Technical specification LCD Icon description Button ... - Salus

Before use please read this manual carefully. Use only. AA 1.5 V alkaline batteries in the thermostat. Place the batteries into the battery slot located ...

RT310 Wiring diagram - salus-controls.es

Pairing the RT310TX thermostat with the RXRT510 receiver Change the Setpoint temperature Frost Protection RT310TX thermostat reset Installer Mode

Technical specification LCD Icon description Button functions RT310 Terminals description RXRT510 Receiver terminals description

User Manual for SALUS models including: RT310, RT310RF, Digital Room Thermostat

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 2 Pages, 251.88KB

Document DEVICE REPORTRT310(RF) QG V2 ENG (1)
XII 2020 [ENG]

Model: RT310 (Digital room thermostat) RT310RF (Digital room wireless thermostat)

Button functions
RT310 / RT310TX Thermostat

1

3

2

4

RXRT510 Receiver

5

6

7

8

Installation Manual

Introduction
RT310 / RT310RF is a digital room thermosat used to control room temperature. Device launching heating or cooling system by shorting terminal blocks, simultaneously informing the action and showing this information on the LCD display. Before use please read this manual carefully. Use only AA 1.5 V alkaline batteries in the thermostat. Place the batteries into the battery slot located under the cover. Do not use rechargeable batteries.
Product compliance
Directives: EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU and RoHS 2011/65/EU. Full information is available on the website www.saluslegal.com
Safety Information
Use in accordance to national and EU regulations. Use the device as intended, keeping it in dry condition. Product for indoor use only. Installation must be carried out by a qualified person in accordance to national and EU regulations.

Technical specification

Thermostat supply Receiver supply Thermostat rating max Receiver rating max
Outputs
Temperature range

RT310 2 x AA alkaline batteries 3 (1) A Voltage free NO / COM /NC terminals 5 - 35°C

RT310RF 2 x AA alkaline batteries 230 V AC 16 (5) A Voltage free NO / COM terminals 5 - 35°C

1. Turn on the LCD backlight 2. HEAT/COOL modes change
or Frost Protection mode activation 3. Increase button 4. Decrease button

Receiver's LED diode Red Green

Status Solid light Flashing Solid light

5. When in Manual Mode, ON will turn the boiler on
6. When in Manual Mode, OFF will turn the boiler of
7. Receiver operates in automatic mode according to the thermostat
8. Receiver output is controlled by the On/Off slide switch.
Description
Power on
Lost connection or pairing mode
System works

LCD Icon description
1 2 3 4

1. Heating Mode ON

5

2. Cooling Mode ON/

6

Frost Protection Mode ON

3. RF signal indicator (only in RT310RF)

4. Low battery status

5. Temperature unit

6. Room / setpoint temperature

RT310 Terminals description

Terminal
1 - COM 2 - NC 3 - NO

Description
Common Terminal Switched Live OFF Switched Live ON

RXRT510 Receiver terminals description

Terminal
NO COM L, N

Description
Switch Terminal Common Switch Terminal Supply (230 V AC)

NO COM L N

DIP switches parameters

12

Cooling

Heating

ON ON Hysteresis +/- 0.25 °C ON ON Hysteresis +/- 1.5°C ON OFF Hysteresis +/- 1.0°C OFF OFF Hysteresis +/- 0.5°C

Hysteresis +/- 0.25°C Hysteresis +/- 0.5°C
TPI 9 CPH TPI 6 CPH

Default value

ON

9CPH

Span
±0.25°C

6CPH

TPI

12

RT310 Wiring diagram

AC 230 V L

MAX 3 (1) A

Thermostat RT310
NC COM
NO Thermostat RT310
NC COM
NO

Thermostat RT310TX Receiver RXRT510

M M

or
N
RT310RF Wiring diagram
Note: If you are using the RT310RF pack, the pairing between the thermostat and the receiver is already done!
AC 230 V L
L COM
N NO N
AC 230 V L
L COM
MAX 16 (5) A
N NO
or
N

Thermostat RT310TX Receiver RXRT510

Change the Setpoint temperature

Actual room temperature.

