from the relief valve must be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. The discharge line from the relief valve should be metallic pipe or a high temperature plastic pipe (CPVC, etc.) to insure that hot water flow will not damage the discharge piping from the relief valve.
 CAUTION
Avoid contact with hot discharge water. Insure that no one is in front of or around the relief valve discharge line. Make sure that the extremely hot water manually discharged from the relief valve will not cause bodily injury or property damage.
WATER CHEMISTRY
In hard water areas, water treatment should be used to reduce the introduction of minerals to the system. Minerals in the water can collect in the storage tank and on the immersion heating elements causing noise on operation. Excessive build up of minerals on the surface of the heating elements can reduce the service life of the elements and lead to a non-warrantable failure.
Proper operation of this electric water heater is based on heating potable water with a hardness of 5 to 25 grains per gallon and a total dissolved solids not exceeding 350 PPM. Consult the manufacturer when heating potable water exceeding these specifications. Heating of high hardness and/or high total dissolved solids water may require frequent cleaning of the storage tank and heating elements to achieve proper operation. The higher the level of dissolved solids or water hardness, the faster the dissolved minerals in the water will precipitate out and form scale deposits on the heating elements and in the storage tank. The level of scale formation is also accelerated as stored water temperature increases. Water with a hardness of less than 5 grains per gallon will usually have a low pH which can be aggressive and corrosive causing non-warrantable damage to the storage tank, heating elements and associated piping.

14

Corrosion due to water chemistry generally shows up first cleaned from the bottom of the tank. in the hot water system because heated water increases the rate of corrosive chemical reactions.

Water heater maintenance includes periodic tank flushing and cleaning and removal of lime scale from the heating elements. Where used, the water heating system circulating pump should be oiled.
FLUSHING THE STORAGE TANK
1. Turn off main power at the electrical disconnect switch.

NOTE:
All gaskets on disassembled clean-out openings must be replaced with new gaskets on re-assembly. Gaskets are available from your distributor.

2. Open the drain valve. Allow water to flow until it runs clean.
3. Close the drain valve when finished flushing.
4. Open a hot water faucet closest to the water heater and the water to run to insure that no air was drawn into the tank during the flushing process. Close the faucet when the water runs clear with no discharge of air.
5. Turn on main power the electrical disconnect switch (after filling).
SEDIMENT REMOVAL
Water born impurities consist of dissolved minerals which precipitate out of the heated water and fine particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank. In time, if not removed, the level of sediment might reach the heating elements.
For convenience, sediment removal and element lime scale removal should be performed at the same time. Proceed with the following instructions:
Sediment and Lime Scale Removal
Sediment and lime scale accumulation on the heating elements is a normal condition common to all immersion type elements. Factors which affect the amount of this formation are:
1. Amount of hot water used. As the volume of water increases, more scale results.

Water scale accumulations on the immersion heating element reduce the ability of the elements to heat water and may cause noise to occur during operation. It is recommended that a heating element be removed at least once a year for examination. If it is scaled, all of the elements should be removed and cleaned. The element gasket must be replaced when the element is removed for cleaning.
Small accumulations of lime scale may be removed with a stiff bristle brush. Severe accumulations of lime scale should be removed by dissolving the accumulation in a commercial delimer. Do not use muratic or hydrochloric acid base deliming solutions to remove lime scale from the elements. Do not pour delimer into tank. Deliming solutions may damage the glass lined interior of the tank.
 DANGER
Keep all delimers away from anode rods to prevent the formation of flammable and explosive gas.
1. Drain the heater following "SHUTDOWN PROCEDURE" instructions.
2. Disconnect the wires attached to the element terminals. Try not to disturb the wiring unnecessarily and reconnection will be easier.
3. Loosen the screw-in element flange with a socket and breaker bar. Do not use an impact gun (air or electric) to remove the element flanges from the tank. Mark the location of each element in the tank openings so they may be returned to their original position.

2. Water temperature. As the temperature of the water is increased, more scale is deposited on the elements.

4. Remove the elements from the opening with a twisting, pulling action if the elements are scaled beyond the size of the tank flange openings. Brush loose scale from

elements. 3. Characteristics of water supply. Regardless of water

treatment, the elements should be examined regularly.

5. Place scaled ends of heating elements into a deliming

Scale accumulation in the bottom of the storage tank may be removed by turning off main power and draining the tank. Once all water is removed, the hand hole access can be

solution and allow scale to dissolve. Do not permit the delimer or water to contact heating element electrical terminals.

removed. This will allow large accumulations of scale to be 6. Flush clean ends of elements with water when deliming

or cleaning is completed.

15

7. Clean remaining gasket recess on each screw-in element flange. Do not reuse element gaskets.
8. Install a new gasket on each element. Install element into the tank opening where it was originally installed. Tighten the flange with the socket and breaker bar used to remove the element.

Water is too hot
1. Refer to "Temperature Regulation" and reset the thermostat setpoint to a lower temperature that will meet requirements for hot water
Water heater makes sounds

9. Attach wires to element terminals from which they were removed.
10. Follow "FILLING THE WATER HEATER" instructions to restore hot water service. Check for water leaks around elements and proper operation when heater is filled.
TROUBLE SHOOTING
Checklist
Before calling for service, check the following points to see if the cause of trouble can be identified and corrected. Reviewing this checklist may eliminate the need of a service call and quickly restore hot water service.
Not enough or no hot water
1. Ensure that the electrical disconnect switch serving the water heater is in the "ON" position. In some areas, water heater electrical service may be limited by the power company. If the heater operates on a controlled circuit, heater recovery may be affected.
2. Check the fuses. The electrical disconnect switch usually contains fuses. The water heater has fuses located behind the cabinet front door. When replacing internal fuses in the water heater control panel, insure that the same type and size of fuse is used.
3. If the water was excessively hot and is now cold, the manual reset high limit may have operated. To reset, turn off electricity and push the reset button. The high limit is located above the thermostat on surface thermostat models, above the upper most heating element in the storage tank on immersion thermostat models. Repeat operation of the high temperature cut-off should be investigated by your mechanical contractor or by a qualified technician. A contactor or thermostat may be malfunctioning.
4. The capacity of the heater may have been exceeded by a large demand for hot water. Large demands require a recovery period to restore water temperature.
5. Cold incoming water temperature will lengthen the time required to heat water to the desired temperature. If the heater was installed in the summer when incoming water temperature was warm, colder ground water in the winter months can create the effect of less hot water.

1. Sediment or lime scale accumulation on the elements causes sizzling and hissing noises, when the heater is operating. If this occurs, the tank bottom and elements should be cleaned. Refer to "MAINTENANCE" for
details.
2. Some of the electrical components of the water make sounds which are normal. Contactors will "click" or snap as the heater starts and stops. Transformers and contactors often hum.
Water leakage is suspected
1. Check to see if the drain valve is tightly closed.
2. The apparent leakage may be condensation which forms on cool surfaces of the heater and piping.
3. If the outlet of the relief valve if leaking, it may represent:
a. Excessive water pressure. b. Excessive water temperature. c. Faulty relief valve.
Excessive water pressure is not the most common cause of relief valve leakage. It is often caused by a "closed system." A check valve, a back flow preventer or pressure reducing valve, in the inlet system will not permit the expanded hot water volume to equalize pressure with the main. A relief valve must release this water or the water heater and plumbing system will be damaged.
When such a condition is encountered, local codes or inspection agency should be consulted to determine which of the following procedures is acceptable in your area.
Installation of an expansion tank.
Removal of the check valve.
4. Examine the flange area of the elements for gasket leakage. Tighten the screw-in flange or, if necessary, follow the "Water and Lime Scale Removal" procedure to remove the element and replace the "O" ring gaskets that seal each element.
IF YOU CANNOT IDENTIFY OR CORRECT THE SOURCE
OF MALFUNCTION:
1. Place the water heater electrical disconnect switch on the "OFF" position.

6. Look for wasted hot water and leaking or open hot water 2. Contact your mechanical contractor or service

faucets.

technician.

7. Sediment or lime scale may be affecting water heater operation. Refer to "Maintenance" for details.
16

Revision Notes: Revision 2 (ECO #C02870) reflects the addition of the scald chart on page 10.