42755150303

woodl

WJH4 Specification Manual

3 Ton 14.50 SEER Grandaire Heat Pump Package Unit - WJH436000KTP0A • Ingrams Water & Air

PDF Viewing Options

Not Your Device? Search For Manuals or Datasheets below:


File Info : application/pdf, 24 Pages, 1.21MB

Document DEVICE REPORTwjh4-specifications
WJH4

UP TO 14.5 SEER, R-410A PACKAGE HEAT PUMP FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 - 5 TONS
Single Phase, 208/230 V, 60 Hz

Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program. For verification of certification for individual products, go to www.ahridirectory.org .

UNIT PERFORMANCE DATA

COOLING

HEATING

Model Number

Net Capacity BTU/h @ 95°F(35°C) SEER

EER

Net Capacity BTU/h @
47°F(8.3°C)

HSPF

WJH424000KTP0A

24,000

14.50 11.50

23,400

8.0

WJH430000KTP0A

29,800

14.50 11.50

28,600

8.0

WJH436000KTP0A

36,000

14.50 11.50

34,400

8.0

WJH442000KTP0A

42,000

14.50 11.50

40,000

8.0

WJH448000KTP0A

46,500

14.00 11.50

45,000

8.0

WJH460000KTP0A

55,000

14.00 11.00

56,000

8.0

Unit Dimensions Height x Width x Depth
inches (mm) 30-1/8 x 51 x 32 (765 x 1295 x 813)
34-1/8 x 51 x 32 (867 x 1295 x 813)
42-1/8 x 51 x 32 (1070 x 1295 x 813)

REFRIGERATION CIRCUIT  Environmentally balanced R-410A refrigerant  Liquid refrigerant filter driers  Copper tube/aluminum fin condenser and evaporator coils
EASY TO INSTALL AND SERVICE  Light weight, compact construction ideal for manufactured housing and residential applications  Hand holds built into the unit base pan  Compact, fully self-contained, electric cooling unit with horizontal supply and return ducts  Easy panel accessibility for maintenance and installation  Accessory electric heaters with single point connections  Designed to be serviced from both the side and front  Cabinet air leakage less than 2.0% at 1.0 inch W.C. and cabinet air leakage less than 1.4%
at 0.5 in. W.C., when tested in accordance with ASHRAE Standard 193
BUILT TO LAST  Vibration isolation provides quiet operation. Compressors have internal over current protection  Direct-drive multi-speed, blower motor standard on all models  No-rust base pan with integrated drain pan standard on all units  Durable pre-painted steel cabinet  Louvered coil enclosure for protection against vandalism and hail damage  Aerodynamic fan blade design reduces the overall sound  All models available with optional factory installed tin-coated copper evaporator coil.
(These models are identified with letters TP in the 11th and 12th positions in the model numbers)
LIMITED WARRANTY*  1 year unit replacement limited warranty  10 year parts limited warranty (including compressor and coil) with timely registration  5 years parts limited warranty if not registered within 90 days of original installation. * See warranty certificate for complete details and restrictions.

Operating Weight lbs (kg)
253 (115)
283 (128) 285 (130) 339 (154) 358 (163) 425 (193)

Specifications subject to change without notice.

426 55 1503 03 6/21/17

Product Specifications

MODEL NUMBER NOMENCLATURE

MODEL SERIES

1

2

3

4

5,6 7,8,9 10 11,12 13

14

15

W J H 4 36 000 K 00 0 A 1

WJ = Package

TYPE

H = Heat Pump 3 = 13 4 = 14 5 = 15 24 = 24,000 BTUH = 2 Tons 30 = 30,000 BTUH = 2.5 Tons 36 = 36,000 BTUH = 3 Tons 42 = 42,000 BTUH = 3.5 Tons 48 = 48,000 BTUH = 4 Tons 60 = 60,000 BTUH = 5 Tons

TIER SEER
NOMINAL COOLING CAPACITY

000 = No factory heat K = 208/230-1-60 00 = No options

NOMINAL HEATING BTUH (input) VOLTAGE

TP = Tin Coated Copper Evap Main Tubes plus Stainless Steel Heat Exchanger
FACTORY INSTALLED OPTIONS

0 = Standard Sales Model Digit Engineering Digit

FEATURE CODE

AHRI* CAPACITIES Cooling Capacities and Efficiencies

UNIT SIZE
24 30 36 42 48 60

NOMINAL TONS
2 2.5 3 3.5 4 5

STANDARD CFM
800 1000 1200 1400 1600 1700

NET COOLING CAPACITY AT 95°F (35°C) (Btuh) 24,000 29,800 36,000 42,000 46,500 55,000

EER
11.50 11.50 11.50 11.50 11.50 11.00

SEER**
14.50 14.50 14.50 14.50 14.00 14.00

Heat Pump Heating Capacities and Efficiencies

UNIT SIZE

NET HEATING CAPACITY AT 47°F
(8.3°C) (Btuh)

COP @ 47°F (8.3°C)

24

23,400

3.7

30

28,600

3.7

36

34,400

3.5

42

40,000

3.5

48

45,000

3.5

60

56,000

3.5

LEGEND dBSound Levels (decibels) db--Dry Bulb SEER--Seasonal Energy Efficiency Ratio wb--Wet Bulb COPCoefficient of Performance * Air Conditioning Heating & Refrigeration Institute  At "A" conditions80°F (26.7°C) indoor db/67°F (19.4°C) indoor wb & 95°F (35°C) outdoor db. ** Rated in accordance with U.S. Government DOE Department of Energy) test procedures and/or AHRI Standards 210/240. Notes: 1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80°F (26.7°C) db, 67°F wb (19.4°C) indoor enteringair temperature and 95°F db (35°C) outdoor enteringair temperature. 2. Before purchasing this appliance, read important energy cost and effi ciency information available from your retailer.

NET HEATING CAPACITY AT 17°F
(8.3°C) (Btuh)
13,400 15,600 20,200 23,400 26,600 33,000

COP @ 17°F (8.3°C)
2.4 2.4 2.4 2.4 2.3 2.4
Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program For verification of certification for individual products, go to www.ahridirectory.org.

HSPF**
8.0 8.0 8.0 8.0 8.0 8.0

2

Specifications subject to change without notice.

427 55 1503 03

A-Weighted Sound Power Level (dBA) - AHRI STANDARDS 270-1995

UNIT SIZE
24 30 36 42 48 60

STANDARD RATING (dBA) 73 75 77 76 75.6 79.0

TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

125

250

500

1000

2000

4000

8000

54.4

54.9

58.8

67.5

53.7

48.5

39.4

55.4

63.9

62.8

59.0

54.7

45.5

37.9

66.2

67.6

72.3

72.6

68.6

62.6

52.5

64.5

68.1

69.9

69.4

67.0

64.0

58.3

59.9

64.4

64.8

65.0

59.7

55.5

48.9

67.6

65.7

68.6

70.5

65.3

59.8

50.0

PHYSICAL DATA
UNIT SIZE NOMINAL CAPACITY (ton)
SHIPPING WEIGHT (lb) (kg)
COMPRESSOR TYPE REFRIGERANT
REFRIGERANT QUANTITIY (lb) QUANTITY (kg)
OUTDOOR METERING DEVICE ORIFICE ID (in.) (mm) OUTDOOR COIL ROWS...FINS/in.
FACE AREA (sq. ft)
OUTDOOR FAN NOMINAL AIRFLOW (cfm)
DIAMETER (in.) DIAMETER (mm) MOTOR HP (RPM) INDOOR METERING DEVICE ORIFICE ID (in.)
(mm) INDOOR COIL ROWS...FINS/in. FACE AREA (sq. ft)
INDOOR BLOWER NOMINAL COOLING AIRFLOW (cfm)
NOMINAL SIZE D x L (in.) (mm)
MOTOR (HP) HIGHPRESSURE SWITCH (psig)
CUTOUT RESET (AUTO) LOWPRESSURE SWITCH (psig)
CUTOUT RESET (AUTO) RETURNAIR FILTERS THROWAWAY (in.)
(mm)

24 2 312 142
7.00 3.18 TXV
-
2...20 9.1
2000 20 508
1/8 (825)
0.059 1.499
3...12 4.3
800 10 x 8 254 x 203
1/3
20x20x1 508x508x25

30 2.5 333 151
7.20 3.27
0.049 1.245

36 3 334 152
SCROLL R-410A 6.30 2.86
Piston 0.057 1.448

42 3.5 388 177
9.10 4.13
0.059 1.499

2...20 10.2

2...20 10.2

2...20 13.0

2000 20 508
1/8 (825)
Piston 0.059 1.499

2800 20 508
1/4 (1100)
0.067 1.702

3100 20 508
1/4 (1100)
0.076 1.9304

3...14 4.3

3...12 4.9

3...14 4.9

1000 11 x 9 279 x 229
1/3

1200 11 x 9 279 x 229
1/2

1400 11 x 9 279 x 229
1/2

650 +/- 15 420 +/- 25

24x30x1 610x762x25

20 +/- 5 45 +/- 10

48

60

4

5

407

475

185

215

7.70

11.5

3.49

5.22

TXV

Piston

-

0.070

-

1.778

2...20 15.5

2...20 15.5

3100 20 508
1/4 (1100)

3300 20 508
1/3 (1100)

TXV

-

-

-

-

3...14 4.9

3...14 4.9

1600 11 x 9 279 x 229
3/4

1700 12 x 11 305 x 279
1

24x36x1 610x914x25

*Required filter sizes shown are based on the AHRI (Air Conditioning, Heating & Refrigeration Institute) rated airflow at a velocity of 300 ft/min (91 m) for throwaway type or 450 ft/min (137 m) for high capacity type. Recommended filters are 1-in. (25 mm) thick.

OPTIONS AND ACCESSORIES

ITEM

DESCRIPTION

Coil Options Compressor Start Kit Corporate Thermostats Crankcase Heater Electric Heaters Low Ambient Kit
Time Guard II

Base unit with tin plated indoor coil hairpins Compressor Start Kit assists compressor start-up by providing additional starting torque.
Thermostats provide control for the system heating and cooling functions. Crankcase Heater provides anti-floodback protection for low-load cooling applications.
Electric Heat Supplement Low Ambient Kit (Motormaster II Control) allows the use of mechanical cooling down to outdoor temperatures as low as 0°F (-18°C) when prop erly installed.
Automatically prevents the compressor from restarting for at least 4 minutes and 45 seconds after shutdown of the compressor. Not required when a corporate programmable thermostat is applied.

FACTORY INSTALLED
OPTION
X

FIELD INSTALLED ACCESSORY
X X X* X X
X

Refer to Price Pages for available accessories.

427 55 1503 03

Specifications subject to change without notice.

3

Accessory Electric Heater Usage

CATALOG ORDERING NO.
CPHEATER125A0* CPHEATER126A0* CPHEATER127A0* CPHEATER128A0* CPHEATER129A0* CPHEATER130A0* CPHEATER131A0* CPHEATER132A0*

NOMINAL CAPACITY (kW)

CIRCUIT BREAKER (Yes/No)

STAGES

24

3.8 / 5.0

No

1



3.8 / 5.0

Yes

1



5.6 / 7.5

No

2



5.6 / 7.5

Yes

2



7.5 / 10.0 7.5 / 10.0

No

2

Yes

2



11.3 / 15.0

Yes

2

15.0 / 20.0

Yes

2

 Approved combination

Multiplication Factors
HEATER kW RATING
240

VOLTAGE DISTRIBUTION 200 208 230 240

Example: 15.0 kW (at 240v) heater on 208v = 15.0 (.75 mult factor) = 11.25 capacity at 208v

USED WITH SIZES

30

36

42



















NONE











48

60









NONE













MULTIPLICATION FACTOR .69 .75 .92 1.00

4

Specifications subject to change without notice.

427 55 1503 03

BASE UNIT DIMENSIONS--24-36

WJH4024 WJH4030 WJH4036

427 55 1503 03

Specifications subject to change without notice.

5

BASE UNIT DIMENSIONS--42-48

WJH4042 WJH4048

6

Specifications subject to change without notice.

427 55 1503 03

BASE UNIT DIMENSIONS--60

:-+

427 55 1503 03

Specifications subject to change without notice.

7

SELECTION PROCEDURE
I. DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS Given:
Required Cooling Capacity (TC . . . . . . . . 28,000 Btuh Sensible Heat Capacity (SHC) . . . . . . . . 20,500 Btuh Required Heating Capacity . . . . . . . . . . . 28,550 Btuh Outdoor Entering-Air Temperature . . . . . 95F (35C) Outdoor-Air Winter Design Temperature 20F (-6.7C) Indoor-Air Winter Design Temperature . . . . . . . . . . . .70F (21.1C) Indoor Entering-Air Temperature . . . . . . . . . . . . . 80F (26.7C) edb, 67F ewb (19.4C) Indoor-Air Quantity . . . . . . . . . . . . . . . . . . . . . . . .1000 CFM
External Static Pressure . . . . . . . . . . . . . . . . . . . 0.20 IN. W.C. Electrical Characteristics (V-Ph-Hz) . . . . . . . . . . 230-1-60 edb -- entering dry bulb
ewb -- entering wet bulb
II. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY
Enter Cooling Capacities table at condenser entering temperature of 95F (35C), indoor air entering at 1000 cfm and 67F (19.4C) ewb (entering wet bulb). The 030 unit will provide a total cooling capacity of 28,800 Btuh and a sensible heat capacity of 21,600 Btuh. For indoor-air temperature other than 80F edb (entering dry bulb), calculate sensible heat capacity correction, as required, using the formula found in Note 3 following the cooling capacities tables. NOTE: Unit ratings are net capacities.
III. SELECT ELECTRIC HEAT Enter the 030 Heating Capacities table at 1000 CFM. At 70F (21.1C) return indoor air and 20F (-6.7C) air entering outdoor coil, the integrated heating capacity is 16,740 Btuh. (Select integrated heating capacity value since deductions for outdoor-coil frost and defrosting have already been made. No correction is required.)

The required heating capacity is 28,550 Btuh. Therefore, 11,810 Btuh (28,550 - 16,740) additional electric heat is required.
Determine additional electric heat capacity in kW.

11,810 Btuh 3414 Btuh/kW

= 3.46 kW of heat required

Enter the Accessory Electric Heater Usage table on page 4 for 208/240v. single-phase, 030 unit. The 5-kW heater at 240v most closely satisfies the heating required. To calculate kW at 230v, multiply the heater kW by multiplication factor 0.92 found in the Multiplication Factors table on page 4.
5 kW x 0.92 = 4.6 kW 4.6 x 3414 = 15,704 Btuh
To calculate kW at 208 v, see Multiplication Factors table on page 4.
Total unit heating capacity is 32,444 Btuh (16,740 +15,704).

IV. DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS

Before entering the air delivery tables, calculate the total static pressure required. From the given, the Accessory Electric Heat Pressure Drop table, and the Filter Pressure Drop table, find:

External static pressure Filter Electric heat
Total static pressure

0.20 IN. W.C. 0.09 IN. W.C. 0.04 IN. W.C. 0.33 IN. W.C.

Enter the table for Dry Coil Air Delivery -- Horizontal Discharge at 1000 CFM and 230v high speed. The blower will deliver 1036 CFM @ 0.40 IN W.C. static pressure. This will adequately handle job requirements.

8

Specifications subject to change without notice.

427 55 1503 03

BUILDING HEAT LOSS, UNIT INTEGRATED HEATING CAPACITY, MBTUH

80 70 60 50 40 30 20 10
0 -10

BALANCE POINT WORKSHEET
23.4

20.5
60

17.6

48

42

14.6

36
11.7
30
8.8
24

5.9

2.9

BASED ON INDOOR ENT. AIR AT 70 ºF AND AT RATED CFM

0.0

0

10

20

30

40

50

60

70

OUTDOOR TEMPERATURE, ºF

kW
Specifications subject to change without notice.

A14654
9

427 55 1503 03

10

PERFORMANCE DATA

COOLING CAPACITY

24
EVAPORATOR AIR
CFM EWB
57 (14) 62 (17) 700 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 800 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 900 63* (17) 67 (19) 72 (22)

75 (24) Capacity
MBtuh Total Sens 24.13 24.13 24.96 21.58 25.41 17.66 27.16 18.15 29.39 14.74 25.10 25.10 25.55 23.03 25.93 18.68 27.67 19.15 29.86 15.30 25.89 25.89 26.06 24.33 26.33 19.62 28.05 20.05 30.22 15.79

See page 16 for cooling notes.

Total Sys kW 1.40 1.40 1.40 1.41 1.41 1.41 1.41 1.42 1.42 1.42 1.43 1.43 1.43 1.43 1.44

85 (29) Capacity
MBtuh Total Sens 22.67 22.67 23.28 20.60 23.69 16.80 25.39 17.31 27.59 14.01 23.59 23.59 23.84 22.03 24.17 17.81 25.86 18.33 28.03 14.57 24.34 24.34 24.36 24.36 24.53 18.74 26.22 19.25 28.37 15.07

CONDENSER ENTERING AIR TEMPERATURES _F (°C)

95 (35)

105 (41)

115 (46)

Total Sys kW

Capacity MBtuh
Total Sens

Total Sys kW

Capacity MBtuh
Total Sens

Total Sys kW

Capacity MBtuh
Total Sens

1.71 21.20 21.20 2.06 19.18 19.18 2.47 17.23 17.23

1.71 21.59 19.65 2.06 19.26 19.17 2.47 17.27 17.27

1.71 21.95 15.92 2.07 19.64 14.77 2.48 17.12 13.57

1.71 23.57 16.44 2.07 21.73 15.60 2.50 19.32 14.52

1.72 25.69 13.23 2.08 23.72 12.42 2.51 21.74 11.67

1.72 22.07 22.07 2.08 20.33 20.33 2.50 18.25 18.25

1.72 22.15 21.95 2.08 20.37 20.37 2.50 18.29 18.29

1.72 22.39 16.92 2.08 20.25 15.91 2.50 17.60 14.64

1.73 24.00 17.45 2.09 22.11 16.59 2.51 19.85 15.73

1.73 26.11 13.76 2.09 24.08 12.98 2.53 22.06 12.21

1.74 22.76 22.76 2.10 21.17 21.17 2.52 19.11 19.11

1.74 22.78 22.78 2.10 21.19 21.19 2.52 19.15 19.15

1.74 22.72 17.85 2.10 20.71 17.02 2.51 18.05 15.69

1.74 24.32 18.35 2.10 22.40 17.50 2.53 20.23 16.79

1.75 26.41 14.26 2.11 24.36 13.48 2.54 22.29 12.72

Total Sys kW 2.96 2.96 2.96 2.99 3.02 2.99 2.99 2.98 3.00 3.04 3.02 3.02 3.00 3.03 3.05

125 (52) Capacity
MBtuh Total Sens 15.34 15.34 15.37 15.37 14.73 12.42 16.69 13.34 19.42 10.81 16.19 16.19 16.22 16.22 15.13 13.44 17.17 14.46 19.80 11.48 16.95 16.95 16.99 16.99 15.48 14.40 17.60 15.54 20.07 12.05

Total Sys kW 3.54 3.54 3.53 3.56 3.59 3.57 3.57 3.55 3.59 3.62 3.60 3.60 3.57 3.62 3.64

Specifications subject to change without notice.

HEATING CAPACITY 24

INDOOR AIR

EDB
65 (18)
70 (21)
75 (24)

CFM
700 800 900 700 800 900 700 800 900

10 (23)

Capacity MBtuh

Total Integ

7.21

6.64

7.25

6.67

7.29

6.70

7.13

6.56

7.16

6.58

7.19

6.61

7.06

6.50

7.09

6.52

7.12

6.55

Total Sys kW
1.43 1.43 1.43 1.50 1.50 1.50 1.57 1.57 1.57

0 (18)

Capacity MBtuh

Total Integ

9.32

8.58

9.36

8.61

9.39

8.64

9.22

8.48

9.25

8.51

9.28

8.53

9.14

8.41

9.16

8.43

9.18

8.45

Total Sys kW
1.49 1.48 1.47 1.56 1.55 1.55 1.64 1.63 1.63

10 (12) Capacity
MBtuh Total Integ 11.68 10.72 11.71 10.75 11.75 10.78 11.56 10.61 11.58 10.63 11.61 10.65 11.45 10.51 11.47 10.53 11.49 10.54

Total Sys kW
1.55 1.53 1.52 1.62 1.61 1.60 1.71 1.69 1.68

OUTDOOR COIL ENTERING AIR TEMPERATURES °F (°C)

20 (7)

30 (1)

40 (4)

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

14.33 13.00 1.61 17.38 15.23 1.68 20.83 20.83

14.37 13.03 1.59 17.43 15.27 1.65 20.89 20.89

14.40 13.06 1.57 17.47 15.31 1.62 20.95 20.95

14.18 12.86 1.69 17.18 15.06 1.76 20.59 20.59

14.20 12.88 1.67 17.22 15.09 1.73 20.64 20.64

14.23 12.91 1.65 17.25 15.12 1.71 20.69 20.69

14.05 12.74 1.78 17.01 14.90 1.85 20.37 20.37

14.06 12.76 1.75 17.03 14.92 1.82 20.41 20.41

14.08 12.77 1.74 17.06 14.95 1.80 20.45 20.45

Total Sys kW
1.76 1.71 1.68 1.84 1.80 1.77 1.94 1.89 1.86

50 (10) Capacity
MBtuh Total Integ 24.83 24.83 24.92 24.92 25.00 25.00 24.54 24.54 24.62 24.62 24.69 24.69 24.26 24.26 24.32 24.32 24.38 24.38

Total Sys kW
1.84 1.79 1.75 1.93 1.88 1.84 2.03 1.97 1.93

60 (16) Capacity
MBtuh Total Integ 29.30 29.30 29.46 29.46 29.60 29.60 28.93 28.93 29.07 29.07 29.20 29.20 28.56 28.56 28.69 28.69 28.80 28.80

Total Sys kW
1.93 1.86 1.81 2.02 1.95 1.90 2.12 2.05 2.00

427 55 1503 03

427 55 1503 03

PERFORMANCE DATA (CONT) COOLING CAPACITY 30

EVAPORATOR

AIR

75 (24)

Capacity

CFM EWB

MBtuh

Total Sens

57 (14) 29.24 29.24

62 (17) 30.19 27.55

875 63* (17) 30.79 22.41

67 (19) 33.31 23.34

72 (22) 36.86 19.05

57 (14) 30.61 30.61

62 (17) 31.02 29.70

1000 63* (17) 31.52 23.91

67 (19) 34.09 24.95

72 (22) 37.71 20.07

57 (14) 31.77 31.77

62 (17) 31.81 31.81

1125 63* (17) 32.11 25.37

67(19) 34.70 26.52

72 (22) 38.37 21.05

See page 16 for cooling notes.

Total Sys kW
1.83 1.83 1.84 1.87 1.91 1.86 1.86 1.87 1.90 1.94 1.89 1.90 1.90 1.93 1.97

85 (29) Capacity
MBtuh Total Sens 27.70 27.70 28.33 26.42 28.86 21.37 31.27 22.30 34.65 18.09 28.97 28.97 29.13 28.47 29.53 22.85 31.97 23.88 35.41 19.09 30.04 30.04 30.08 30.08 30.05 24.27 32.52 25.41 35.99 20.05

CONDENSER ENTERING AIR TEMPERATURES _F (°C)

95 (35)

105 (41)

115 (46)

Total Sys

Capacity MBtuh

Total Sys

Capacity MBtuh

Total Sys

Capacity MBtuh

kW Total Sens kW Total Sens kW Total Sens

2.15 26.11 26.11 2.52 24.49 24.49 2.96 22.75 22.75

2.15 26.44 25.27 2.52 24.56 24.41 2.96 22.80 22.80

2.16 26.91 20.34 2.53 24.89 19.29 2.97 22.79 18.22

2.18 29.18 21.25 2.56 27.03 20.20 3.00 24.77 19.12

2.23 32.38 17.13 2.61 30.03 16.15 3.06 27.59 15.16

2.18 27.29 27.29 2.56 25.55 25.55 3.01 23.72 23.72

2.18 27.33 27.33 2.56 25.59 25.59 3.01 23.75 23.75

2.19 27.49 21.77 2.56 25.40 20.69 3.00 23.23 19.57

2.21 29.80 22.80 2.59 27.56 21.70 3.04 25.24 20.58

2.26 33.04 18.10 2.65 30.61 17.10 3.10 28.09 16.07

2.22 28.28 28.28 2.60 26.44 26.44 3.05 24.52 24.52

2.22 28.32 28.32 2.60 26.48 26.48 3.05 24.55 24.55

2.21 27.96 23.16 2.59 25.81 22.03 3.04 23.58 20.87

2.25 30.28 24.29 2.62 27.99 23.15 3.08 25.60 21.98

2.30 33.56 19.03 2.68 31.06 18.00 3.14 28.45 16.95

Total Sys kW
3.50 3.50 3.50 3.54 3.61 3.55 3.55 3.54 3.58 3.65 3.59 3.60 3.57 3.62 3.69

125 (52) Capacity
MBtuh Total Sens 20.93 20.93 20.97 20.97 20.56 17.11 22.46 18.03 25.07 14.15 21.82 21.82 21.84 21.84 20.97 18.43 22.85 19.44 25.47 15.04 22.52 22.52 22.55 22.55 21.30 19.67 23.16 20.79 25.78 15.89

Total Sys kW
4.14 4.14 4.12 4.18 4.25 4.19 4.19 4.16 4.22 4.30 4.24 4.24 4.21 4.26 4.34

Specifications subject to change without notice.

HEATING CAPACITY 30

INDOOR AIR

EDB
65 (18)
70 (21)
75 (24)

CFM
875 1000 1125 875 1000 1125 875 1000 1125

10 (23)

Capacity MBtuh

Total Integ

7.47

6.87

7.58

6.97

7.67

7.06

7.19

6.61

7.30

6.72

7.40

6.81

6.90

6.35

7.01

6.45

7.11

6.55

Total Sys kW
1.56 1.57 1.57 1.64 1.64 1.65 1.71 1.72 1.72

0 (18)

Capacity MBtuh

Total Integ

10.12 9.31

10.25 9.43

10.37 9.54

9.84

9.05

9.97

9.18

10.09 9.29

9.54

8.78

9.68

8.91

9.80

9.02

Total Sys kW
1.65 1.65 1.65 1.73 1.73 1.73 1.81 1.81 1.81

10 (12) Capacity
MBtuh Total Integ 13.30 12.21 13.66 12.54 13.77 12.64 12.91 11.85 13.08 12.01 13.24 12.16 12.58 11.55 12.76 11.71 12.90 11.84

Total Sys kW
1.75 1.76 1.75 1.83 1.83 1.82 1.92 1.91 1.91

OUTDOOR COIL ENTERING AIR TEMPERATURES °F (°C)

20 (7)

30 (1)

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

Total Sys kW

16.77 15.21 1.86 20.50 17.96 1.97

16.93 15.35 1.85 20.71 18.15 1.95

17.06 15.47 1.84 20.88 18.30 1.94

16.57 15.03 1.96 20.24 17.73 2.07

16.72 15.16 1.94 20.45 17.91 2.05

16.86 15.29 1.93 20.61 18.06 2.03

16.37 14.85 2.05 20.00 17.53 2.17

16.53 14.99 2.03 20.19 17.69 2.14

16.65 15.10 2.03 20.34 17.83 2.13

40 (4) Capacity
MBtuh Total Integ 24.97 24.97 25.24 25.24 25.47 25.47 24.62 24.62 24.89 24.89 25.11 25.11 24.29 24.29 24.54 24.54 24.76 24.76

Total Sys kW
2.10 2.07 2.05 2.20 2.17 2.15 2.30 2.27 2.25

50 (10) Capacity
MBtuh Total Integ 30.32 30.32 30.70 30.70 30.98 30.98 29.87 29.87 30.24 30.24 30.52 30.52 29.43 29.43 29.78 29.78 30.07 30.07

Total Sys kW
2.25 2.21 2.18 2.35 2.31 2.28 2.46 2.41 2.39

60 (16) Capacity
MBtuh Total Integ 36.79 36.79 37.28 37.28 37.61 37.61 36.22 36.22 36.69 36.69 37.03 37.03 35.66 35.66 36.12 36.12 36.45 36.45

Total Sys kW
2.43 2.38 2.36 2.53 2.48 2.46 2.65 2.59 2.56

11

12

PERFORMANCE DATA (CONT)

COOLING CAPACITY

36

EVAPORATOR AIR

CFM EWB

1050 1200 1350

57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67(19) 72 (22)

75 (24)
Capacity
MBtuh
Total Sens 35.93 35.93 37.16 32.72 37.80 26.59 40.63 27.40 43.93 21.95 37.48 37.48 38.06 35.03 38.56 28.13 41.32 28.90 44.53 22.75 38.67 38.67 38.83 36.99 39.12 29.53 41.83 30.27 44.95 23.44

See page 16 for cooling notes.

Total
Sys
kW 2.36 2.36 2.36 2.36 2.37 2.39 2.39 2.39 2.39 2.41 2.42 2.42 2.42 2.43 2.44

85 (29)
Capacity
MBtuh
Total Sens 33.75 33.75 34.64 31.84 35.24 25.75 38.07 26.70 41.38 21.32 35.25 35.25 35.55 34.11 35.95 27.33 38.73 28.26 41.96 22.17 36.40 36.40 36.44 36.44 36.50 28.79 39.21 29.67 42.38 22.92

CONDENSER ENTERING AIR TEMPERATURES °F (°C)

95 (35)

105 (41)

115 (46)

Total Capacity

Total Capacity

Total

Capacity

Sys

MBtuh

Sys

MBtuh

Sys

MBtuh

kW Total Sens kW Total Sens kW Total Sens

2.70 31.52 31.52 3.08 29.19 29.19 3.52 26.69 26.69

2.70 32.05 30.86 3.08 29.38 29.75 3.52 26.74 26.74

2.70 32.57 24.84 3.08 29.78 23.85 3.52 26.72 22.69

2.70 35.38 25.86 3.09 32.52 24.93 3.54 29.45 23.92

2.72 38.64 20.59 3.12 35.74 19.79 3.57 32.68 18.87

2.73 32.94 32.94 3.12 30.53 30.53 3.56 27.93 27.93

2.73 33.04 32.82 3.12 30.58 30.58 3.56 27.97 27.97

2.73 33.26 26.45 3.12 30.41 25.47 3.56 27.26 24.30

2.74 36.00 27.47 3.13 33.12 26.57 3.58 30.03 25.59

2.76 39.19 21.46 3.16 36.22 20.68 3.61 33.12 19.74

2.76 34.04 34.04 3.15 31.58 31.58 3.60 28.94 28.94

2.76 34.09 34.09 3.15 31.62 31.62 3.60 28.98 28.98

2.77 33.77 27.94 3.16 30.89 26.97 3.60 27.73 25.85

2.77 36.45 28.95 3.17 33.55 28.08 3.62 30.48 27.11

2.80 39.58 22.24 3.20 36.58 21.46 3.65 33.42 20.55

Total
Sys
kW 4.03 4.03 4.03 4.05 4.08 4.08 4.08 4.08 4.09 4.12 4.12 4.12 4.11 4.13 4.16

125 (52)
Capacity
MBtuh
Total Sens 23.44 23.44 23.49 23.49 22.54 20.97 25.85 22.65 29.43 17.90 24.77 24.77 24.83 24.83 23.13 22.62 26.44 24.43 29.83 18.82 25.94 25.94 25.98 25.98 23.68 24.16 26.96 26.05 30.10 19.65

Total
Sys
kW 4.55 4.55 4.53 4.64 4.66 4.64 4.64 4.58 4.67 4.70 4.71 4.71 4.64 4.71 4.75

Specifications subject to change without notice.

HEATING CAPACITY 36

INDOOR AIR

EDB
65 (18)
70 (21)
75 (24)

CFM
1050 1200 1350 1050 1200 1350 1050 1200 1350

10 (23)

Capacity MBtuh

Total Integ

10.63 9.78

10.83 9.96

11.01 10.13

10.08 9.27

10.27 9.45

10.45 9.61

9.51

8.75

9.70

8.92

9.86

9.07

Total Sys kW
2.08 2.09 2.11 2.15 2.17 2.19 2.24 2.26 2.28

0 (18) Capacity
MBtuh Total Integ 13.98 12.86 14.19 13.05 14.39 13.24 13.46 12.38 13.66 12.57 13.86 12.75 12.91 11.88 13.14 12.09 13.33 12.27

Total Sys kW
2.18 2.19 2.21 2.26 2.27 2.29 2.35 2.37 2.38

10 (12) Capacity
MBtuh Total Integ 17.60 16.15 17.87 16.40 18.09 16.61 17.08 15.67 17.36 15.94 17.59 16.14 16.55 15.19 16.82 15.44 17.04 15.64

Total Sys kW
2.29 2.30 2.31 2.38 2.38 2.39 2.48 2.48 2.49

OUTDOOR COIL ENTERING AIR TEMPERATURES _F (°C)

20 (7)

30 (1)

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

Total Sys kW

21.69 19.67 2.41 26.19 22.94 2.56

22.40 20.31 2.42 26.47 23.19 2.54

22.61 20.51 2.42 26.70 23.40 2.53

21.12 19.15 2.51 25.84 22.64 2.67

21.43 19.44 2.50 26.11 22.88 2.65

21.70 19.68 2.50 26.35 23.09 2.64

20.59 18.68 2.61 25.51 22.35 2.79

20.89 18.95 2.60 25.78 22.59 2.76

21.15 19.18 2.61 26.00 22.78 2.75

40 (4) Capacity
MBtuh Total Integ 30.74 30.74 31.10 31.10 31.39 31.39 30.33 30.33 30.67 30.67 30.96 30.96 29.92 29.92 30.26 30.26 30.54 30.54

Total Sys kW
2.70 2.66 2.65 2.82 2.78 2.77 2.95 2.91 2.89

50 (10) Capacity
MBtuh Total Integ 36.06 36.06 36.49 36.49 36.68 36.68 35.56 35.56 36.02 36.02 36.27 36.27 35.06 35.06 35.52 35.52 35.82 35.82

Total Sys kW
2.85 2.79 2.76 2.99 2.92 2.89 3.13 3.06 3.02

60 (16) Capacity
MBtuh Total Integ 41.91 41.91 42.00 42.00 41.92 41.92 41.41 41.41 41.55 41.55 41.52 41.52 40.90 40.90 41.07 41.07 41.08 41.08

Total Sys kW
3.00 2.93 2.89 3.14 3.07 3.02 3.29 3.21 3.16

427 55 1503 03

427 55 1503 03

PERFORMANCE DATA (CONT)

COOLING CAPACITY

42

EVAPORATOR

AIR

75 (24)

Capacity MB

CFM EWB

tuh

Total Sens

57 (14) 42.14 42.14

62 (17) 43.42 36.94

1225 63* (17) 44.22 29.99

67 (19) 47.88 31.26

72 (22) 53.01 25.46

57 (14) 44.02 44.02

62 (17) 44.58 39.74

1400 63* (17) 45.24 31.99

67 (19) 48.95 33.40

72 (22) 54.17 26.80

57 (14) 45.62 45.62

62 (17) 45.69 45.69

1575 63* (17) 46.05 33.91

67 (19) 49.78 35.47

72 (22) 55.07 28.09

See page 16 for cooling notes.

Total
Sys
kW 2.64 2.64 2.65 2.67 2.69 2.68 2.69 2.69 2.71 2.73 2.73 2.73 2.73 2.75 2.78

85 (29)
Capacity MB
tuh
Total Sens 39.63 39.63 40.45 35.78 41.17 28.91 44.54 30.15 49.32 24.38 41.35 41.35 41.57 38.42 42.05 30.87 45.46 32.26 50.34 25.70 42.79 42.79 42.85 42.85 42.74 32.75 46.20 34.29 51.13 26.97

CONDENSER ENTERING AIR TEMPERATURES °F (°C)

95 (35)

105 (41)

115 (46)

Total Capacity MB Total Capacity MB Total Capacity MB

Sys

tuh

Sys

tuh

Sys

tuh

kW Total Sens kW Total Sens kW Total Sens

3.08 37.01 37.01 3.57 33.27 33.27 4.08 29.84 29.84

3.09 37.42 34.53 3.57 33.34 33.34 4.09 29.89 29.89

3.09 38.00 27.77 3.58 33.40 26.01 4.08 29.10 24.34

3.11 41.19 29.02 3.61 37.71 27.83 4.17 32.76 26.04

3.15 45.63 23.29 3.64 41.90 22.17 4.21 38.07 21.00

3.13 38.61 38.61 3.62 35.22 35.22 4.16 31.40 31.40

3.13 38.66 38.66 3.62 35.31 35.31 4.16 31.46 31.46

3.13 38.79 29.71 3.62 34.39 28.04 4.14 29.80 26.25

3.16 42.00 31.10 3.65 38.44 29.89 4.22 33.67 28.17

3.19 46.51 24.59 3.69 42.63 23.44 4.25 38.72 22.26

3.18 39.93 39.93 3.67 36.90 36.90 4.24 32.77 32.77

3.18 39.99 39.99 3.67 36.95 36.95 4.24 32.83 32.83

3.18 39.39 31.55 3.67 35.82 30.22 4.22 30.44 28.04

3.20 42.60 33.09 3.70 38.98 31.84 4.26 34.50 30.21

3.23 47.18 25.83 3.73 43.21 24.67 4.30 39.18 23.46

Total
Sys
kW 4.70 4.70 4.69 4.76 4.86 4.77 4.78 4.74 4.82 4.91 4.84 4.84 4.80 4.88 4.96

125 (52)

Capacity MB Total

tuh

Sys

Total Sens kW

26.47 26.47 5.43

26.52 26.52 5.43

24.87 22.66 5.40

28.12 24.34 5.46

33.06 19.39 5.57

27.77 27.77 5.50

27.82 27.82 5.50

25.51 24.46 5.45

28.82 26.35 5.52

34.00 20.78 5.64

28.92 28.92 5.57

28.97 28.97 5.57

26.11 26.11 5.51

29.45 28.21 5.58

34.88 22.14 5.72

Specifications subject to change without notice.

HEATING CAPACITY 42

INDOOR AIR

EDB
65 (18)
70 (21)
75 (24)

CFM
1225 1400 1575 1225 1400 1575 1225 1400 1575

10 (23) Capacity
MBtuh Total Integ 12.34 11.36 12.54 11.54 12.71 11.69 11.85 10.90 12.06 11.09 12.24 11.26 11.26 10.36 11.48 10.56 11.67 10.74

Total Sys kW
2.53 2.55 2.57 2.61 2.63 2.65 2.68 2.70 2.73

0 (18) Capacity
MBtuh Total Integ 15.76 14.50 15.97 14.70 16.16 14.87 15.29 14.07 15.53 14.29 15.73 14.47 14.75 13.57 14.99 13.80 15.21 13.99

Total Sys kW
2.57 2.58 2.59 2.66 2.67 2.69 2.75 2.76 2.78

10 (12) Capacity
MBtuh Total Integ 19.85 18.22 20.10 18.45 20.31 18.64 19.40 17.80 19.67 18.05 19.88 18.25 18.88 17.33 19.15 17.58 19.39 17.80

Total Sys kW
2.65 2.65 2.65 2.75 2.75 2.76 2.86 2.86 2.87

OUTDOOR COIL ENTERING AIR TEMPERATURES _F (°C)

20 (7)

30 (1)

40 (4)

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

25.09 22.75 2.79 29.92 26.22 2.93 35.54 35.54

25.31 22.95 2.78 30.19 26.45 2.91 35.91 35.91

25.49 23.12 2.78 30.42 26.65 2.89 36.21 36.21

24.42 22.15 2.89 29.57 25.91 3.07 35.07 35.07

25.02 22.69 2.90 29.86 26.16 3.04 35.46 35.46

25.23 22.88 2.90 30.11 26.38 3.03 35.77 35.77

23.67 21.47 3.00 29.23 25.61 3.20 34.61 34.61

24.06 21.82 2.99 29.52 25.86 3.18 34.98 34.98

24.38 22.11 2.99 29.75 26.06 3.16 35.30 35.30

Total Sys kW
3.11 3.07 3.04 3.25 3.21 3.19 3.39 3.35 3.33

50 (10) Capacity
MBtuh Total Integ 42.06 42.06 42.55 42.55 42.96 42.96 41.48 41.48 41.97 41.97 42.37 42.37 40.89 40.89 41.38 41.38 41.78 41.78

Total Sys kW
3.32 3.27 3.23 3.46 3.41 3.38 3.61 3.56 3.52

60 (16)

Capacity MBtuh

Total

Integ

49.79

49.79

50.45

50.45

50.96

50.96

49.05

49.05

49.70

49.70

50.21

50.21

48.32

48.32

48.96

48.96

49.46

49.46

Total Sys kW
3.56 3.50 3.46 3.71 3.64 3.60 3.87 3.80 3.76

13

14

PERFORMANCE DATA (CONT)

COOLING CAPACITY

48

EVAPORATOR AIR
CFM EWB
57 (14) 62 (17)

75 (24) Capacity
MBtuh Total Sens 46.42 46.42 47.91 40.50

1400 63* (17) 48.68 33.02 67 (19) 52.27 34.25

72 (22) 57.10 27.89

1600 1800

57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19)

48.26 49.02 49.67 53.29 58.19 49.79 50.03 50.44 54.07

48.26 43.31 35.05 36.42 29.22 49.79 49.53 37.00 38.50

72 (22) 59.02 30.47

See page 16 for cooling notes.

Total Sys kW 3.18 3.18 3.18 3.20 3.22 3.23 3.23 3.24 3.25 3.27 3.28 3.28 3.29 3.30 3.32

85 (29) Capacity
MBtuh Total Sens 44.08 44.08 45.08 39.17 45.78 31.78 49.14 32.98 53.65 26.66 45.74 45.74 46.11 41.79 46.64 33.77 50.03 35.11 54.58 27.94 47.12 47.12 47.17 47.17 47.28 35.67 50.68 37.14 55.27 29.16

CONDENSER ENTERING AIR TEMPERATURES °F (°C)

95 (35)

105 (41)

115 (46)

Total Sys

Capacity MBtuh

Total Sys

Capacity MBtuh

Total Sys

Capacity MBtuh

kW Total Sens kW Total Sens kW Total Sens

3.54 41.54 41.54 3.95 38.75 38.75 4.42 35.66 35.66

3.55 42.09 37.68 3.96 38.91 38.54 4.42 35.70 35.70

3.55 42.67 30.46 3.96 39.29 29.02 4.42 35.60 27.47

3.58 45.78 31.63 3.99 42.12 30.16 4.45 38.13 28.58

3.61 49.95 25.33 4.02 45.93 23.91 4.49 41.59 22.37

3.60 43.02 43.02 4.01 40.04 40.04 4.48 36.76 36.76

3.61 43.09 43.09 4.01 40.09 40.09 4.48 36.80 36.80

3.61 43.39 32.40 4.02 39.87 30.91 4.48 36.05 29.29

3.63 46.50 33.70 4.04 42.68 32.18 4.50 38.56 30.53

3.66 50.71 26.58 4.08 46.53 25.11 4.54 42.02 23.54

3.66 44.25 44.25 4.07 41.10 41.10 4.54 37.62 37.62

3.66 44.30 44.30 4.07 41.15 41.15 4.54 37.65 37.65

3.66 43.93 34.25 4.07 40.31 32.70 4.53 36.41 30.99

3.68 47.02 35.68 4.10 43.10 34.10 4.56 38.87 32.36

3.71 51.27 27.76 4.13 46.95 26.26 4.59 42.32 24.66

Total Sys kW 4.95 4.95 4.95 4.98 5.01 5.02 5.02 5.01 5.03 5.07 5.07 5.07 5.06 5.08 5.12

125 (52) Capacity
MBtuh Total Sens 32.25 32.25 32.29 32.29 31.60 25.78 33.83 26.88 36.91 20.74 33.12 33.12 33.15 33.15 31.96 27.51 34.15 28.73 37.21 21.88 33.80 33.80 33.83 33.83 32.23 29.06 34.38 30.42 37.39 22.97

Total Sys kW 5.57 5.57 5.57 5.59 5.61 5.63 5.63 5.62 5.64 5.66 5.68 5.69 5.67 5.69 5.71

Specifications subject to change without notice.

HEATING CAPACITY 48

INDOOR AIR

ED B

CFM

1400

65 (18)

1600

1800

1400

70 (21)

1600

1800

1400

75 (24)

1600

1800

10 (23) Capacity
MBtuh Total Integ 15.18 13.97 15.30 14.07 15.41 14.18 15.09 13.89 15.19 13.97 15.29 14.07 15.08 13.88 15.16 13.95 15.25 14.03

Total Sys kW
2.94 2.96 2.99 3.06 3.08 3.11 3.20 3.22 3.24

0 (18) Capacity
MBtuh Total Integ 19.00 17.48 19.11 17.58 19.23 17.69 18.87 17.37 18.96 17.45 19.07 17.54 18.82 17.32 18.89 17.38 18.98 17.46

Total Sys kW
3.05 3.07 3.09 3.18 3.19 3.21 3.32 3.33 3.35

10 (12) Capacity
MBtuh Total Integ 23.31 21.40 23.43 21.50 23.55 21.62 23.15 21.25 23.24 21.33 23.35 21.43 23.04 21.15 23.12 21.22 23.21 21.30

Total Sys kW
3.17 3.17 3.19 3.31 3.31 3.32 3.45 3.45 3.46

OUTDOOR COIL ENTERING AIR TEMPERATURES _F (°C)

20 (7)

30 (1)

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

Total Sys kW

28.19 25.57 3.30 33.88 29.68 3.43

28.32 25.68 3.29 34.03 29.82 3.41

28.46 25.81 3.29 34.20 29.96 3.40

27.98 25.37 3.44 33.59 29.43 3.58

28.08 25.47 3.42 33.73 29.55 3.55

28.20 25.58 3.43 33.87 29.68 3.54

27.80 25.21 3.59 33.33 29.20 3.74

27.89 25.30 3.57 33.45 29.31 3.70

28.00 25.39 3.57 33.58 29.42 3.69

40 (4) Capacity
MBtuh Total Integ 40.24 40.24 40.45 40.45 40.66 40.66 39.86 39.86 40.06 40.06 40.25 40.25 39.48 39.48 39.67 39.67 39.85 39.85

Total Sys kW
3.57 3.53 3.51 3.72 3.68 3.66 3.89 3.84 3.82

50 (10) Capacity
MBtuh Total Integ 47.39 47.39 47.70 47.70 47.98 47.98 46.87 46.87 47.18 47.18 47.45 47.45 46.35 46.35 46.65 46.65 46.91 46.91

Total Sys kW
3.71 3.65 3.62 3.86 3.80 3.77 4.03 3.97 3.93

60 (16) Capacity
MBtuh Total Integ 55.53 55.53 55.99 55.99 56.39 56.39 54.85 54.85 55.31 55.31 55.70 55.70 54.16 54.16 54.61 54.61 55.01 55.01

Total Sys kW
3.84 3.76 3.71 4.01 3.93 3.87 4.18 4.09 4.04

427 55 1503 03

427 55 1503 03

PERFORMANCE DATA (CONT)

COOLING CAPACITY 60

EVAPORATOR AIR

CFM

EWB

1500 1700 1850

57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22)

75 (24) Capacity
MBtuh Total Sens 53.70 53.70 56.51 46.21 57.26 37.98 61.62 39.46 67.09 32.70 55.91 55.91 57.92 49.22 58.63 40.05 63.05 41.68 68.57 34.07 57.35 57.35 58.83 51.31 59.48 41.54 63.92 43.28 69.49 35.05

See page 16 for cooling notes.

Total Sys kW 3.72 3.74 3.75 3.78 3.83 3.78 3.80 3.81 3.84 3.88 3.83 3.84 3.85 3.88 3.93

CONDENSER ENTERING AIR TEMPERATURES _F (°C)

85 (29)

95 (35)

105 (41)

Capacity MBtuh
Total Sens

Total Sys kW

Capacity MBtuh
Total Sens

Total Sys kW

Capacity MBtuh
Total Sens

50.79 50.79 4.25 47.77 47.77 4.87 44.64 44.64

53.06 45.28 4.27 49.52 44.21 4.89 45.86 42.96

53.73 37.03 4.28 50.11 35.97 4.90 46.36 34.78

57.81 38.52 4.32 53.91 37.46 4.94 49.85 36.25

62.88 31.73 4.36 58.56 30.66 4.99 54.07 29.45

52.81 52.81 4.32 49.60 49.60 4.94 46.27 46.27

54.33 48.19 4.33 50.68 47.03 4.95 46.90 45.63

54.95 39.07 4.34 51.18 37.98 4.96 47.27 36.73

59.07 40.70 4.38 55.00 39.60 5.00 50.76 38.34

64.19 33.07 4.42 59.69 31.95 5.05 55.01 30.69

54.11 54.11 4.37 50.79 50.79 4.99 47.33 47.33

55.15 50.22 4.38 51.43 48.93 5.00 47.52 47.52

55.69 40.53 4.38 51.83 39.41 5.00 47.83 38.14

59.83 42.27 4.42 55.65 41.14 5.04 51.31 39.85

64.99 34.02 4.46 60.36 32.87 5.10 55.59 31.59

Total Sys kW 5.59 5.61 5.62 5.67 5.72 5.67 5.68 5.68 5.73 5.79 5.72 5.72 5.73 5.78 5.83

115 (46) Capacity
MBtuh Total Sens 41.30 41.30 42.02 41.46 42.40 33.40 45.56 34.86 49.38 28.08 42.73 42.73 42.89 42.89 43.17 35.30 46.33 36.90 50.18 29.28 43.64 43.64 43.70 43.70 43.62 36.67 46.77 38.38 50.64 30.14

Total Sys kW 6.44 6.45 6.46 6.51 6.58 6.52 6.52 6.53 6.58 6.64 6.57 6.58 6.57 6.63 6.69

Specifications subject to change without notice.

HEATING CAPACITY 60

INDOOR AIR

EDB
65 (18)
70 (21)
75 (24)

CFM
1500 1700 1850 1500 1700 1850 1500 1700 1850

10 (23) Capacity
MBtuh Total Integ 20.53 18.88 20.57 18.92 20.61 18.96 20.52 18.88 20.57 18.92 20.62 18.97 20.49 18.85 20.55 18.91 20.60 18.96

Total Sys kW
3.42 3.41 3.41 3.60 3.59 3.59 3.80 3.78 3.78

0 (18) Capacity
MBtuh Total Integ 24.97 22.98 24.98 22.99 25.01 23.01 24.95 22.96 24.97 22.98 25.00 23.00 24.92 22.93 24.94 22.95 24.97 22.98

Total Sys kW
3.56 3.54 3.53 3.76 3.73 3.72 3.97 3.94 3.92

10 (12) Capacity
MBtuh Total Integ 30.06 27.59 30.04 27.57 30.04 27.57 30.01 27.55 29.99 27.53 29.99 27.53 29.95 27.49 29.94 27.48 29.94 27.48

Total Sys kW
3.71 3.67 3.65 3.92 3.87 3.85 4.14 4.09 4.07

OUTDOOR COIL ENTERING AIR TEMPERATURES °F (°C)

20 (7)

30 (1)

Capacity MBtuh
Total Integ

Total Sys kW

Capacity MBtuh
Total Integ

Total Sys kW

35.90 32.56 3.88 42.74 37.45 4.07

35.85 32.51 3.82 42.65 37.37 3.99

35.83 32.50 3.79 42.61 37.33 3.94

35.80 32.47 4.10 42.58 37.31 4.30

35.75 32.42 4.03 42.49 37.23 4.21

35.73 32.41 4.00 42.44 37.19 4.16

35.71 32.39 4.34 42.41 37.16 4.55

35.66 32.34 4.26 42.32 37.08 4.45

35.64 32.32 4.22 42.28 37.05 4.39

40 (4) Capacity
MBtuh Total Integ 50.54 50.54 50.44 50.44 50.39 50.39 50.25 50.25 50.15 50.15 50.11 50.11 49.95 49.95 49.85 49.85 49.80 49.80

Total Sys kW
4.32 4.21 4.15 4.55 4.43 4.37 4.80 4.67 4.60

50 (10) Capacity
MBtuh Total Integ 59.05 59.05 58.95 58.95 58.90 58.90 58.66 58.66 58.55 58.55 58.50 58.50 58.27 58.27 58.15 58.15 58.09 58.09

Total Sys kW
4.52 4.38 4.30 4.77 4.61 4.53 5.03 4.86 4.77

60 (16) Capacity
MBtuh Total Integ 68.78 68.78 68.71 68.71 68.69 68.69 68.28 68.28 68.19 68.19 68.15 68.15 67.78 67.78 67.67 67.67 67.63 67.63

Total Sys kW
4.75 4.56 4.46 5.02 4.81 4.69 5.30 5.08 4.95

15

16

PERFORMANCE DATA (CONT)
LEGEND BF-- Bypass Factor db - Dry Bulb edb-- Entering Dry-Bulb Ewb -- Entering Wet-Bulb kW -- Total Unit Power Input ldb-- Leaving Dry-Bulb lwb-- Leaving Wet-Bulb SHC -- Sensible Heat Capacity (1000 Btuh) TC -- Total Capacity (1000 Btuh) (net)
*At 75_F (23.9_C) entering dry bulb (Tennessee Valley Authority [TVA] rating conditions); all other at 80_F (26.75_C) entering dry bulb.
COOLING NOTES: 1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat. 2. Direct interpolation is permissible. Do not extrapolate. 3. The following formulas may be used:

Specifications subject to change without notice.

Sensible capacity (Btuh) tldb = tedb -
1.10 x CFM

tlwb = Wet-bulb temperature corresponding to enthalpy air leaving evaporator coil (hlwb)

hlwb =thoetwalbca-pacity (Btuh) 4.5 x CFM

Where: hewb = Enthalpy of air entering evaporator coil

4. The SHC is based on 80_F (26.7_C) edb temperature of air entering evaporator coil. Below 80_F (26.7_C) edb, subtract (corr factor x CFM) from SHC. Above 80_F (26.7_C) edb, add (corr factor x CFM) to SHC. Correction Factor = 1.10 x (1 - BF) x (edb - 80).

427 55 1503 03

PERFORMANCE DATA (CONT)

Filter Pressure Drop (IN. W.C.)

FILTER SIZE in. (mm)
20X20X1 (508X508X25)
20X24X1 (508X610x25)
24X30X1 (610X762x25)
24X36X1 (610X914X25)

500 600 700 800 900 0.05 0.07 0.08 0.10 0.12

--

--

-- 0.08 0.09

--

--

-- 0.04 0.05

--

--

--

--

--

1000 0.13 0.10 0.06 --

1100 0.14 0.11 0.07 --

1200 0.15 0.13 0.07 0.06

CFM 1300 1400

--

--

0.14 0.15

0.08 0.09

0.07 0.07

1500 -- 0.16 0.10 0.08

1600 -- -- -- 0.09

1700 -- -- -- 0.09

1800 -- -- -- 0.10

1900 -- -- -- 0.11

2000 -- -- -- 0.12

2100 -- -- -- 0.13

2200 -- -- -- 0.14

Accessory Electric Heat Pressure Drop (IN. W.C.)

HEATER

kW

800

1000

1200

1400

CFM

1600

5-20

0.033

0.037

0.042

0.047

0.052

1800 0.060

2000 0.067

2200 0.075

Wet Coil Air Delivery* (Deduct 10 percent for 208 Volt Operation)

230 VOLT HORIZONTAL DISCHARGE

UNIT SIZE

SPEED TAP

AIR DELIVERY2

0.1

0.2

EXTERNAL STATIC PRESSURE (IN. W.C.)

0.3

0.4

0.5

0.6

0.7

1

SCFM

933

799

758

707

675

608

549

24

2

3

SCFM SCFM

1016

921

882

854

809

761

711

1079

1041

1003

970

944

909

866

1

SCFM

1052

1018

984

943

914

879

833

30

2

3

SCFM SCFM

1141 1246

1107 1213

1069 1181

1036 1144

1006 1108

974 1078

932 1043

1

SCFM

1311

1253

1195

1136

1083

1023

958

36

2

3

SCFM SCFM

1413 1571

1364 1525

1313 1473

1256 1423

1203 1364

1148 1313

1084 1261

1

SCFM

1499

1434

1394

1349

1307

1273

1232

42

2

3

SCFM SCFM

1568 1635

1532 1593

1497 1560

1459 1523

1407 1484

1381 1439

1346 1406

1

SCFM

1657

1625

1590

1554

1517

1486

1448

48

2

3

SCFM SCFM

1707 1931

1673 1900

1644 1870

1614 1840

1586 1809

1549 1778

1515 1749

1

SCFM

1774

1746

1717

1678

1639

1590

1538

60

2

3

SCFM SCFM

1857 2183

1820 2144

1784 2115

1752 2079

1720 2049

1671 2018

1625 1986

0.8 497 668 810 795 899 1015 895 1022 1210 1169 1304 1369 1417 1479 1714 1492 1579 1933

0.9 435 599 764 732 856 973 818 969 1156 1108 1252 1335 1381 1449 1683 1461 1532 1859

1.0 394 552 724 678 784 931 729 882 1090 1038 1185 1264 1340 1407 1646 1418 1509 1733

*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static pressure available for ducting. NOTES: 1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point. 2. Standard Cubic Feet per Minute

427 55 1503 03

Specifications subject to change without notice.

17

ELECTRICAL DATA

Units

Nominal VPHHZ

Voltage Range
MIN MAX

Compressor RLA LRA

OFM IFM FLA FLA

24

208/230160 197 253 10.3

61.6

0.9

2.8

30

208/230160 197 253 13.5

72.5

0.9

2.8

36

208/230160 197 253 14.7

75.0

1.7

4.1

42

208/230160 197 253 16.3 112.3

1.7

4.1

48

208/230160 197 253 18.3 108.0

1.7

6.0

60

208/230160 197 253 26.2 144.2

1.9

7.6

Electrical Heat

Nominal

FLA

kW*

208 240

/





3.8/5

18 20.8

5.6/7.2

27 31.3

7.5/10

36.1 41.7

/





3.8/5

18 20.8

5.6/7.2

27 31.3

7.5/10

36.1 41.7

/





3.8/5

18 20.8

5.6/7.2

27 31.3

7.5/10

36.1 41.7

11.3/15

54.1 62.5

/





3.8/5

18 20.8

5.6/7.2

27 31.3

7.5/10

36.1 41.7

11.3/15

54.1 62.5

/





3.8/5

18 20.8

5.6/7.2

27 31.3

7.5/10

36.1 41.7

11.3/15

54.1 62.5

15.0/20.0 72.1 83.3

/





3.8/5

18 20.8

5.6/7.2

27 31.3

7.5/10

36.1 41.7

11.3/15

54.1 62.5

15.0/20.0 72.1 83.3

Power Supply

MCA

208

230

MOCP**

16.6

16.6

25

39.1

42.6

40/45

50.3

55.7

60/60

61.7

68.7

70/70

20.6

20.6

30

43.1

46.6

45/50

54.3

59.7

60/60

65.7

72.7

70/80

24.2

24.2

35

46.7

50.2

50/60

57.9

63.3

60/70

69.3

76.3

70/80

91.8 102.3 100/110

26.1

26.1

40

48.7

52.5

50/60

59.9

65.3

60/70

71.3

78.3

80/80

93.8 104.3 100/110

30.6

30.6

45

53.1

56.6

60/60

64.3

69.7

70/70

75.7

82.7

80/90

98.2 108.7 100/110

120.7

134

125/150

42.3

42.3

60

64.8

68.3

70/70

76.0

81.4

80/90

87.4

94.4

90/100

109.9 120.4 110/125

132.4 146.4 150/150

*kW @ 208/240 ** HACR Type Circuit Breaker
LEGEND FLA - Full Load Amps LRA - Locked Rotor Amps MCA - Minimum Circuit Amps MOCP - Maximum Overcurrent Protection RLA - Rated Load Amps
NOTES: 1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse or circuit breaker. 2. Minimum wire size is based on 60_C copper wire. If other than 60_C wire is used, or if length exceeds wire length in table, determine size from NEC.

*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

18

Specifications subject to change without notice.

427 55 1503 03

TYPICAL INSTALLATION
RETURN AIR TOP COVER

INDOOR THERMOSTAT
FROM POWER SOURCE

Power Wiring Control Wiring
Condenser Airflow
Evaporator Airflow

LOW VOLTAGE ENTRY

POWER ENTRY
COMPOSITE RUST-PROOF BASEPAN
CONDENSATE DRAIN CONNECTION

DISCONNECT PER NEC (UNIT AND ELECTRIC HEATER)
A10135

427 55 1503 03

Specifications subject to change without notice.

19

TYPICAL CONNECTION WIRING SCHEMATIC--208/230-1-60

A14563

20

Specifications subject to change without notice.

427 55 1503 03

TYPICAL LADDER WIRING SCHEMATIC--208/230-1-60

427 55 1503 03

Specifications subject to change without notice.

A14564
21

TYPICAL WIRING SCHEMATIC (CONT)
Wires to be removed

Accessory Electric Heater Wiring

A14444

CONTROLS
Sequence of operation
When power is supplied to unit, the transformer (TRAN) is energized.
Cooling Operation -- With a call for cooling (O,Y,G), the reversing valve, contactor, and indoor fan are energized. When the cooling demand is met, Y and G are de-energized, shutting off the contactor (compressor, outdoor fan). The indoor fan stops after a 60 second delay.
Heating Operation -- With a call for heating (Y,G), the contactor and indoor fan are energized. When the heating demand is met, Y and G are de-energized, shutting off the contactor (compressor, outdoor fan). The indoor fan stops after a 60 second delay.
Continuous Fan -- With the continuous indoor fan option selected on the thermostat, G is continuously energized keeping the indoor fan running at all times.
Defrost -- The defrost control is a time/temperature control which includes a field-selectable time period between defrost cycles of 30, 60, and 90 minutes. Electronic timer and defrost cycle start only when contactor is energized and defrost thermostat (DFT) is closed.
Defrost mode is identical to cooling mode, except outdoor fan motor stops and a bank of optional electric heat turns on to warm air supplying the conditioned space.

APPLICATION DATA
Condensate trap -- A 2-in. (51 mm) condensate trap must be field supplied.

1" (25 mm) MIN.

TRAP OUTLET

2" (51 mm) MIN.

Maximum cooling airflow -- To minimize the possibility of condensate blow-off from the evaporator, airflow through the units should not exceed 450 CFM/ton.
Minimum cooling airflow -- The minimum cooling airflow is 350 cfm/ton.
Minimum cooling operating outdoor air temperature -- All standard units have a minimum ambient operating temperature of 40F (4.4C). With accessory low ambient temperature kit, units can operate at temperatures down to 0F (-17.8C).
Maximum operating outdoor air temperature -- Maximum outdoor operating air temperature for cooling is 125F (51.7C).

22

Specifications subject to change without notice.

427 55 1503 03

GUIDE SPECIFICATIONS
SMALL PACKAGED PRODUCT AIR-TO-AIR HEAT PUMP CONSTANT VOLUME APPLICATION
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 2 TO 5 TONS, NOMINAL (COOLING)
PART I - GENERAL SYSTEM DESCRIPTION
Outdoor packaged, electrically controlled, air-to-air heat pump utilizing a scroll compressor for heating and cooling duty. Unit shall discharge supply air horizontally as shown on contract drawings.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with AHRI Standards 210/240, and 270. Designed in accordance with UL Standard 1995.
B. Unit shall be designed to conform to ASHRAE 15.
C. Unit shall be UL listed as a total package for safety requirements.
D. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer's recommendations.
PART 2- PRODUCTS
EQUIPMENT
A. General:
Factory-assembled, single piece, air-to-air heat pump. Contained within the unit enclosure shall be all factory wiring, piping, controls, and refrigerant charge (R-410A).
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated, bonderized, zinc-coated, prepainted steel.
2. Basepan shall be made of a single-piece non-corrosive, composite material.
3. Indoor fan compartment cabinet surfaces shall be insulated with a minimum 1/2 in. (12.7 mm) thick, flexible insulation, coated on the air side, with aluminum foil-faced insulation.
4. Cabinet panels shall be easily removable for servicing.
5. Unit shall have a factory-installed, sloped, noncorrosive, condensate drain.
6. Unit insulation conforms to ASHRAE 62P.
C. Fans:
1. Indoor Blower (Indoor Fan):
a. Fan shall be multispeed, direct drive as shown on the equipment drawings.
b. Fan wheel shall be made from steel, be double-inlet type. It shall have forward-curved blades with a corrosion-resistant finish and shall be dynamically balanced.
2. Outdoor fan shall be of the direct-driven propeller type with aluminum blades, riveted to corrosion-resistant steel spiders. It shall be dynamically balanced, and shall discharge air upwards.
D. Compressor:
Fully-hermetic scroll type with external vibration isolation.

E. Coils:
1. Indoor and outdoor coils shall have aluminum-plate fins mechanically bonded to seamless copper tubes with all joints brazed.
2. Tube sheet openings shall be bellied to prevent tube wear.
3. Outdoor coil shall be protected by metal louvered panels.
F. Refrigerant Components:
1. TXV and AccuRater feed system.
2. Service gauge connections on suction and discharge lines.
3. Equipped with liquid line filter drier.
4. Equipped with accumulators on all sizes.
G. Controls and Safeties:
1. Unit Controls:
a. Unit shall be complete with self-contained low voltage control circuit.
b. Unit shall incorporate an outdoor coil defrost system to prevent excessive frost accumulation during heating cycle and shall be controlled as follows:
(1.) Defrost shall be initiated on the basis of time and coil temperature.
(2.) A 30/60/90-minute timer shall activate defrost cycle only if coil temperature is low enough to indicate a heavy frost condition.
(3.) Defrost cycle shall terminate when defrost thermostat is satisfied or shall have a positive termination time of 10 minutes.
2. Safeties:
a. High Pressure Switch
b. Loss of Charge Switch
H. Operating Characteristics: 1. Unit shall be capable of starting and running at 125F (51.7C) ambient outdoor temperature [60 size max ambient is 115F (46.1C)]. 2. Compressor with standard controls shall be capable of operation down to 40F (4.4C) ambient outdoor temperature in cooling duty.
3. Compressor shall be capable of operation in heating cycle down to -20F (-28.9C) ambient outdoor-air temperature.
4. Unit shall be capable of simultaneous heating duty and defrost cycle operation when using electric heaters indicated in Section L, Special Features.
I. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
J. Motors:
1. Compressor motors shall be of the refrigerant-cooled type with line break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings and inherent automatic-reset thermal overload protection.
3. Outdoor-fan motor shall be totally enclosed.

427 55 1503 03

Specifications subject to change without notice.

23

GUIDE SPECIFICATIONS (CONT)
K. Grille
1. Louvered Grille:
Louvered grille shall be standard on all units.
L. Special Features Available
1. Coil Options:
Shall include factory-installed optional tin-plated indoor coil.
2. Thermostat:
To provide for two-stage heating and one-stage cooling in addition to manual or automatic changeover and indoor fan control.
3. Low-Ambient Package:
Shall consist of a solid-state control and outdoor coil temperature sensor for controlling outdoor fan motor operation, which shall allow unit to operate down to 0F (-17.8C) outdoor ambient temperature in cooling.

4. Crankcase Heater:
Shall provide anti-floodback protection for low-load cooling applications.
5. Electric heaters: a. Electric heater shall be available as a field-installed option. b. Heater elements shall be open wire type, adequately supported and insulated with ceramic bushings.
c. Electric heater packages must provide single point power connection capability.
6. Compressor Start Kit: Shall be available to give a boost to the compressor motor at each start-up.
7. Outdoor Thermostat Kit:
Thermostat allows for staging of electric heaters based on outdoor air temperature.

Accessory Model Number
CPLOWAMB001A00
CPHSTART002A00 CPCRKHTR008A00 CPCRKHTR004A00

WJH4 ACCESSORIES Description
Low Ambient Control - enables cooling system to operate down to 0 Deg. F by cycling condenser fan on and off. Compressor Start Kit
240V Crankcase Heater

Use With
ALL
ALL 24 - 36 42 - 60

2017 Copyright International Comfort Products Lewisburg, Tennessee 37091 USA

24

Specifications subject to change without notice.

427 55 1503 03


Acrobat Distiller 11.0 (Windows)