Press or , to set the temperature.

After 2 seconds, the new temperature setpoint will be overwritten.
Frost Protection

The thermostat will display the measured temperature again. The heating mode icon will
start flashing if the temperature setpoint is higher than the measured temperature.

Sleep Mode
When Sleep Mode is active all the thermostat functions will be paused.
3 sec.

3 sec.
To enter sleep mode, press and hold and for 5 seconds.

To exit sleep mode, press any button.

Pairing the RT310TX thermostat with the RXRT510 receiver

NOTE: IN THE RT310RF SET, THE THERMOSTAT IS FACTORY PAIRED WITH THE RECEIVER!

If you want to pair the thermostat with the receiver again, make sure that the device is disconnected from the power supply and the switches on the receiver are in the AUTO and ON positions.

1

2

3

5 sec Press , button to turn On/Off frost protection.

When the snowflake icon is displayed right next to the flame icon (heating mode) it means that
the frost protection mode is active.

The Frostpoint temperature can be reviewed by pressing the UP button once, but can only be changed in Installer Mode.

Heat / Cool mode selection*
The user can change the heating and cooling mode.
NOTE: In cooling mode, the thermostat reports a cooling demand with a 3-minute
delay.

1

2

5 sec

TEST / PAIRING

To switch the thermostat to cooling mode, press and hold the snowflake button for 5 seconds.

1

TEST / PAIRING
When the thermostat switches to cooling mode, the snowflake icon will be displayed and the flame icon will
disappear.
2

Connect the receiver to the power supply and wait for the red diode to glow
continuously.
4

Then set the switch to the OFF position and quickly move it to the ON position.
5

Red flashing LED will confirm entering the pairing
mode.
6

TEST / PAIRING
3 sec
Press and hold the TEST / PAIRING button for 3 seconds.
7

TEST / PAIRING
The pairing process takes up to 9 minutes.
8

When the red diode on the receiver lights up
continuously, the devices have been paired on a new
frequency.

Installer Mode
3 sec.

3 sec.

3 sec.

Press three buttons at the same time for 3 seconds.

dxx

Function

d01 Temperature display increments d02 Temperature offset d03 Frost Protection setpoint temperature

Reset of the RT310 thermostat

Press to change the parameter. To change the parameter value use and buttons.

Parameter value

Default value

0.1°C or 0.5°C 0.5°C

+/- 3.0°C

0.0°C

5.0°C - 17.0°C 5.0°C

Press the RESET button (you can use a paper clip), the thermostat will reset and turn on automatically.
RESET

RT310TX thermostat reset
Remove the batteries without pressing any button. Wait 2 minutes and insert the batteries again. Your device will be restarted.

TEST / PAIRING

+

-

When you want to change the batteries your device will use the internal memory to backup your settings. You have 30 seconds to change the batteries before losing your settings.

+

-

IMPORTER: QL CONTROLS Sp. z o.o. Sp. k. ul. Rolna 4, 43-262 Kobielice

PRODUCER: Salus Limited 6/F, Building 20E, Phase 3, Hong Kong Science Park, 20 Science Park East Avenue, Shatin, New Territories, Hong Kong

5 sec

TEST / PAIRING

To switch the thermostat to heating mode, press and hold the snowflake button for 5 seconds.

* Function available from software version v2.1

TEST / PAIRING
When the thermostat switches to heating mode, the flame icon will be
displayed.

TEST / PAIRING
To complete the pairing process press and hold the TEST / PAIRING button for 3 seconds.

TEST / PAIRING
The thermostat will return to the main screen.

www.salus-controls.eu
SALUS Controls is a member of the Computime Group. Maintaining a policy of continuous product development SALUS Controls plc reserve the right to change specification, design and materials of products listed in this brochure without prior notice.


Adobe InDesign 16.1 (Windows) 3-Heights(TM) PDF Optimization Shell 5.9.1.5 (http://www -tools.com)

Search Any Device: