Document DEVICE REPORTehb lht cbox 2308COMMERCIAL PRODUCT SPECIFICATIONS PACKAGED HEAT PUMP LHT EnlightTM Rooftop Units High Efficiency - 60 Hz Bulletin No. 210986 August 2023 Supersedes May 2023 ASHRAE 90.1 COMPLIANT 13 to 20 Tons Net Cooling Capacity - 150,000 to 224,000 Btuh Net Heating Capacity - 144,000 to 224,000 Btuh Optional Electric Heat - 15 to 90 kW MODEL NUMBER IDENTIFICATION Brand/Family L = EnlightTM L H T 240 H 4 M N 1 Y Voltage Y = 208/230V-3 phase-60Hz G = 460V-3 phase-60Hz J = 575V-3 phase-60Hz Unit Type H= Heat Pump Unit Minor Design Sequence 1 = 1st Revision Major Design Sequence T = 1st Generation Nominal Cooling Capacity - Tons 156 = 13 Tons 180= 15 Tons 240 = 20 Tons Factory Installed Electric Heat N = No Heat E = 15 kW Electric Heat J = 30 kW Electric Heat K = 45 kW Electric Heat L = 60 kW Electric Heat P = 90 kW Electric Heat Blower Type M = MSAV® Multi-Stage Air Volume, Belt Drive Cooling Efficiency H = High Efficiency Refrigerant Type 4 = R-410A FEATURE HIGHLIGHTS EnlightTM rooftop units featuring the Lennox® CORE Control System create a bright future through a highly energy-efficient and environmentally sustainable design. Comprehensive configurations meet a wide range of applications, making it the most flexible product line Lennox has to offer. 1. Scroll Compressors 2. Check/Thermal Expansion Valves 3. Filter/Driers 4. Reversing Valves 5. Copper Tube Outdoor Coil 6. Outdoor Coil Fan Motors 7. Heavy Gauge Steel Cabinet 8. Hinged Access Panels 9. MSAV® Multi-Stage Air Volume Blower 10. Disconnect Switch (option) 11. Electric Heat (option) 12. Air Filters 13. Lennox CORE®Control System 14. Economizer (option) 15. Barometric Relief Dampers (option) 16. Power Exhaust (option) H CQ OM P J N 8.8.8.8 B L K D E I G F CONTENTS Approvals And Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Cooling/Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Electrical Accessories - Disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Optional Conventional Temperature Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 - Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 - Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 2 APPROVALS AND WARRANTY APPROVALS · AHRI Standard 340/360 certified · ETL and CSA listed · CSA certified energy ratings · Unit and components ETL, NEC and CEC bonded for grounding to meet safety standards for servicing · All models are ASHRAE 90.1 energy efficiency compliant and meet or exceed requirements of Section 6.8 · All models meet DOE 2023 energy efficiency standards · All models meet California Code of Regulations, Title 24 and ASHRAE 90.1 Section 6.4.3.10 requirements for staged airflow · All units are ENERGY STAR® certified · ISO 9001 Registered Manufacturing Quality System WARRANTY · Compressors - Limited five years · Lennox CORE® Unit Controller - Limited three years · Variable Frequency Drive (VFD) - Limited five years · High Performance Economizers (optional) - Limited five years · All other covered components - Limited one year FEATURES AND BENEFITS COOLING/HEATING SYSTEM High Pressure Switches · Designed to maximize sensible and latent cooling performance at design conditions · Mechanical cooling operates from 0°F to 125°F · Protects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation · Mechanical heating operates at ambient temperatures above -15°F NOTE - Optional Electric Heat operates at ambient Low Pressure Switches · Protects the compressors from low pressure conditions such as low refrigerant charge, or low/no airflow temperatures below -4°F and operates in conjunction with mechanical heating down to -15°F. Indoor Coil Freeze Protection · Protects the indoor coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant R-410A Refrigerant · Non-chlorine based charge F Coil Construction · Ozone friendly · Copper tube construction B Compressor System · Scroll compressor on all models for high performance, · Enhanced rippled-edge aluminum fins · Flared shoulder tubing connections reliability, and quiet operation · Silver soldered construction · Resiliently mounted on rubber grommets for quiet operation Compressor Crankcase Heaters · Protects against refrigerant migration that can occur during low ambient operation · Factory leak tested Indoor Coil · Cross-row circuiting · Rifled copper tubing C Check/Thermal Expansion Valves · Ensures optimal performance throughout the application Outdoor Coil · Two independent slanted coils for easy cleaning range Antimicrobial Condensate Drain Pan · Removable element head D Filter/Driers · High capacity filter/drier protects the system from dirt and moisture E Reversing Valve · 4-way interchange reversing valve rapidly changes · Composite pan, sloped to meet drainage requirements per ASHRAE 62.1 · Anti-Microbial additive prevents growth of mold and mildew, which improves indoor air quality and reduces drain line blockage · Side or bottom drain connections the direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 3 FEATURES AND BENEFITS COOLING / HEATING SYSTEM (continued) G Outdoor Coil Fan Motors · All models have PSC motors · Thermal overload protected · Totally enclosed · Permanently lubricated ball bearings · Shaft up · Wire basket mount Outdoor Coil Fan · PVC coated fan guards furnished Required Selections Cooling Capacity · Specify nominal cooling capacity Options/Accessories Field Installed Condensate Drain Trap · Available in copper or PVC Factory or Field Installed Drain Pan Overflow Switch · Monitors condensate level in drain pan · Shuts down unit if drain becomes clogged CABINET H Construction · Heavy-gauge steel panels · Full perimeter heavy-gauge galvanized steel base rail · Base rails have rigging holes · Three sides of the base rail have fork slots · Raised edges around duct and power entry openings in the bottom of the unit for water protection Airflow Choice · Units are shipped in downflow (vertical) configuration NOTE - Units can be field converted to horizontal air flow with optional Horizontal Return Air Panel Kit and Horizontal Roof Curb. Power Entry · Electrical lines can be routed through the unit base or through horizontal access knock-outs Exterior Panels · Constructed of heavy-gauge, galvanized steel · Textured pre-paint with polyurethane finish · Cyclic salt fog and UV exposure up to 1,680 hours per ASTM D5894 Insulation · Fully insulated with non-hygroscopic fiberglass insulation (conditioned areas) · Unit base is fully insulated · Base insulation serves as an air seal to the roof curb, eliminating the need to add a seal during installation I Hinged Access Panels · Filter section · Heating/blower section · Compressor/controls section · Panel seals and quarter-turn latching handles provide a tight air and water seal Required Selections Airflow Configuration · Specify downflow or horizontal Options/Accessories Factory Installed Corrosion Protection · Completely flexible immersed coating · Electrodeposited dry film process (AST ElectroFin E-Coat) · ASTM B117 / DIN 53167 Salt Spray - 15,000+ hours · ASTM G85 Annex A3 SWAAT Modified Salt Spray - 3,000 hours · VA Master Construction Specification Division 23 for High Humidity Installations · CID AA-52474A (GSA) · Indoor Corrosion Protection: · Coated coil · Painted blower housing · Painted base · Outdoor Corrosion Protection: · Coated coil · Painted outdoor base Factory or Field Installed Combination Coil/Hail Guards · Heavy gauge steel frame · Painted to match cabinet · Expanded metal mesh protects outdoor coil Field Installed Horizontal Return Air Panel Kit · Required for horizontal applications with Horizontal Roof Curb · Contains panel with return air opening for field replacement of existing unit panel and panel to cover bottom return air opening in unit · See dimension drawings EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 4 FEATURES AND BENEFITS BLOWER A wide selection of supply air blower options are available to meet a variety of airflow requirements. Motor · Overload protected · Ball bearings NOTE - All blower motors 5 hp and above meet minimum energy efficiency standards in accordance with the Energy Independence and Security Act (EISA). of 2007 J Supply Air Blower · Forward curved blades · Double inlet · Blower wheel is statically and dynamically balanced · Ball bearings · Adjustable pulley (allows speed change) · Blower assembly slides out of unit for servicing · Grease fittings furnished · MSAV® Multi-Stage Air Volume stages the amount of airflow according to compressor stages, heating demand, ventilation demand or smoke alarm · MSAV® Multi-Stage Air Volume utilizes a Variable Frequency Drive (VFD) to stage the supply blower airflow · VFD alters the frequency and voltage of the power supply to the blower to control blower speed · The amount of airflow for each stage can be set according to a parameter in the Lennox® CORE Unit Controller · Unit is shipped from the factory with preset airflow · LHT180H models with MSAV® Multi-Stage Air Volume can be ordered with or without an Electronic Bypass Control · If equipped with the bypass control the MSAV® MultiStage Air Volume features manual (default) or automatic electronic bypass control of the VFD · In case of a VFD malfunction, a VFD alarm is generated by the Lennox® CORE Unit controller · VFD can be manually bypassed to continue unit operation at full blower speed or the unit controller can be set to automatically switch to full blower speed if a VFD alarm is generated · VFD has an operational range of 40 to 125°F outdoor air ambient temperature · Lower operating costs are obtained when the blower is operated on lower speeds Required Selections NOTE - Units equipped a Variable Frequency Drive (VFD) are designed to operate on balanced, three-phase power. Operating units on unbalanced three-phase power will reduce the reliability of all electrical components in the unit. Unbalanced power is a result of the power delivery system supplied by the local utility company. Factory-installed inverters are sized to drive blower motors with an equivalent current rating using balanced threephase power. If unbalanced three-phase power is supplied, the installer must replace the existing factory-installed inverter with an inverter that has a higher current rating to allow for the imbalance. Refer to the installation instructions for additional information and replacement information. Ordering Information · Specify motor horsepower and drive kit number when base unit is ordered Options/Accessories Field Installed Blower Belt Auto-Tensioner · Provides proper tension to belt drive blower belt without the need for regular adjustments · Maintains airflow and proper performance ELECTRICAL NOTE - All units include terminal block and fuse block in power entry junction box for single power entry application. SmartWireTM System · Keyed and color-coded wiring connectors prevent miswiring · Wire coloring scheme is standardized across all models · Each connection is intuitively labeled to make troubleshooting and servicing quick and easy Electrical Plugs · Positive connection electrical plugs connect common accessories or maintenance parts for easy removal or installation Phase/Voltage Detection · Monitors power supply to ensure correct phase at unit start-up · If phase is incorrect, the unit will not start and an alarm code reports to the unit controller · Prevents unit start-up if the unit is the incorrect phase; unit start-ups in the wrong phase could lead to issues such as compressors functioning in reverse · Monitors power supply voltage to ensure proper voltage · If voltage is not correct (over/under voltage conditions) the unit will not start and an alarm code reports to the unit controller EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 5 FEATURES AND BENEFITS ELECTRICAL(continued) Required Selections Voltage Choice · Specify when ordering base unit Options/Accessories Factory Installed Circuit Breakers · HACR type · Overload and short circuit protection · Factory wired and mounted in the power entry panel · Current sensitive and temperature activated · Manual reset Short-Circuit Current Rating (SCCR) · Higher short-circuit protection up to 100kA NOTE - Disconnect Switch not available with higher SCCR option. SCCR option only available with factory installed electric heat. Factory or Field Installed K Disconnect Switch · Accessible outside of unit · Spring loaded weatherproof cover furnished L Electric Heat · Helix wound nichrome elements · Individual element limit controls · Wiring harness · Unit fuse block · See Options/Accessories tables for ordering information GFI Service Outlets (2) · 115V ground fault circuit interrupter (GFCI) type options: · Factory installed, powered and wired · Factory installed, non-powered, field wired · Field installed, non-powered, field wired Field Installed GFI Weatherproof Cover · Single-gang cover · Heavy-duty UV-resistant polycarbonate case construction · Hinged base cover with gasket INDOOR AIR QUALITY M Air Filters · Disposable 2 inch MERV 4 filters furnished as standard Options/Accessories Factory or Field Installed Healthy Climate® High Efficiency Air Filters · Disposable MERV 8 or MERV 13 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2-inch pleated filters Field Installed Healthy Climate® High Efficiency MERV 16 Air Filters · Disposable MERV 16 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2-inch pleated filters Healthy Climate® UVC Germicidal Light Kit · Germicidal lamps emit ultra-violet (UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds · UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan) · Destroys the organism or controls its ability to reproduce · Field installed in the blower/evaporator coil section · Magnetic safety interlock terminates power when access panels are removed · All necessary hardware for installation is included · Lamps operate on 110/230V-1ph power supply NOTE - Step-down transformer may be ordered separately for 460V and 575V units. · Approved by ETL Needlepoint Bipolar Ionization (NPBI) Kit · NPBI technology integrates with system controls for effective air treatment · Ionization has been shown to effectively reduce harmful pathogens, pollutants and odors NOTE - Please visit www.sciencedirect.com for additional information. · Brush-type ionizer introduces a high concentration of both positive and negative ions into the airstream · The bipolar ions are then dispersed into the occupied space through the duct system proactively reducing the airborne contaminants · Ions travel within the building air stream and attach to particles, pathogens, and gas molecules, making them larger and easier to capture in the filtration system · UL 2998 certified for zero ozone emission Indoor Air Quality (CO2) Sensors · Monitors CO2 levels, reports to the Lennox CORE® Unit Controller which adjusts economizer dampers as needed Replacement Filter Media Kit With Frame · Replaces existing pleated filter media · Includes washable metal mesh screen and metal frame with clip for holding replaceable non-pleated filter EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 6 CONTROL SYSTEM LENNOX® CORE CONTROL SYSTEM N The Lennox® CORE Control System is designed to accelerate equipment install and service. Standard with all EnlightTM rooftop units, control system integrates key technologies that lower installation costs, drive system efficiency, and protect your investments. The Lennox® CORE Unit Controller is a microprocessorbased controller that provides flexible control of all unit functions. CORE Mobile Service App · Guided Setup with progress indicators, detailed help, and exportable summaries to manage simple, trouble-free setup, reducing commissioning times · Enhanced Test Functionality provides real-time sensor readings, trending, and reports that enable easy troubleshooting · Ability to set and configure parameters of the CORE Control System to manage sequence of operation · Economizer test function ensures economizer is operating correctly Additional Features: · Built-In 7-Segment Display shows Unit Status and active alarms for easy troubleshooting · Buttons for test and clearing delays · SmartWireTM System with keyed and removable screw terminals ensure correct field wiring · Built-in BACnet MS/TP and IP allow open integration to building management systems. · Two-port Ethernet Switch enables daisy chaining for BACnet IP and automatic firmware updates NOTE - Unit Internet Connection required. · Profile setup copies key settings between units with the same configuration to reduce setup time · USB port allows a technician to download and transfer unit information to help verify service was performed · USB software updates on the Lennox® CORE Unit Controller enhance functionality without the need to change components · Unit Controller Software Configurable Built-In Functions · Discharge Air Cooling Control · Up to three distinct Cooling Airflows in Thermostat Mode · Programmable independent heating, ventilation and cooling blower speeds · Discharge Air Heating Control · Economizer Control Options (See Economizer / Exhaust Air / Outdoor Air sections) · Exhaust Fan Control Modes for fresh air damper position · Configurable Morning Warm-up · Night Setback Mode · Fresh Air Tempering for Improved Ventilation · Demand Control Ventilation · Low Ambient Controls for operation down to 0°F · Two Defrost Control Methods (demand and timed - heat pumps only) Component Protection / Unit Safeguards: · Compressor Time-Off Delay · Adjustable Blower On/Off Delay · Return Air Temperature Limit Control · Safety Switch Input allows Controller to respond to a external safety switch trip · Service Relay Output · Thermostat Bounce Delay · Smoke Alarm Mode has four choices (unit off, positive pressure, negative pressure, purge) · "Strike Three" Protection · Minimum Compressor Run Time Control Methods / Interfaces: · DDC and 24V Thermostat · BACnet MS/TP and IP · LONTalk (Factory and Field Option) · Lennox S-BUS · Compatibility with Lennox Wireless Room Sensors · Zone Temperature Sensor Input · Dehumidistat and Humidity Sensor Inputs · Indoor Air Quality Inputs (2) · Built-in Control Parameter Defaults · Permanent Diagnostic Code Storage · Field Adjustable Control Parameters (Over 200 settings) · Multiple Configurable Digital Inputs · LED Indicators · PC Interface connects the Lennox® CORE Unit Controller to a PC with the Lennox Unit Controller Software NOTE - Lennox® CORE Control System features vary with the type of rooftop unit in which the control is installed. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 7 CONTROL SYSTEM OPTIONS / ACCESSORIES LENNOX® CORE CONTROL SYSTEM (continued) ECONOMIZER Controls Options · Economizer operation is set and controlled by the Factory or Field Installed Blower Proving Switch · Monitors blower operation, shuts down unit if blower fails Lennox® CORE unit controller · Simple plug-in connections from Economizer to unit controller for easy installation · All EnlightTM rooftop units are equipped with factory installed CEC Title 24 approved sensors for outside, Dirty Filter Switch return and discharge air temperature monitoring · Senses static pressure increase and issues alarm if necessary NOTE - Optional sensors may be used instead of unit sensors to determine whether outdoor air is suitable Fresh Air Tempering for free cooling. See Options/Accessories table. · Used in applications with high outside air requirements Factory or Field Installed · Controller energizes the first stage heat as needed to O High Performance Economizer maintain a minimum supply air temperature for comfort, · Approved for California Title 24 building standards regardless of the thermostat demand · Low leakage dampers are Air Movement and Control · When ordered as a factory option, sensor ships with the Association International (AMCA) Class 1A Certified - unit for field installation Maximum 3 CFM per sq. ft. leakage at 1 in. w.g. Smoke Detector · Photoelectric type · Installed in supply air section, return air section or both sections · Available with power board and single sensor (supply or return) or power board and two sensors (supply and return) · Power board located in unit control compartment Interoperability via BACnet® or LonTalk® Protocols · Communication compatible with third-party automation systems that support the BACnet Application Specific Controller device profile, LonMark® Space Comfort Controller functional profile, or LonMark Discharge Air Controller functional profile Commercial Control Systems Field Installed Thermostats · Control system and thermostat options, see page 11 · ASHRAE 90.1 and IECC compliant · Downflow or Horizontal with Outdoor Air Hood · Outdoor Air Hood with mist elimination is included when Economizer is factory installed and is furnished with Economizer when ordered for field installation NOTE - Downflow or horizontal economizer applications require optional Downflow or Horizontal Barometric Relief Dampers with Exhaust Hood. · Linked damper action · High torque 24-volt fully-modulating spring return damper motor · Return air and outdoor air dampers · Plug-in connections to unit NOTE - High Performance Economizers are not approved for use with enthalpy controls in Title 24 applications. NOTE - The Free Cooling setpoint for Title 24 applications must be set based on the Climate Zone where the system is installed. See Section 140.4 "Prescriptive Requirements for Space Conditioning Systems" of the California Energy Commission's 2019 Building Energy Efficiency Standards. NOTE - Refer to Installation Instructions for complete setup information. Differential Sensible Control · Factory setting · Uses outdoor air and return air sensors that are furnished with the unit · The Lennox® CORE unit controller compares outdoor air temperature with return air · When the outdoor air is below the configured setpoint and cooler than return air, the controller activates the Economizer EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 8 OPTIONS / ACCESSORIES ECONOMIZER (continued) EXHAUST Factory or Field Installed NOTE - Differential Sensible Control can be configured in the field to provide Offset Differential Sensible Control or Single Sensible Control. Factory or Field Installed P Downflow Barometric Relief Dampers · Allow relief of excess air NOTE - In Offset Differential Sensible Control mode, the Economizer is enabled if the temperature · Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle differential (offset) between outdoor air and return air reaches the configured setpoint. In Single Sensible Control mode, the Economizer is enabled when outdoor air temperature falls below the configured setpoint. · Exhaust hood is factory installed when dampers are factory installed with Economizer · Exhaust hood is furnished with dampers when ordered for field installation Global Control · Unit controller communicates with a DDC system with · Bird screen furnished Q Power Exhaust Fans one global sensor (enthalpy or sensible) · Install internal to unit for downflow applications only · Determines whether outside air is suitable for free with Economizer option cooling on all units connected to the control system · Provides exhaust air pressure relief · Sensor must be field provided · Interlocked to run when supply air blower is operating Single Enthalpy Control (Not for Title 24) · Outdoor air enthalpy sensor enables Economizer if the outdoor enthalpy is less than the setpoint of the control · Fans run when outdoor air dampers are 50% open (adjustable) · Motor is overload protected Differential Enthalpy Control (Not for Title 24) · Order two Single Enthalpy Controls · Dual propeller type fans are 20 in. diameter · Five blades · One is field installed in the return air section · Two 1/3 hp motors · One is installed in the outdoor air section · SCCR rated · Allows the Economizer control to select between outdoor air or return air, whichever has lower enthalpy Field Installed Outdoor Air CFM Control · Maintains constant outdoor air volume levels on the supply air fan and varying unit airflows · Velocity sensor located in the rooftop unit outdoor air section, the Lennox® CORE unit controller changes the Economizer position to help minimize the effect of supply fan speed changes on outdoor air volume levels · Setpoint for outdoor air volume is established by field testing NOTE - Not available with Demand Control Ventilation (CO2 Sensor) or Building Pressure Control. Building Pressure Control · Maintains constant building pressure level · Includes a static pressure transducer and outdoor static pressure assembly NOTE - Requires Economizer with furnished Outdoor Air Hood and Downflow Barometric Relief Dampers. NOTE - All models are equipped with 2-stage power exhaust fans. Power exhaust operates in 1st stage (one fan) up to 70% of supply air blower speed. Both exhaust fans operate in 2nd stage when supply air blower speed is above 70% (adjustable) of full speed. Field Installed Horizontal Barometric Relief Dampers · For use when unit is configured for horizontal applications requiring an Economizer · Allows relief of excess air · Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle · Field installed in return air duct · Bird screen and hood furnished · Using differential pressure information between the outdoor air and the building air, the Lennox® CORE unit controller changes the Economizer position to help maintain a constant building pressure NOTE - Not available with Demand Control Ventilation (CO2 Sensor) or Outdoor Air CFM Control. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 9 OPTIONS / ACCESSORIES OUTDOOR AIR OPTIONS Factory or Field Installed Outdoor Air Damper · Downflow or Horizontal · Linked mechanical dampers · 0 to 25% (fixed) outdoor air adjustable · Installs in unit · Includes outdoor air hood · Motorized model features fully modulating spring return damper motor with plug-in connection · Manual model features parallel blade, gear-driven dampers with adjustable fixed position NOTE - Manual Outdoor Air Damper is a field installed option only. NOTE - Outdoor Air Hood is included when damper is factory installed and is furnished with damper when ordered for field installation. ROOF CURBS Field Installed · Nailer strip furnished (downflow only) · Mates to unit · US National Roofing Contractors Approved · Shipped knocked down Downflow Hybrid Roof Curbs · Interlocking tabs fasten corners together · No tools required for assembly · Can also be fastened together with furnished hardware · Available in 8, 14, 18, and 24 inch heights Adjustable Pitch Curb · Fully adjustable pitch curbs (3/4 in. per foot in any direction) provide a level platform for rooftop units allowing flexible installations on roofs with uneven or sloped angles · Interlocking tabs fasten corners together · No tools required for assembly · Hardware is furnished to connect upper curb with lower curb · Available in 14 inch height Horizontal · Meet National Roofing Code requirements · Converts unit from downflow to horizontal (side) air flow · Return air is on unit · Supply air is on curb · See dimension drawings · Available in 26, 30, 37, and 41 inch heights NOTE - Requires Horizontal Return Air Panel Kit. NOTE - Optional Insulation Kit is available to help prevent sweating. Adaptor Curbs (not shown) · Curbs are regionally sourced · Dimensions vary based upon the source NOTE - Contact your local sales representative for a detailed cut sheet with applicable dimensions. CEILING DIFFUSERS Field Installed Ceiling Diffusers (Flush or Step-Down) · White powder coat finish on diffuser face and grilles · Insulated UL listed duct liner · Diffuser box has collars for duct connection · Step-down diffusers have double deflection blades · Flush diffusers have fixed blades · Provisions for suspending · Internally sealed to prevent recirculation · Removable return air grille · Adapts to T-bar ceiling grids or plaster ceilings Transitions (Supply and Return) · Used with diffusers · Installs in roof curb · Galvanized steel construction · Flanges furnished for duct connection to diffusers · Fully insulated EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 10 OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS CS8500 Commercial 7-Day Programmable Thermostat CS3000 Commercial 5-2 Day Programmable Thermostat MAINT · Fully Communicating Sensor · Full Color Touchscreen Interface · Variable Speed System Control (On Compatible Units) · Up To 4 Heat / 4 Cool · Built-In Sensors For Temperature, Humidity And Optional CO2 · Remote Sensor Options For Occupancy, Temperature · BACnet Capable Options · 5-2 or 7-Day Scheduling · Smooth Setback Recovery · Heat/Cool Auto-Changeover · Four-Wire Installation · FDD, ASHRAE, IECC Compliant CS7500 Commercial 7-Day Programmable Thermostat Commercial · Conventional Multi-Stage Thermostat · Intuitive Display · Push-Button Operation · Up To 2 Heat / 2 Cool · Built-In Temperature Sensor · Remote Temperature Sensing · Up to 5-2 Day Scheduling · Smooth Setback Recovery · Heat/Cool Auto-changeover Wireless/Wired Temperature/Humidity Room Sensor (LCS-5030) · Premium Universal Thermostat · Full Color Touchscreen Interface · Up To 4 Heat / 3 Cool · Built-In Sensors For Temperature and Humidity · Remote Sensors Options For Temperature, Discharge Air, Outdoor Air · 5-2 or 7-Day Scheduling · Smooth Setback Recovery · Heat/Cool Auto-Changeover · FDD, ASHRAE, IECC Compliant · Simple Push-Button Override · Variable Speed System Control (On Compatible Units) · Up To 4 Heat / 4 Cool · AA Battery / 24VAC Powered · BluetoothTM Mesh Operation · SBUS Wired Operation · Automatic Sensor Averaging · Locking Hex Screw Wireless Repeater for LCS-5030 · Extends Effective Range of Wireless Sensor (LCS-5030) · 24VAC Only · Locking Hex Screw NOTE - Wireless only. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 11 OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS Wired Temperature/Humidity Room Sensor (Non-Communicating) · Terminal blocks for wiring connections · Five-wire sensor connection · Off-white plastic enclosure · Non-adjustable · Relative humidity range: 0 -100% · +/- 3% Accuracy OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS Description CS8500 Commercial 7 Day Programmable Thermostat CS8500 7-Day Thermostat No CO2 Sensing With CO2 Sensing Sensors/Accessories ¹ Remote non-adjustable wall-mount 10k ¹ Remote non-adjustable wall-mount 11k Sysbus Network Cable (Yellow) for CS8500 and LCS-5030 Wired Room Sensor Twisted pair 100% shielded communication cable, Red and Black 22 AWG, yellow jacket, rated at 75°C, 300V, Plenum rated Insulation - Low smoke PVC, NEC, CMP 500 ft. box 1000 ft. box 2500 ft. roll CS7500 Commercial 7-Day Programmable Thermostat CS7500 7-Day Thermostat Sensors/Accessories ² Remote non-adjustable wall-mount 20k ² Remote non-adjustable wall-mount 10k Remote non-adjustable discharge air (duct mount) Outdoor temperature sensor CS3000 Commercial 5-2 Day Programmable Thermostat CS3000 5-2 Day Thermostat Sensors/Accessories Remote non-adjustable wall mount 10k averaging Thermostat wall mounting plate Universal Thermostat Guard with Lock (clear) Inside Dimensions (H x W x D) 5-7/8 x 8-3/8 x 3 in. Temperature/Humidity Room Sensors LCS-5030 Wireless/Wired Temperature/Humidity Room Sensor Wireless Repeater for LCS-5030 A335MT13AE1 Wired Temperature/Humidity Room Sensor (Non-Communicating) 1 Up to nine of the same type remote temperature sensors can be connected in parallel. 2 Remote wall-mount sensors can be applied in any of the following combinations: One Sensor - (1) 47W36, Two Sensors - (2) 47W37, Three Sensors - (2) 47W36 and (1) 47W37 Four Sensors - (4) 47W36, Five Sensors - (3) 47W36 and (2) 47W37 Catalog No. 24K55 24K53 47W37 94L61 27M19 94L63 68M25 24K41 47W36 47W37 19L22 X2658 11Y05 47W37 X2659 39P21 21L07 21L09 21W06 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 12 SEQUENCE OF OPERATION M S AV ® M U LT I - S TA G E A I R VO LU M E Objective: Outline the unit functions as a result of room thermostat or zone sensor demands. Given: When economizer is present, it will function as an integral part of the unit cooling system. When not present, unit will function as if economizer is present but outdoor ambient is high and sensed as not suitable. UNIT OPERATION WITH 2-STAGE THERMOSTAT (2 COOL AND 2 HEAT STAGES, Y1, Y2, W1, W2) Supply Air Blower Speed Unit has following supply air blower speed setting: Ventilation speed Cooling Speed - Low Cooling Speed - High Heating speed Smoke speed (Used only in smoke removal option - not discussed) ¹ Unit Features An Economizer And Outdoor Air Is Suitable Cooling - Thermostat Mode (Y1, Y2) Y1 Demand: All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting). Y2 Demand: All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55°F supply air temperature. If economizer stays at maximum open for 3 minutes, compressor 1 is energized while supply air blower stays on high cooling speed providing maximum cooling capacity. ¹ O utdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection. Unit Does Not Feature An Economizer Or Outdoor Air Is Not Suitable Y1 Demand: Compressor 1 operates, and supply air blower operates at low cooling speed. Y2 Demand: All compressors operate and supply air blower operates at high cooling speed. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 13 SEQUENCE OF OPERATION M S AV ® M U LT I - S TA G E A I R VO LU M E UNIT OPERATION WITH 3-STAGE THERMOSTAT OR ZONE SENSOR (3 COOL AND 2 HEAT STAGES, Y1, Y2, Y3 AND W1, W2) Supply Air Blower Speed Unit has following supply air blower speed setting: Ventilation speed Cooling Speed - Low Cooling Speed - Medium Cooling Speed - High Heating speed Smoke speed (Used only in smoke removal option - not discussed) ¹ Unit Features An Economizer And Outdoor Air Is Suitable Cooling - Thermostat or Zone Sensor Mode (Y1, Y2, Y3) Y1 Demand: All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting). Y2 Demand: All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55°F supply air temperature. If economizer stays at maximum open for 3 minutes, compressor 1 is energized while supply air blower stays on high cooling speed providing maximum cooling capacity. After compressors are energized the economizer stays at maximum open. Y3 Demand: Compressors 1 and 2 are energized while supply air blower stays on high cooling speed. ¹ O utdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection. Unit Does Not Feature An Economizer or Outdoor Air Is Not Suitable Y1 Demand: Compressor 1 operates at part load and supply air blower operates at low cooling speed. Y2 Demand: Compressor 1 operates at part load with compressor 2 ON, and supply air blower operates at medium cooling speed. Y3 Demand: All compressors operate and supply air blower operates at high cooling speed. Defrost Mode Coil Sensors (RT48 - Circuit 1 and RT49 - Circuit 2) and Ambient Sensor (RT17) provides input to the Lennox® CORE Unit Controller to initiate a defrost cycle if needed. Coil sensors are located on a return bend for each circuit on the front of the outdoor coil. Ambient sensor is located on the inside of the corner mullion on the back of the outdoor coil section. If a coil sensor measures a temperature below 35°F during mechanical heating mode, defrost logic is enabled. The system will constantly monitor coil and ambient temperatures and will initiate a defrost cycle if the controller determines that the target temperature difference between the coil and ambient temperature has been satisfied, or when the accumulated run time with coil temperature below 35°F reaches 6 hours. Defrost will not be activated on more than one circuit at the time. If the ambient sensor fails, or the circuit is in uncalibrated state, the controller will switch to time/temperature defrost operation. Electric heat is energized during a defrost cycle to maintain discharge air temperature. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 14 SEQUENCE OF OPERATION M S AV ® M U LT I - S TA G E A I R VO LU M E Heating Mode: Thermostat or Zone Sensor W1 Demand: A first-stage heating demand (W1) will energize compressors 1 and 2 and the outdoor fans. NOTE L1 & L2 reversing valves are de-energized in the heating mode. Units With Optional Electric Heat: An increased heating demand (W2) will energize electric heat. Electric heat is also energized during the defrost cycle (W1) to maintain discharge air temperature. Modulating Outdoor Air Damper The minimum damper position for "occupied low blower" and "occupied high blower" is adjusted during unit setup to provide minimum fresh air requirements per ASHRAE 62.1 at the corresponding supply air blower speeds. When supply air blower is off or the unit is in unoccupied mode, the outdoor air damper is closed. When unit is in occupied mode and supply air blower is operating at a speed below the "midpoint" blower speed, the outdoor air damper is at minimum "low blower" position. When unit is in occupied mode and supply air blower is operating at a speed equal to or above the "midpoint" blower speed, the outdoor air damper is at minimum "high blower" position. NOTE - The "midpoint" blower speed is an average of the minimum and maximum blower speed (minimum speed + maximum speed divided by 2). Power Exhaust Operation NOTE - POWER EXHAUST OPERATION IS THE SAME FOR ALL CONTROL OPTIONS MSAV® models are equipped with 2-stage power exhaust fans. Power exhaust fans operate when economizer outdoor air dampers are 50% open (adjustable). Power exhaust operates in 1st stage (one fan) up to 70% of supply air blower speed. 2nd stage power exhaust fans (both fans) operate when supply air blower speed is above 70% (adjustable) of full speed. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 15 OPTIONS / ACCESSORIES Item Description Catalog Number COOLING SYSTEM Condensate Drain Trap Drain Pan Overflow Switch PVC Copper BLOWER - SUPPLY AIR Blower Option Motors MSAV® Multi-Stage Air Volume option (With VFD Bypass Control) MSAV® Multi-Stage Air Volume option (Without VFD Bypass Control) Belt Drive - 3 hp Belt Drive - 5 hp Belt Drive - 7.5 hp Drive Kits See Blower Data Tables for usage and selection Belt Drive - 10 hp Kit #1 535-725 rpm Kit #2 710-965 rpm Kit #3 685-856 rpm Kit #4 850-1045 rpm Kit #5 945-1185 rpm Kit #6 850-1045 rpm Kit #7 945-1185 rpm Kit #8 1045-1285 rpm Kit #10 1045-1285 rpm Kit #11 1135-1365 rpm Blower Belt Auto-Tensioner 22H54 76W27 21Z07 Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory 24B80 CABINET Combination Coil/Hail Guards Corrosion Protection 23U71 Factory CONTROLS Blower Proving Switch Commercial Controls CPC Einstein Integration LonTalk® Module Novar® LSE Dirty Filter Switch Fresh Air Tempering Smoke Detector - Supply or Return (Power board and one sensor) Smoke Detector - Supply and Return (Power board and two sensors) NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed. 21Z10 Factory 54W27 Factory 53W68 21Z08 22H56 22H57 Unit Model No 156 180 240 X X X X X X OX OX OX O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X X X OX OX OX O O O OX OX OX O O O OX OX OX O O O OX OX OX OX OX OX OX OX OX OX OX OX EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 16 OPTIONS / ACCESSORIES Item Description Catalog Number Unit Model No 156 180 240 INDOOR AIR QUALITY Air Filters Healthy Climate® High Efficiency Air Filters 24 x 24 x 2 (Order 6 per unit) Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media) MERV 8 54W67 OX OX OX MERV 13 52W40 OX OX OX MERV 16 21U42 X X X 44N61 X X X Indoor Air Quality (CO2) Sensors Sensor - Wall-mount, off-white plastic cover with LCD display 77N39 X X X Sensor - Wall-mount, off-white plastic cover, no display 23V86 X X X Sensor - Black plastic case with LCD display, rated for plenum mounting 87N52 X X X Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting 87N54 X X X CO2 Sensor Duct Mounting Kit - for downflow applications 85L43 X X X Aspiration Box - for duct mounting non-plenum rated CO2 sensors (77N39) 90N43 X X X Needlepoint Bipolar Ionization (NPBI) Needlepoint Bipolar Ionization (NPBI) Kit 21U37 X X 21U38 X UVC Germicidal Light Kit 1 Healthy Climate® UVC Light Kit (110/230v-1ph) 21A94 X X X Step-Down Transformers 460V primary, 230V secondary 10H20 X X X 575V primary, 230V secondary 10H21 X X X ELECTRICAL Voltage 60 Hz 208/230V - 3 phase Factory O O O 460V - 3 phase Factory O O O 575V - 3 phase Factory O O O Disconnect Switch (see Electric Heat Tables for usage, HACR Circuit Breakers 80 amp 54W85 OX OX OX 150 amp 54W86 OX OX OX 250 amp 54W87 OX OX OX Factory O O O ² Short-Circuit Current Rating (SCCR) of 100kA (includes Phase/Voltage Detection) Factory O O O GFI Service Outlets 15 amp non-powered, field-wired (208/230V, 460V, 575V) 74M70 OX OX OX 15 amp factory-wired and powered (208/230V, 460V) Factory O O O ³ 20 amp non-powered, field-wired (208/230V, 460V, 575V) 67E01 X X X ³ 20 amp non-powered, field-wired (575V) Factory O O O Weatherproof Cover for GFI 10C89 X X X 1 Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s). 2 Disconnect Switch not available with SCCR option. SCCR option is only available with factory installed electric heat or no electric. SCCR option is not available if the MOCP of the configured unit is greater than 200A. 3 Canada requires a minimum 20 amp circuit. Select 20 amp, non-powered, field wired GFI. NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 17 OPTIONS / ACCESSORIES Item Description Catalog Number Unit Model No 156 180 240 ELECTRIC HEAT 15 kW 30 kW 45 kW 60 kW 208/230V-3ph 22H66 OX OX OX 460V-3ph 22H67 OX OX OX 575V-3ph 22V35 OX OX OX 208/230V-3ph 22H70 OX OX OX 460V-3ph 22H71 OX OX OX 575V-3ph 22V37 OX OX OX 208/230V-3ph 22H74 OX OX OX 460V-3ph 22H75 OX OX OX 575V-3ph 22V39 OX OX OX 208/230V-3ph 22H78 OX OX OX 460V-3ph 22H79 OX OX OX 575V-3ph 22V41 OX OX OX 90 kW 208/230V-3ph 22H80 OX 460V-3ph 22H81 OX 575V-3ph 22V42 OX ECONOMIZER High Performance Economizer (Approved for California Title 24 Building Standards / AMCA Class 1A Certified) High Performance Economizer Downflow or Horizontal - Includes Outdoor Air Hood. Order Downflow or Horizontal Barometric Relief Dampers separately. E1ECON17C-2 22J18 OX OX OX Economizer Controls Differential Enthalpy (Not for Title 24) Order 2 21Z09 OX OX OX Sensible Control Sensor is Furnished Factory O O O Single Enthalpy (Not for Title 24) 21Z09 OX OX OX Global Control Sensor Field Provided Factory O O O Building Pressure Control Outdoor Air CFM Control Barometric Relief Dampers With Exhaust Hood Downflow Barometric Relief Dampers 13J77 X X X 13J76 X X X 54W78 OX OX OX Horizontal Barometric Relief Dampers OUTDOOR AIR 16K99 X X X Outdoor Air Dampers With Outdoor Air Hood Motorized 22J27 OX OX OX Manual NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed. 13U05 X X X EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 18 OPTIONS / ACCESSORIES Item Description Catalog Number Unit Model No 156 180 240 ¹ POWER EXHAUST (DOWNFLOW APPLICATIONS ONLY) Standard Static, SCCR Rated 208/230V 22H90 OX OX OX 460V 22H91 OX OX OX 575V 22V34 OX OX OX ROOF CURBS Hybrid Roof Curbs, Downflow 8 in. height 14 in. height 18 in. height 24 in. height Adjustable Pitch Curb 14 in. height Standard Roof Curbs, Horizontal - Requires Horizontal Return Air Panel Kit 26 in. height - slab applications 37 in. height - rooftop applications Insulation Kit For Standard Horizontal Roof Curbs For 26 in. Curb For 37 in. Curb Horizontal Return Air Panel Kit Required for Horizontal Applications with Roof Curb 11F58 X X X 11F59 X X X 11F60 X X X 11F61 X X X 43W26 X X X 11T89 X X X 11T96 X X X 73K32 X X X 73K34 X X X 87M00 X X X CEILING DIFFUSERS Step-Down - Order one RTD11-185S 13K63 X X RTD11-275S 13K64 X Flush - Order one FD11-185S 13K58 X X FD11-275S 13K59 X Transitions (Supply and Return) - Order one C1DIFF33C-1 12X68 X X C1DIFF34C-1 12X70 X 1 Field installed Power Exhaust requires Economizer with Outdoor Air Hood and Downflow Barometric Relief Dampers with Exhaust Hood. Must be ordered separately. NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 19 SPECIFICATIONS General Data Nominal Tonnage 13 Ton 15 Ton 20 Ton Model Number LHT156H4M LHT180H4M LHT240H4M Efficiency Type High High High Blower Type MSAV® MSAV® MSAV® Multi-Stage Air Volume Multi-Stage Air Volume Multi-Stage Air Volume Cooling Gross Cooling Capacity - Btuh 154,000 181,000 232,000 Performance 1 Net Cooling Capacity - Btuh 150,000 176,000 224,000 1 AHRI Rated Air Flow - cfm 4500 5500 7000 Total Unit Power - kW 12.3 15.8 20.1 1 IEER (Btuh/Watt) 15.7 15.5 15.5 1 EER (Btuh/Watt) 12.1 11.1 11.1 Refrigerant Refrigerant Type R-410A R-410A R-410A Charge Circuit 1 21 lbs. 0 oz. 22 lbs. 12 oz. 22 lbs. 8 oz. Circuit 2 21 lbs. 0 oz. 21 lbs. 12 oz. 21 lbs. 8 oz. Heating 1 Total High Heat Capacity - Btuh 144,000 174,000 224,000 Performance Total Unit Power - kW 12.4 15.0 19.3 1 C.O.P. 3.40 3.40 3.40 1 Total Low Heat Capacity - Btuh 80,000 96,000 128,000 Total Unit Power (kW) 11.1 13.4 17.9 1 C.O.P. 2.10 2.10 2.10 Electric Heat (kW) Available - See page 18 15, 30, 45, 60 kW 15, 30, 45, 60 kW 15, 30, 45, 60, 90 kW Compressor Type (number) Scroll (2) Scroll (2) Scroll (2) Outdoor Coils Net face area (total) - sq. ft. 55.1 55.1 55.1 Number of rows 2 2 2 Fins per inch 20 20 20 Outdoor Coil Motor - (No.) horsepower (6) 1/3 (6) 1/3 (6) 1/3 Fans Motor rpm 1075 1075 1075 Total Motor watts 2150 2150 2150 Diameter - (No.) in. (6) 24 (6) 24 (6) 24 Number of blades 3 3 3 Total Air volume - cfm 16,300 16,300 16,300 Indoor Coils Net face area (total) - sq. ft. 21.4 21.4 21.4 Tube diameter - in. 3/8 3/8 3/8 Number of rows 4 4 4 Fins per inch 14 14 14 Drain connection - No. and size (1) 1in. FPT (1) 1in. FPT (1) 1in. FPT Expansion device type Balance Port Thermostatic Expansion Valve (removable element head) 2 Indoor Nominal motor output 3 hp, 5 hp 3 hp, 5 hp, 7.5 hp 5 hp, 7.5 hp, 10 hp Blower Max. usable motor output (US) 3.45 hp, 5.75 hp 3.45 hp, 5.75 hp, 8.62 hp 5.75 hp, 8.62 hp, 11.5 hp and Drive Selection Motor - Drive kit number 3 hp Kit 1 535-725 rpm Kit 2 710-965 rpm 3 hp Kit 1 535-725 rpm Kit 2 710-965 rpm 5 hp Kit 3 685-856 rpm Kit 4 850-1045 rpm 5 hp 5 hp Kit 5 945-1185 rpm Kit 3 - 685-856 rpm Kit 3 - 685-856 rpm 7.5 hp Kit 4 850-1045 rpm Kit 4 850-1045 rpm Kit 6 850-1045 rpm Kit 5 945-1185 rpm Kit 5 945-1185 rpm Kit 7 945-1185 rpm 7.5 hp Kit 8 1045-1285 rpm Kit 6 850-1045 rpm 10 hp Kit 7 945-1185 rpm Kit 7 945-1185 rpm Kit 8 1045-1285 rpm Kit 10 1045-1285 rpm Kit 11 1135-1365 rpm Blower wheel nominal D x W - in. (2) 15 x 15 in. (2) 15 x 15 in. (2) 15 x 15 Filters Type of filter MERV 4, Disposable Number and size - in. (6) 24 x 24 x 2 Electrical characteristics 208/230V, 460V or 575V - 60 hertz - 3 phase NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 AHRI Certified to AHRI Standard 340/360: Cooling Ratings - 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air. High Temperature Heating Ratings - 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air. Low Temperature Heating Ratings - 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air. 2 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. NOTE Motor service factor limit - 1.0. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 20 COOLING/HEATING RATINGS NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 13 TON - COOLING LHT156H4M (1 COMPRESSOR - PART LOAD) Entering Wet Bulb Tem- Total Air Volume perature cfm Total Cool Cap. kBtuh 65°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 75°F 85°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 1800 58.6 1.96 .77 .94 1.00 55.8 2.26 .79 .96 1.00 52.6 2.62 .81 .99 1.00 63°F 2250 61.8 1.93 .84 1.00 1.00 58.8 2.23 .86 1.00 1.00 55.8 2.59 .89 1.00 1.00 2700 65.2 1.89 .91 1.00 1.00 62.2 2.20 .94 1.00 1.00 58.9 2.57 .97 1.00 1.00 1800 62.8 1.92 .59 .74 .90 59.5 2.22 .59 .76 .92 56.0 2.59 .60 .78 .95 67°F 2250 65.5 1.89 .63 .81 .99 62.2 2.20 .64 .83 1.00 58.6 2.57 .65 .86 1.00 2700 67.5 1.87 .67 .88 1.00 64.1 2.18 .68 .91 1.00 60.2 2.55 .70 .94 1.00 1800 67.2 1.87 .41 .57 .72 64.0 2.18 .41 .58 .73 60.4 2.55 .41 .58 .74 71°F 2250 70.6 2.14 .42 .61 .79 66.6 2.16 .42 .62 .81 62.7 2.53 .43 .63 .83 2700 71.8 1.82 .44 .65 .86 68.1 2.15 .45 .67 .88 64.5 2.51 .46 .68 .91 Total Cool Cap. kBtuh 49.1 52.8 55.7 52.6 54.9 56.6 56.7 59.0 60.6 95°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 3.03 .83 1.00 1.00 3.00 .92 1.00 1.00 2.98 1.00 1.00 1.00 3.01 .61 .80 .98 2.98 .67 .89 1.00 2.97 .72 .98 1.00 2.97 .41 .59 .77 2.95 .44 .65 .86 2.93 .46 .71 .95 13 TON - COOLING LHT156H4M (2 COMPRESSORS - PART LOAD / FULL LOAD) Entering Wet Bulb Tem- Total Air Volume perature cfm Total Cool Cap. kBtuh 85°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 95°F 105°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 3000 124.4 7.04 .69 .82 .94 117.1 7.96 .70 .84 .95 109.5 9.37 .71 .86 .97 63°F 3750 132.1 7.07 .74 .89 .99 124.3 7.99 .76 .91 1.00 116.4 9.39 .78 .93 1.00 4500 138.5 7.09 .79 .94 1.00 131.3 8.02 .81 .95 1.00 120.8 9.41 .83 .98 1.00 3000 133.4 7.07 .54 .67 .79 125.8 7.99 .54 .68 .81 118.0 9.39 .55 .69 .82 67°F 3750 141.0 7.11 .58 .72 .86 133.0 8.03 .58 .73 .88 122.3 9.43 .59 .76 .90 4500 147.2 7.14 .60 .77 .92 138.3 8.05 .61 .79 .93 129.9 9.10 .62 .81 .95 3000 142.5 7.10 .41 .53 .64 135.1 8.03 .41 .53 .65 126.1 9.06 .40 .53 .66 71°F 3750 150.6 7.13 .42 .56 .69 142.3 8.05 .42 .56 .71 131.0 9.54 .42 .58 .73 4500 154.2 7.54 .43 .59 .75 148.1 8.08 .43 .60 .76 140.0 9.54 .44 .61 .78 Total Cool Cap. kBtuh 98.7 107.9 114.2 109.3 115.8 116.9 117.4 125.0 130.3 115°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 10.72 .73 .90 .99 11.97 .80 .95 1.00 11.96 .86 1.00 1.00 11.97 .55 .70 .85 11.97 .59 .77 .92 11.19 .63 .85 .97 11.95 .40 .54 .68 11.17 .42 .58 .74 11.19 .43 .62 .81 13 TON - COOLING LHT156H4M (2 COMPRESSORS - FULL LOAD) Entering Wet Bulb Tem- Total Air Volume perature cfm Total Cool Cap. kBtuh 85°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 95°F 105°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 4160 150.1 8.13 .73 .88 1.00 141.2 9.14 .75 .90 1.00 132.0 10.28 .76 .93 1.00 63°F 5200 157.4 8.20 .79 .96 1.00 148.8 9.20 .81 .99 1.00 140.0 10.34 .84 1.00 1.00 6240 164.7 8.26 .85 1.00 1.00 157.0 9.73 .88 1.00 1.00 147.8 10.41 .90 1.00 1.00 4160 160.1 8.22 .57 .71 .85 151.2 9.23 .57 .72 .87 141.5 10.36 .58 .74 .89 67°F 5200 167.2 8.28 .61 .77 .93 156.2 10.15 .61 .79 .95 147.8 10.41 .62 .81 .98 6240 172.7 8.34 .65 .83 .99 166.1 10.18 .65 .85 1.00 149.7 10.89 .68 .89 1.00 4160 169.9 8.31 .42 .55 .68 160.4 10.17 .42 .56 .70 148.9 10.88 .42 .57 .72 71°F 5200 177.9 8.38 .43 .59 .75 171.6 9.84 .44 .60 .77 159.6 10.92 .44 .61 .78 6240 186.0 8.86 .45 .63 .81 175.0 9.50 .45 .64 .82 164.4 10.96 .46 .66 .85 Total Cool Cap. kBtuh 122.7 131.3 137.0 131.8 135.0 143.3 142.3 148.8 149.7 115°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 11.57 .79 .96 1.00 13.31 .86 1.00 1.00 13.98 .94 1.00 1.00 13.31 .59 .76 .93 13.99 .64 .84 1.00 13.99 .69 .91 1.00 13.99 .42 .58 .73 14.01 .44 .63 .82 12.76 .46 .69 .90 13 TON - HEATING LHT156H4M Indoor Coil Air Volume 70°F Dry Bulb cfm 4160 5200 6240 65°F Total Comp. Heating Motor Capacity Input kBtuh kW 190.6 10.10 196.3 9.32 200.3 8.82 Air Temperature Entering Outdoor Coil 45°F 25°F 5°F Total Comp. Total Comp. Total Heating Motor Heating Motor Heating Capacity Input Capacity Input Capacity kBtuh kW kBtuh kW kBtuh 136.1 8.83 94.7 7.92 61.7 139.6 8.27 96.6 7.53 63.1 142.3 7.92 98.4 7.30 64.5 Comp. Motor Input kW 7.09 6.86 6.73 -15°F Total Comp. Heating Motor Capacity Input kBtuh kW 37.5 6.62 38.6 6.56 39.7 6.55 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 21 COOLING/HEATING RATINGS NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 15 TON - COOLING LHT180H4M (1 COMPRESSOR - PART LOAD) Entering Wet Bulb Tem- perature Total Air Volume cfm Total Cool Cap. kBtuh 65°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 75°F 85°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F Total Cool Cap. kBtuh 95°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 2000 64.3 2.43 0.76 0.94 1 60.6 2.67 0.77 0.98 1 56.8 2.96 0.79 1 1 52.9 3.32 0.81 1 1 63°F 2400 67.1 2.46 0.82 1 1 63.6 2.69 0.83 1 1 60.1 2.98 0.86 1 1 56 3.33 0.89 1 1 2800 70.3 2.49 0.88 1 1 66.8 2.71 0.91 1 1 63.2 2.99 0.95 1 1 58.7 3.34 0.99 1 1 2000 68.9 2.47 0.57 0.73 0.9 65 2.7 0.57 0.74 0.93 60.9 2.98 0.58 0.76 0.96 56.3 3.33 0.58 0.78 1 67°F 2400 71.2 2.49 0.61 0.79 1 67.3 2.71 0.61 0.81 1 63.1 2.99 0.62 0.83 1 58.4 3.34 0.63 0.86 1 2800 73.1 2.51 0.64 0.85 1 69.2 2.72 0.65 0.88 1 65 3 0.67 0.91 1 59.9 3.34 0.68 0.96 1 2000 73.8 2.52 0.4 0.56 0.71 69.9 2.73 0.39 0.56 0.72 65.7 3 0.39 0.56 0.73 60.8 3.34 0.38 0.57 0.75 71°F 2400 76.1 2.54 0.41 0.59 0.77 72.2 2.75 0.41 0.6 0.78 67.9 3.02 0.41 0.61 0.81 62.7 3.35 0.41 0.62 0.84 2800 77.9 2.56 0.43 0.63 0.83 73.8 2.76 0.43 0.64 0.85 69 3.02 0.43 0.66 0.88 64.1 3.36 0.43 0.68 0.93 15 TON - COOLING LHT180H4M (2 COMPRESSORS - PART LOAD / FULL LOAD) Entering Wet Bulb Tem- perature Total Air Volume cfm Total Cool Cap. kBtuh 85°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 95°F 105°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F Total Cool Cap. kBtuh 115°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 3300 138 8.46 0.67 0.81 0.92 129.3 9.47 0.68 0.82 0.94 119.4 10.93 0.69 0.84 0.95 109.6 11.93 0.7 0.86 0.97 63°F 4000 146.3 8.54 0.72 0.87 0.97 136.9 9.52 0.73 0.89 0.99 126.8 10.99 0.74 0.9 1 116.6 11.97 0.76 0.92 1 4800 154.2 8.62 0.77 0.92 1 143.9 9.58 0.79 0.94 1 133.6 11.05 0.81 0.96 1 123 12.39 0.83 0.97 1 3300 149 8.56 0.52 0.65 0.77 139.5 9.54 0.52 0.66 0.79 127.3 10.66 0.52 0.67 0.81 117.8 11.98 0.52 0.68 0.83 67°F 4000 157.2 8.64 0.55 0.69 0.84 146.8 9.61 0.55 0.71 0.85 136 10.73 0.55 0.72 0.87 124.5 12.03 0.56 0.74 0.89 4800 164.1 8.72 0.58 0.75 0.9 152.9 9.67 0.59 0.76 0.91 141.8 10.78 0.59 0.78 0.93 129.6 12.45 0.6 0.81 0.95 3300 160.1 8.66 0.39 0.51 0.63 149.6 9.63 0.38 0.51 0.63 139.4 10.75 0.37 0.51 0.64 127.6 12.43 0.36 0.51 0.66 71°F 4000 167.5 8.74 0.4 0.54 0.67 157.3 9.7 0.4 0.54 0.68 146.4 10.81 0.39 0.54 0.7 132.1 12.49 0.38 0.55 0.72 4800 174.8 8.82 0.42 0.57 0.72 164.2 9.77 0.41 0.58 0.74 152.6 10.87 0.41 0.58 0.76 140.6 12.15 0.4 0.59 0.79 15 TON - COOLING LHT180H4M (2 COMPRESSORS - FULL LOAD) Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Tem- Total Air Volume perature Total Cool Cap. 85°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb Total Cool Cap. 95°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb Total Cool Cap. 105°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb Total Cool Cap. 115°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 4800 176.1 10.46 0.72 0.87 1 165 11.67 0.73 0.89 1 153 13.07 0.74 0.91 1 140.1 15.42 0.77 0.94 1 63°F 6000 185.8 10.55 0.78 0.95 1 174 11.75 0.79 0.97 1 161.8 13.16 0.82 0.99 1 150.7 15.45 0.84 1 1 7200 193.4 10.62 0.84 1 1 182.4 11.83 0.86 1 1 170.9 13.22 0.88 1 1 156.5 15.46 0.91 1 1 4800 188.5 10.58 0.56 0.7 0.83 177.3 11.78 0.56 0.71 0.85 164.5 13.17 0.56 0.72 0.88 152.9 15.45 0.57 0.74 0.91 67°F 6000 197.8 10.66 0.59 0.76 0.91 185.7 11.87 0.6 0.77 0.94 172.5 13.24 0.61 0.79 0.97 155.8 15.46 0.62 0.83 1 7200 204.2 10.74 0.63 0.82 0.98 192.1 11.92 0.64 0.84 1 175 13.84 0.65 0.87 1 165.4 15.48 0.66 0.89 1 4800 201.2 10.71 0.41 0.54 0.67 189.3 11.89 0.41 0.55 0.68 176.3 13.27 0.4 0.55 0.7 164.4 15.47 0.4 0.56 0.71 71°F 6000 210.5 10.8 0.43 0.58 0.73 198.4 12 0.43 0.59 0.75 183.5 13.87 0.42 0.6 0.78 172.9 15.53 0.42 0.61 0.79 7200 217.1 10.97 0.44 0.62 0.79 204.7 12.07 0.44 0.63 0.82 193.3 13.93 0.44 0.64 0.83 177.6 15.58 0.44 0.66 0.87 15 TON - HEATING LHT180H4M Indoor Coil Air Volume 70°F Dry Bulb cfm 4800 6000 7200 65°F Total Comp. Heating Motor Capacity Input kBtuh kW 232.5 12.63 240.4 11.67 247.5 11.08 Air Temperature Entering Outdoor Coil 45°F 25°F 5°F Total Comp. Total Comp. Total Heating Motor Heating Motor Heating Capacity Input Capacity Input Capacity kBtuh kW kBtuh kW kBtuh 165.3 11.38 112.0 10.27 74.7 170.7 10.68 115.5 9.76 77.1 175.1 10.22 118.8 9.45 79.9 Comp. Motor Input kW 9.51 9.17 8.95 -15°F Total Comp. Heating Motor Capacity Input kBtuh kW 45.8 8.73 47.7 8.58 49.9 8.51 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 22 COOLING/HEATING RATINGS NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 20 TON - COOLING LHT240H4M (1 COMPRESSOR - PART LOAD) Entering Wet Bulb Tem- Total Air Volume perature cfm Total Cool Cap. kBtuh 65°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 75°F 85°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 3200 92.2 3.35 0.82 1 1 86.6 3.91 0.84 1 1 80.4 4.54 0.86 1 1 63°F 4000 98 3.33 0.9 1 1 92.4 3.88 0.93 1 1 86 4.52 0.96 1 1 4800 102.7 3.32 0.98 1 1 96.6 3.87 1 1 1 90.2 4.5 1 1 1 3200 98.3 3.33 0.61 0.8 0.98 92.3 3.88 0.61 0.81 0.99 85.1 4.53 0.62 0.84 1 67°F 4000 102.1 3.32 0.66 0.88 1 95.5 3.87 0.66 0.9 1 88.9 4.51 0.68 0.93 1 4800 105 3.32 0.71 0.96 1 98.6 3.87 0.73 0.98 1 91.4 4.5 0.75 1 1 3200 105.1 3.32 0.41 0.6 0.77 98.7 3.87 0.41 0.6 0.78 91.5 4.5 0.4 0.61 0.81 71°F 4000 108.7 3.31 0.44 0.66 0.86 102.1 3.86 0.43 0.66 0.88 94.8 4.48 0.43 0.68 0.91 4800 111.5 3.31 0.46 0.71 0.94 104.6 3.85 0.46 0.73 0.97 97.1 4.47 0.46 0.75 0.99 Total Cool Cap. kBtuh 73.9 79.4 83.7 77.8 81.4 84.2 84.3 87.3 89.6 95°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 5.26 0.89 1 1 5.23 0.99 1 1 5.21 1 1 1 5.24 0.62 0.86 1 5.22 0.7 0.97 1 5.21 0.77 1 1 5.21 0.39 0.62 0.84 5.2 0.42 0.69 0.95 5.19 0.46 0.77 1 20 TON - COOLING LHT240H4M (2 COMPRESSORS - PART LOAD / FULL LOAD) Entering Wet Bulb Tem- Total Air Volume perature cfm Total Cool Cap. kBtuh 85°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 95°F 105°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 4800 182.4 11.6 0.7 0.85 0.96 165.7 13.2 0.7 0.87 0.97 151.9 14.91 0.72 0.89 0.99 63°F 6000 194.3 11.61 0.76 0.92 1 182.6 13.23 0.77 0.93 1 162.7 14.94 0.79 0.95 1 7200 202.9 11.63 0.81 0.97 1 188.4 13.26 0.84 0.98 1 172.8 14.97 0.86 1 1 4800 197.2 11.62 0.54 0.67 0.81 181.3 13.21 0.53 0.68 0.83 164.8 14.95 0.53 0.69 0.85 67°F 6000 208.2 11.63 0.57 0.74 0.89 192.1 13.24 0.57 0.75 0.91 174.6 14.99 0.58 0.77 0.93 7200 217.1 11.65 0.61 0.79 0.95 200.2 13.26 0.62 0.81 0.96 182.2 15.01 0.62 0.84 0.98 4800 212.2 11.63 0.39 0.52 0.65 195.7 13.24 0.38 0.52 0.66 179.8 14.99 0.37 0.52 0.67 71°F 6000 223.8 11.66 0.41 0.56 0.71 207.2 13.26 0.4 0.57 0.73 189.6 15.03 0.39 0.57 0.75 7200 232 11.67 0.43 0.6 0.77 214.7 13.28 0.42 0.61 0.79 196.7 15.05 0.41 0.62 0.82 Total Cool Cap. kBtuh 135.8 146.7 156 148.3 157.1 162.9 162.3 170.4 176.7 115°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 16.9 0.73 0.91 1 16.92 0.82 0.97 1 16.94 0.89 1 1 16.94 0.52 0.71 0.88 16.98 0.58 0.79 0.95 16.99 0.63 0.87 1 16.97 0.35 0.52 0.69 17 0.38 0.58 0.77 17.02 0.4 0.63 0.85 20 TON - COOLING LHT240H4M (2 COMPRESSORS - FULL LOAD) Entering Wet Bulb Tem- Total Air Volume perature cfm Total Cool Cap. kBtuh 85°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F Total Cool Cap. kBtuh Outdoor Air Temperature Entering Outdoor Coil 95°F 105°F Comp. Sensible To Total Total Comp. Sensible To Total Motor Ratio (S/T) Cool Motor Ratio (S/T) Input Dry Bulb Cap. Input Dry Bulb kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F 6400 229.1 14.17 0.73 0.88 1 212.2 15.82 0.73 0.9 1 195.8 17.66 0.75 0.93 1 63°F 8000 241.1 14.3 0.79 0.96 1 223.9 15.94 0.81 0.99 1 207.6 17.78 0.83 1 1 9600 253 14.41 0.85 1 1 236.1 16.07 0.87 1 1 220.6 17.93 0.9 1 1 6400 245.8 14.34 0.56 0.7 0.85 228.6 15.99 0.55 0.71 0.87 210.9 17.83 0.55 0.73 0.89 67°F 8000 259 14.47 0.59 0.77 0.93 240 16.11 0.6 0.78 0.96 221.3 17.94 0.6 0.81 0.98 9600 266.6 14.55 0.63 0.83 0.99 249 16.2 0.64 0.85 1 229.2 18.03 0.65 0.88 1 6400 262.7 14.51 0.41 0.54 0.68 245.3 16.16 0.4 0.55 0.69 227.2 18 0.39 0.55 0.7 71°F 8000 276.4 14.64 0.42 0.59 0.74 257.4 16.29 0.42 0.59 0.76 237.7 18.11 0.41 0.6 0.78 9600 284.9 14.72 0.44 0.63 0.81 264.8 16.36 0.44 0.64 0.83 245.5 18.19 0.43 0.65 0.86 Total Cool Cap. kBtuh 178.9 190.5 202.9 192.7 201.9 208.7 208.2 217.1 224.5 115°F Comp. Sensible To Total Motor Ratio (S/T) Input Dry Bulb kW 75°F 80°F 85°F 19.73 0.77 0.96 1 19.86 0.85 1 1 20 0.93 1 1 19.89 0.56 0.74 0.92 19.99 0.61 0.83 1 20.07 0.66 0.91 1 20.06 0.38 0.55 0.72 20.16 0.4 0.61 0.81 20.24 0.43 0.66 0.89 20 TON - HEATING LHT240H4M Indoor Coil Air Volume 70°F Dry Bulb cfm 6400 8000 9600 65°F Total Comp. Heating Motor Capacity Input kBtuh kW 290.0 16.08 297.6 14.90 308.2 14.16 Air Temperature Entering Outdoor Coil 45°F 25°F 5°F Total Comp. Total Comp. Total Heating Motor Heating Motor Heating Capacity Input Capacity Input Capacity kBtuh kW kBtuh kW kBtuh 210.2 14.43 146.5 12.97 99.7 214.6 13.58 149.5 12.39 102.0 223.5 13.09 156.1 12.02 107.7 Comp. Motor Input kW 11.98 11.62 11.42 -15°F Total Comp. Heating Motor Capacity Input kBtuh kW 64.5 11.46 66.3 11.36 71.5 11.32 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 23 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 24 BLOWER DATA BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE FOR ALL UNITS ADD: 1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (electric heat, Economizer, etc.) 3 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) Then determine from blower table blower motor output and drive required. See page 25 for wet coil, option/accessory air resistance data, and factory installed drive kit specifications. See page 26 for minimum air volume required for use with optional electric heat. Air Volume cfm 0.20 RPM BHP TOTAL STATIC PRESSURE - Inches Water Gauge (Pa) 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2750 385 0.30 505 0.50 600 0.70 680 0.90 755 1.10 820 1.30 - - - - - - - - - - - - - - - - - - 3000 395 0.35 515 0.55 610 0.75 685 1.00 760 1.20 825 1.45 885 1.70 - - - - - - - - - - - - 3250 405 0.40 520 0.60 615 0.85 695 1.10 765 1.30 830 1.60 890 1.85 950 2.10 - - - - - - 3500 415 0.45 530 0.70 620 0.95 700 1.20 775 1.45 840 1.70 900 2.00 955 2.25 1005 2.55 3750 425 0.50 540 0.75 630 1.05 710 1.30 780 1.60 845 1.85 905 2.15 960 2.45 1010 2.70 4000 435 0.55 545 0.85 635 1.10 715 1.40 785 1.70 850 2.00 910 2.30 965 2.60 1020 2.90 4250 445 0.60 555 0.90 645 1.25 725 1.55 795 1.85 855 2.15 915 2.45 970 2.80 1025 3.10 4500 4750 5000 5250 5500 5750 6000 6250 6500 455 0.70 565 1.00 655 1.35 730 1.65 800 2.00 865 2.35 925 2.65 980 3.00 1030 3.30 470 0.75 575 1.10 660 1.45 740 1.80 810 2.15 870 2.50 930 2.85 985 3.20 1040 3.55 480 0.85 585 1.25 670 1.60 750 1.95 815 2.30 880 2.70 940 3.05 995 3.40 1045 3.80 495 0.95 595 1.35 680 1.70 755 2.10 825 2.50 890 2.90 945 3.25 1000 3.65 1050 4.00 505 1.05 605 1.45 690 1.85 765 2.25 835 2.65 895 3.05 955 3.45 1010 3.85 1060 4.25 520 1.15 615 1.60 700 2.00 775 2.45 840 2.85 905 3.25 960 3.65 1015 4.10 1065 4.50 530 1.30 630 1.75 710 2.15 785 2.60 850 3.05 910 3.45 970 3.90 1025 4.35 1075 4.80 545 1.40 640 1.90 720 2.35 795 2.80 860 3.25 920 3.70 975 4.15 1030 4.60 1080 5.05 560 1.55 650 2.05 730 2.50 805 3.00 870 3.45 930 3.95 985 4.40 1040 4.85 1090 5.35 6750 570 1.70 665 2.20 745 2.70 815 3.20 880 3.70 940 4.20 995 4.65 1045 5.10 1095 5.60 7000 585 1.85 675 2.35 755 2.90 825 3.40 890 3.95 950 4.45 1005 4.95 1055 5.40 1105 5.95 7250 600 2.00 690 2.60 765 3.10 835 3.65 900 4.15 955 4.65 1015 5.25 1065 5.75 1115 6.25 7500 615 2.20 700 2.75 775 3.30 845 3.85 910 4.45 965 4.95 1020 5.50 1075 6.05 1125 6.60 7750 630 2.40 715 3.00 790 3.55 855 4.10 920 4.70 975 5.25 1030 5.80 1080 6.35 1130 6.90 8000 640 2.55 725 3.20 800 3.80 865 4.35 930 4.95 985 5.50 1040 6.10 1090 6.70 1140 7.25 8250 655 2.80 740 3.40 810 4.00 880 4.65 940 5.25 995 5.85 1050 6.45 1100 7.05 1150 7.65 8500 670 3.00 750 3.65 825 4.30 890 4.90 950 5.55 1005 6.15 1060 6.80 1110 7.40 1160 8.05 8750 9000 9250 9500 9750 10,000 10,250 10,500 10,750 685 3.25 765 3.90 835 4.55 900 5.20 960 5.85 1015 6.45 1070 7.15 1120 7.75 1165 8.35 700 3.50 780 4.20 850 4.85 910 5.50 970 6.15 1025 6.80 1080 7.50 1130 8.15 1175 8.75 715 3.75 790 4.45 860 5.15 925 5.85 985 6.55 1040 7.20 1090 7.85 1140 8.55 1185 9.20 730 4.00 805 4.75 875 5.45 935 6.15 995 6.90 1050 7.60 1100 8.25 1150 8.95 1195 9.60 745 4.30 820 5.05 885 5.75 950 6.55 1005 7.20 1060 7.95 1110 8.65 1160 9.40 1205 10.05 760 4.60 835 5.40 900 6.15 960 6.85 1015 7.60 1070 8.35 1120 9.05 1170 9.80 1215 10.50 775 4.90 845 5.65 910 6.45 970 7.20 1030 8.00 1080 8.75 1135 9.55 1180 10.25 1225 11.00 790 5.20 860 6.00 925 6.85 985 7.65 1040 8.40 1095 9.20 1145 10.00 1190 10.70 1235 11.45 805 5.55 875 6.40 940 7.25 1000 8.05 1055 8.85 1105 9.65 1155 10.45 1200 11.20 - - - - - - 11,000 820 5.90 890 6.80 950 7.60 1010 8.45 1065 9.30 1115 10.05 1165 10.90 - - - - - - - - - - - - 2.00 RPM BHP --- --- --- --- --- ----- --1060 3.00 1070 3.25 1075 3.45 1080 3.65 1085 3.90 1095 4.15 1100 4.40 1110 4.70 1115 4.95 1120 5.20 1130 5.50 1140 5.85 1145 6.10 1155 6.45 1160 6.75 1170 7.15 1180 7.50 1185 7.85 1195 8.25 1205 8.65 1215 9.05 1220 9.40 1230 9.85 1240 10.30 1250 10.80 1260 11.25 --- ----- ----- ----- --- 2.20 RPM BHP --- --- --- --- --- ----- --1110 3.30 1115 3.55 1120 3.75 1130 4.05 1135 4.25 1140 4.50 1150 4.80 1155 5.10 1160 5.35 1170 5.65 1175 5.95 1185 6.30 1190 6.60 1200 6.95 1205 7.30 1215 7.65 1225 8.05 1230 8.40 1240 8.85 1250 9.25 1255 9.65 1265 10.10 1275 10.55 1285 11.05 1295 11.50 --- ----- ----- ----- ----- --- 2.40 RPM BHP --- --- --- --- --- ----- ----- --1160 3.85 1165 4.10 1175 4.35 1180 4.65 1185 4.90 1195 5.20 1200 5.50 1205 5.80 1215 6.10 1220 6.45 1225 6.75 1235 7.10 1240 7.45 1250 7.85 1260 8.25 1265 8.60 1275 9.00 1280 9.40 1290 9.85 1300 10.30 1310 10.80 1315 11.20 --- ----- ----- ----- ----- ----- ----- --- 2.60 RPM BHP --- --- --- --- --- ----- ----- --1205 4.15 1210 4.45 1215 4.70 1225 5.00 1230 5.30 1235 5.60 1240 5.90 1250 6.25 1255 6.55 1265 6.90 1270 7.25 1275 7.60 1285 8.00 1290 8.35 1300 8.75 1305 9.15 1315 9.60 1325 10.05 1330 10.45 1340 10.90 1350 11.40 --- ----- ----- ----- ----- ----- ----- ----- --- BLOWER DATA FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS Nominal hp Maximum hp Drive Kit Number RPM Range 3 3.45 1 535 - 725 3 3.45 2 710 - 965 5 5.75 3 685 - 856 5 5.75 4 850 - 1045 5 5.75 5 945 - 1185 7.5 8.63 6 850 - 1045 7.5 8.63 7 945 - 1185 7.5 8.63 8 1045 - 1285 10 11.50 7 945 - 1185 10 11.50 10 1045 - 1285 10 11.50 11 1135 - 1365 NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. NOTE Motor service factor limit - 1.0. FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE Air Volume cfm Wet Indoor Coil in. w.g. Electric Heat in. w.g. Economizer in. w.g. MERV 8 Filters MERV 13 3250 .03 - - - - - - .01 .04 3500 .03 - - - - - - .01 .04 3750 .03 - - - - - - .01 .04 4000 .04 - - - - - - .01 .04 4250 .04 - - - - - - .01 .05 4500 .05 - - - - - - .01 .05 4750 .05 - - - - - - .02 .05 5000 .05 - - - - - - .02 .06 5250 .06 - - - - - - .02 .06 5500 .07 - - - - - - .02 .06 5750 .07 - - - - - - .02 .07 6000 .08 .01 - - - .03 .07 6250 .08 .01 .01 .03 .07 6500 .09 .01 .02 .03 .08 6750 .10 .01 .03 .03 .08 7000 .10 .01 .04 .04 .08 7250 .11 .01 .05 .04 .09 7500 .12 .01 .06 .04 .09 8000 .13 .02 .09 .05 .10 8500 .15 .02 .11 .05 .10 9000 .16 .04 .14 .06 .11 9500 .18 .05 .16 .07 .12 10,000 .20 .06 .19 .07 .12 10,500 .22 .09 .22 .08 .13 11,000 .24 .11 .25 .09 .14 MERV 16 0.07 0.08 0.08 0.09 0.10 0.10 0.11 0.12 0.12 0.13 0.14 0.14 0.15 0.16 0.17 0.17 0.18 0.19 0.21 0.22 0.24 0.25 0.27 0.29 0.30 Horizontal Roof Curb in. w.g. .04 .05 .05 .06 .07 .07 .08 .08 .09 .10 .11 .11 .12 .13 .14 .15 .16 .17 .19 .21 .24 .26 .29 .31 .34 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 25 BLOWER DATA MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT Electric Heat kW Minimum cfm 15 6000 30 6000 45 6000 60 6000 90 6000 POWER EXHAUST FAN PERFORMANCE Return Air System Static Air Volume Exhausted Pressure in. w.g. cfm 0.00 8630 0.05 8210 0.10 7725 0.15 7110 0.20 6470 0.25 5790 0.30 5060 0.35 4300 0.40 3510 0.45 2690 0.50 1840 CEILING DIFFUSER AIR RESISTANCE - in. w.g. Air Volume cfm Step-Down Diffuser RTD11-185S RTD11-275S 2 Ends Open 1 Side/2 Ends Open All Ends & Sides Open 2 Ends Open 1 Side/2 Ends Open All Ends & Sides Open 5000 .51 .44 .39 - - - - - - - - - 5200 .56 .48 .42 - - - - - - - - - 5400 .61 .52 .45 - - - - - - - - - 5600 .66 .56 .48 - - - - - - - - - 5800 .71 .59 .51 - - - - - - - - - 6000 .76 .63 .55 .36 .31 .27 6200 .80 .68 .59 - - - - - - - - - 6400 .86 .72 .63 - - - - - - - - - 6500 - - - - - - - - - .42 .36 .31 6600 .92 .77 .67 - - - - - - - - - 6800 .99 .83 .72 - - - - - - - - - 7000 1.03 .87 .76 .49 .41 .36 7200 1.09 .92 .80 - - - - - - - - - 7400 1.15 .97 .84 - - - - - - - - - 7500 - - - - - - - - - .51 .46 .41 7600 1.20 1.02 .88 - - - - - - - - - 8000 - - - - - - - - - .59 .49 .43 8500 - - - - - - - - - .69 .58 .50 9000 - - - - - - - - - .79 .67 .58 9500 - - - - - - - - - .89 .75 .65 10,000 - - - - - - - - - 1.00 .84 .73 10,500 - - - - - - - - - 1.10 .92 .80 11,000 - - - - - - - - - 1.21 1.01 .88 Flush Diffuser FD11-185S FD11-275S .27 - - - .30 - - - .33 - - - .36 - - - .39 - - - .42 .29 .46 - - - .50 - - - - - - .34 .54 - - - .58 - - - .62 .40 .66 - - - .70 - - - - - - .45 .74 - - - - - - .50 - - - .57 - - - .66 - - - .74 - - - .81 - - - .89 - - - .96 CEILING DIFFUSER AIR THROW DATA - ft. Model No. Air Volume cfm 1 Effective Throw Range - ft. RTD11-185S Step-Down FD11-185S Flush 5600 39 - 49 28 - 37 5800 42 - 51 29 - 38 156, 180 6000 6200 44 - 54 45 - 55 40 - 50 42 - 51 6400 46 - 55 43 - 52 6600 47 - 56 45 - 56 1 Throw is the horizontal or vertical distance an airstream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 26 Model No. 240 Air Volume cfm 7200 7400 7600 7800 8000 8200 8400 8600 8800 1 Effective Throw Range - ft. RTD11-275S Step-Down FD11-275S Flush 33 - 38 26 - 35 35 - 40 28 - 37 36 - 41 29 - 38 38 - 43 40 - 50 39 - 44 42 - 51 41 - 46 43 - 52 43 - 49 44 - 54 44 - 50 46 - 57 47 - 55 48 - 59 ELECTRICAL/ELECTRIC HEAT DATA Model No. 1 Voltage - 60Hz Compressor 1 (Non-Inverter) Rated Load Amps Locked Rotor Amps Compressor 2 (Non-Inverter) Rated Load Amps Locked Rotor Amps Outdoor Fan Motors (6) Full Load Amps (6 Non-ECM) Total Power Exhaust (2) 0.33 HP Full Load Amps Total Service Outlet 115V GFI (amps) Indoor Blower Motor Horsepower Full Load Amps 2 Maximum Overcurrent Protection (MOCP) Unit Only With (2) 0.33 HP Power Exhaust 3 Minimum Circuit Ampacity (MCA) Unit Only With (2) 0.33 HP Power Exhaust 208/230V - 3 Ph 17.6 136 22.4 149 2.4 LHT156H4 460V - 3 Ph 8.5 66.1 10.6 75 1.3 14.4 2.4 4.8 15 3 5 7.8 1.3 2.6 15 3 5 10.6 16.7 4.8 7.6 90 90 40 45 90 100 45 50 71 77 35 38 76 82 37 40 ELECTRIC HEAT DATA Electric Heat Voltage 208V 240V 208V 240V 2 Maximum Unit+ 15 kW 4 110 125 125 125 Overcurrent Electric Heat 30 kW 4 150 175 175 175 Protection (MOCP) 45 kW 4 200 225 4 200 225 60 kW 4 200 225 225 225 3 Minimum Circuit Ampacity (MCA) Unit+ 15 kW 110 116 116 122 Electric Heat 30 kW 149 161 155 167 45 kW 188 206 194 213 60 kW 196 215 202 222 2 Maximum Unit+ 15 kW 125 125 4 125 150 Overcurrent Electric Heat 30 kW 175 175 175 175 Protection (MOCP) and (2) 0.33 HP Power Exhaust 45 kW 4 200 225 4 200 225 60 kW 225 225 4 225 250 3 Minimum Unit+ 15 kW 115 121 121 127 Circuit Electric Heat 30 kW 154 166 160 172 Ampacity (MCA) and (2) 0.33 HP Power Exhaust 45 kW 193 211 199 217 60 kW 201 220 207 226 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available. 480V 60 80 110 110 57 80 103 107 60 90 110 110 60 83 105 110 480V 60 90 110 110 60 83 105 110 70 90 110 125 63 85 108 112 575V - 3 Ph 6.3 55.3 7.7 54 1 6 1 2 20 3 5 3.9 6.1 30 35 35 35 26 29 28 31 600V 45 70 80 90 44 62 80 84 50 70 90 90 46 64 82 86 600V 50 70 90 90 47 65 83 86 50 70 90 90 49 67 85 88 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 27 ELECTRICAL/ELECTRIC HEAT DATA 15 TON Model No. 1 Voltage - 60Hz Compressor 1 (Non-Inverter) Rated Load Amps Locked Rotor Amps Compressor 2 (Non-Inverter) Rated Load Amps Locked Rotor Amps Outdoor Fan Motors (6) Full Load Amps (6 Non-ECM) Total Power Exhaust (2) 0.33 HP Full Load Amps Total Service Outlet 115V GFI (amps) Indoor Blower Motor Horsepower Full Load Amps 2 Maximum Overcurrent Protection (MOCP) Unit Only With (2) 0.33 HP Power Exhaust 3 Minimum Circuit Ampacity (MCA) Unit Only With (2) 0.33 HP Power Exhaust 208/230V - 3 Ph 25.3 184 25 164 2.4 LHT180H4 460V - 3 Ph 9.6 84 12.2 100 1.3 14.4 7.8 2.4 1.3 4.8 2.6 15 15 3 5 7.5 3 5 7.5 10.6 16.7 24.2 4.8 7.6 11 100 110 110 45 50 50 110 110 125 50 50 50 575V - 3 Ph 8.4 60 9 78 1 6 1 2 20 3 5 7.5 3.9 6.1 9 35 40 40 40 40 45 82 88 96 38 41 44 30 32 35 87 93 101 41 43 47 32 34 37 ELECTRIC HEAT DATA Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480 600V 600V 600V 2 Maximum Overcurrent Protection (MOCP) Unit+ 15 kW 4 125 150 150 150 150 150 70 70 70 50 50 60 Electric Heat 30 kW 175 175 4 175 200 4 175 200 90 90 90 70 70 80 45 kW 4 200 225 225 225 4 225 250 110 110 125 90 90 90 60 kW 4 225 250 4 225 250 4 225 250 110 125 125 90 90 100 3 Minimum Circuit Ampacity (MCA) Unit+ 15 kW 121 127 127 133 135 141 61 63 67 48 50 53 Electric Heat 30 kW 160 172 166 178 174 186 83 86 89 66 68 71 45 kW 199 217 205 224 213 231 106 108 112 84 86 89 60 kW 207 226 213 233 221 240 110 113 116 88 90 93 2 Maximum Overcurrent Protection (MOCP) Unit+ Electric Heat and (2) 0.33 HP Power Exhaust 15 kW 150 150 150 150 150 150 70 70 70 50 60 60 30 kW 4 175 200 4 175 200 200 200 90 90 100 70 70 80 45 kW 225 225 4 225 250 4 225 250 110 125 125 90 90 100 60 kW 4 225 250 4 225 250 250 250 125 125 125 90 100 100 3 Minimum Circuit Ampacity (MCA) Unit+ 15 kW 126 132 132 138 140 146 63 66 69 50 52 55 Electric Heat 30 kW 165 177 171 183 179 191 86 88 92 68 70 73 and (2) 0.33 HP Power Exhaust 45 kW 204 222 210 228 218 236 108 111 114 86 88 91 60 kW 212 231 218 237 226 245 113 116 119 90 92 95 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 28 ELECTRICAL/ELECTRIC HEAT DATA 20 TON Model No. 1 Voltage - 60Hz Compressor 1 (Non-Inverter) Rated Load Amps Locked Rotor Amps Compressor 2 (Non-Inverter) Rated Load Amps Locked Rotor Amps Outdoor Fan Motors (6) Full Load Amps (6 Non-ECM) Total Power Exhaust (2) 0.33 HP Full Load Amps Total Service Outlet 115V GFI (amps) Indoor Blower Motor Horsepower Full Load Amps 2 Maximum Overcurrent Protection (MOCP) Unit Only With (2) 0.33 HP Power Exhaust 3 Minimum Circuit Ampacity (MCA) Unit Only With (2) 0.33 HP Power Exhaust LHT240H4 208/230V - 3 Ph 460V - 3 Ph 32.6 14.8 240 130 31.1 13 255 123 2.4 1.3 14.4 7.8 2.4 1.3 4.8 2.6 15 15 5 7.5 10 5 7.5 10 16.7 24.2 30.8 7.6 11 14 125 125 125 60 60 60 125 125 150 60 60 70 575V - 3 Ph 11.1 93.7 11 93.7 1 6 1 2 20 5 7.5 10 6.1 9 11 45 50 50 50 50 50 103 111 118 47 51 54 37 40 42 108 116 122 50 53 56 39 42 44 ELECTRIC HEAT DATA Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 2 Maximum Overcurrent Protection (MOCP) Unit+ Electric Heat 15 kW 150 150 4 150 175 175 175 70 80 80 60 60 60 30 kW 200 200 4 200 225 4 200 225 100 100 100 80 80 80 45 kW 4 225 250 250 250 4 250 4 300 125 125 125 100 100 100 60 kW 250 250 4 250 4 300 4 250 4 300 125 125 150 100 100 110 90 kW 4 300 4 350 4 300 4 350 350 4 350 175 175 175 125 150 150 3 Minimum Circuit Ampacity (MCA) Unit+ 15 kW 143 149 150 156 157 163 70 73 76 56 58 60 Electric Heat 30 kW 182 194 189 201 196 208 93 96 99 74 76 78 45 kW 221 239 228 246 235 253 115 118 121 92 95 97 60 kW 229 248 236 255 243 262 120 123 126 95 98 100 90 kW 291 320 299 327 305 334 156 159 162 124 127 129 2 Maximum Overcurrent Protection (MOCP) Unit+ Electric Heat and (2) 0.33 HP Power Exhaust 15 kW 4 150 175 175 175 175 175 80 80 80 60 60 70 30 kW 200 200 4 200 225 225 225 100 100 110 80 80 80 45 kW 250 250 4 250 4 300 4 250 4 300 125 125 125 100 100 100 60 kW 4 250 4 300 4 250 4 300 4 250 4 300 125 150 150 100 110 110 90 kW 4 300 4 350 350 4 350 350 4 350 175 175 175 150 150 150 3 Minimum Circuit Ampacity (MCA) Unit+ Electric Heat and (2) 0.33 HP Power Exhaust 15 kW 147 153 155 161 161 167 73 76 79 58 60 62 30 kW 186 198 194 206 201 213 95 99 102 76 78 80 45 kW 226 244 233 251 240 258 118 121 124 94 97 99 60 kW 233 253 241 260 247 267 122 126 129 97 100 102 90 kW 296 325 303 332 310 339 158 162 165 126 129 131 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 29 ELECTRICAL ACCESSORIES - DISCONNECTS 13 TON | LHT156H4 Motor Horsepower 3 5 3 5 3 5 Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V Unit Only 54W85 54W85 54W86 54W86 54W85 54W85 54W85 54W85 + Power Exhaust 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 + Electric Heat 15 kW 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 30 kW 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 + Electric Heat 45 kW 54W87 54W86 54W87 54W86 54W85 54W85 54W85 54W85 + Electric Heat 60 kW 54W87 54W87 54W87 54W87 54W86 54W86 54W85 54W85 + Power Exhaust + Elec. Heat 15 kW 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 30 kW 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 45 kW 54W87 54W86 54W87 54W86 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 60 kW 54W87 54W87 54W87 54W87 54W86 54W86 54W85 54W85 15 TON | LHT180H4 Motor Horsepower 3 5 7.5 3 5 7.5 3 5 7.5 Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V Unit Only 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 15 kW 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 30 kW 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 45 kW 54W87 54W86 54W87 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 60 kW 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 15 kW 54W85 54W85 54W85 54W85 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 30 kW 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 45 kW 54W87 54W86 54W87 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 60 kW 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 20 TON | LHT240H4 Motor Horsepower 5 7.5 10 5 7.5 10 5 7.5 10 Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V Unit Only 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 15 kW 54W85 54W85 54W85 54W85 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 30 kW 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 45 kW 54W87 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 + Electric Heat 60 kW 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 + Electric Heat 90 kW ¹ NA ¹ NA ¹ NA ¹ NA ¹ NA ¹ NA 54W86 54W86 54W86 54W86 54W86 54W86 + Power Exhaust + Elec. Heat 15 kW 54W85 54W85 54W86 54W85 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 30 kW 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 45 kW 54W87 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W86 54W85 54W85 54W85 + Power Exhaust + Elec. Heat 60 kW 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W86 + Power Exhaust + Elec. Heat 90 kW ¹ NA ¹ NA Disconnects - 5 4W85 - 80A 54W86 - 150A 54W87 - 250A 1 Disconnect must be field furnished. EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 30 ¹ NA ¹ NA ¹ NA ¹ NA 54W86 54W86 54W86 54W86 54W86 54W86 ELECTRIC HEAT CAPACITIES 15 kW 30 kW 45 kW 60 kW 90 kW Volts Input kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages 208 11.3 38,600 1 22.5 76,800 1 33.8 115,300 2 45.0 153,600 2 67.6 230,700 2 220 12.6 43,000 1 25.2 86,000 1 37.8 129,000 2 50.4 172,000 2 75.6 258,000 2 230 13.8 47,100 1 27.5 93,900 1 41.3 141,000 2 55.1 188,000 2 82.7 282,200 2 240 15.0 51,200 1 30.0 102,400 1 45.0 153,600 2 60.0 204,800 2 90.0 307,100 2 440 12.6 43,000 1 25.2 86,000 1 37.8 129,000 2 50.4 172,000 2 75.6 258,000 2 460 13.8 47,100 1 27.5 93,900 1 41.3 141,000 2 55.1 188,000 2 82.7 282,200 2 480 15.0 51,200 1 30.0 102,400 1 45.0 153,600 2 60.0 204,800 2 90.0 307,100 2 550 12.6 43,000 1 25.2 86,000 1 37.8 129,000 2 50.4 172,000 2 75.6 258,000 2 575 13.8 47,100 1 27.5 93,900 1 41.3 141,000 2 55.1 188,000 2 82.7 282,200 2 600 15.0 51,200 1 30.0 102,400 1 45.0 153,600 2 60.0 204,800 2 90.0 307,100 2 FIELD WIRING NOTES · For use with copper wiring only · Field wiring not furnished · All wiring must conform to NEC or CEC and local electrical codes · For specific wiring information, please refer to the installation instructions EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 31 UNIT CLEARANCES Unit With Economizer C OUTDOOR AIR HOOD D B Note: 210-240-300 sizes shown A 1 Unit Clearance A B in. mm in. mm in. Service Clearance 60 1524 36 914 36 Minimum Operation Clearance 45 1143 36 914 36 NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface. 1 S ervice Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation. C mm 934 914 D in. mm 66 1676 41 1041 Top Clearance Unobstructed OUTDOOR SOUND DATA Unit Model Number Octave Band Sound Power Levels dBA, re 10-12 Watts - Center Frequency - Hz 125 250 500 1000 2000 4000 8000 156, 180, 240 79 84 88 89 85 82 73 Note - The octave sound power data does not include tonal corrections. 1 Sound Rating Number according to AHRI Standard 370-2001 (includes pure tone penalty). Sound Rating Number is the overall A-Weighted Sound Power Level (LwA), dBA (100 Hz to 10,000 Hz). 1 Sound Rating Number (dBA) 94 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 32 WEIGHT DATA UNIT Model Number Net lbs. kg Shipping lbs. kg 156 Base Unit 2198 997 2398 1088 156 Max. Unit 2488 1129 2688 1219 180 Base Unit 2226 1010 2426 1100 180 Max. Unit 2516 1141 2716 1232 240 Base Unit 2268 1029 2468 1119 240 Max. Unit 2558 1160 2758 1251 NOTE - Max. Unit is the unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories EXTERNAL to unit. WEIGHT DATA ECONOMIZER / OUTDOOR AIR / EXHAUST Economizer Economizer Dampers (with Outdoor Air Hood) Barometric Relief Dampers (downflow) Barometric Relief Dampers (horizontal) Outdoor Air Dampers with Hood (downflow) Motorized Manual Power Exhaust ELECTRIC HEAT 15 kW 30 kW 45 kW 60 kW 90 kW COIL/HAIL GUARDS All models ROOF CURBS Hybrid Roof Curbs, Downflow 8 in. height 14 in. height 18 in. height 24 in. height Adjustable Pitch Curb, Downflow 14 in. height Horizontal, Standard 26 in. height 37 in. height CEILING DIFFUSERS Step-Down Flush Transitions RTD11-185S RTD11-275S FD11-185S FD11-275S C1DIFF33C-1 C1DIFF34C-1 OPTIONS / ACCESSORIES Shipping Weight lbs. kg 167 76 30 14 20 9 39 18 22 10 62 28 59 27 59 27 76 34 76 34 84 38 36 16 136 62 169 77 191 87 224 102 224 102 168 76 238 108 168 76 238 108 80 36 75 34 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 33 DIMENSIONS CORNER WEIGHTS CENTER OF GRAVITY Model No. AA BB CC DD EE FF lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm LHT156 Base Unit 411 187 485 220 705 321 598 272 58-3/8 1481 37-1/8 943 LHT156 Max. Unit 509 231 575 261 745 338 659 300 57-1/8 1452 39-3/4 1010 LHT180 Base Unit 412 187 486 221 719 327 610 277 58-3/8 1482 36-3/4 934 LHT180 Max. Unit 511 232 577 262 758 345 671 305 57-1/8 1452 39-3/8 1000 LHT240 Base Unit 415 189 488 222 738 336 628 285 58-1/4 1479 36-1/4 921 LHT240 Max. Unit 513 233 578 263 777 353 690 314 57 1450 38-7/8 987 Base Unit - The unit with NO INTERNAL OPTIONS. Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit. AA BB 4-1/4 (108) 28-3/8 (721) 12-3/8 (314) 15 (381) 60-1/2 (1537) BOTTOM RETURN AIR OPENING ALTERNATE (THRU THE BASE) BOTTOM SUPPLY 18 (457) AIR OPENINGS CONDENSATE DRAIN LOCATION 1-5/8 in. (41 mm) Diameter 5-5/8 (143) 12-3/8 (314) 4-1/2 (114) 28 (711) 28 (711) 20 (508) 20 (508) EE CENTER OF GRAVITY FF 4 (102) DD CC 4 (102) BOTTOM POWER ENTRY 5 X 8 inches (127 X 203 mm) TOP VIEW 90-1/8 (2289) OPTIONAL DISCONNECT (Factory Installed) 132-5/8 OPTIONAL (3369) 115 VOLT OUTLET (Factory Installed Inside Unit) CONDENSATE DRAIN 5-3/8 (137) 54-1/4 (1378) 51 (1295) 28-3/4 (730) SIDE ELECTRICAL INLETS 91-1/8 (2315) BASE END VIEW 3-1/4 (83) LIFTING HOLES (For Rigging Front and Back) FORKLIFT SLOTS (Front and Left Side Only) 107-3/4 (2737) BASE SIDE VIEW 25-3/8 (645) EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 34 DIMENSIONS OUTDOOR AIR HOOD (Furnished with Economizer or Outdoor Air Damper) OUTDOOR AIR HOOD DETAIL 16 (406) EXHAUST AIR HOOD (Furnished with Optional Downflow Barometric Relief Dampers, Field Installed) ACCESSORIES OPTIONAL HORIZONTAL BAROMETRIC RELIEF DAMPERS WITH HOOD (Field installed in horizontal return air duct adjacent to unit) 31-5/8 (803) 1 29-1/2 (749) 6-1/2 (165) 14-1/2 (368) 1 13 (330) FRONT VIEW NOTE - Two furnished per order no. 1 NOTE - Opening size required in return air duct. SIDE VIEW EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 35 DIMENSIONS HYBRID ROOF CURBS - DOUBLE DUCT OPENING ACCESSORIES 86-1/8 (2188) 82-5/8 21 (2099) (533) 17 (432) 16 (406) 8-1/4 (210) 61-1/2 (1562) RETURN OPENING 102 (2591) 61-1/2 (1562) SUPPLY OPENING 81-1/2 (2070) 98-1/2 (2502) 8 (203) 14 (356) 18 (457) 24 (610) NOTE - Roof deck may be omitted within confines of curb. TYPICAL FLASHING DETAIL FOR ROOF CURB BASE BOTTOM PACKAGED UNIT FIBERGLASS INSULATION (Furnished) NAILER STRIP (Furnished) ROOF CURB (Extends around entire perimeter of unit) RIGID INSULATION (Field Supplied) COUNTER FLASHING (Field Supplied) CANT STRIP (Field Supplied) ROOFING MATERIAL DETAIL ROOF CURB 1-3/4 (44) 1/2 (13) 8 (203) 14 (356) 18 (457) 24 (610) FACTORY INSTALLED PERIMETER WOOD NAILER STRIP 1-3/4 (44) EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 36 DIMENSIONS ACCESSORIES ADJUSTABLE PITCH CURB - DOUBLE DUCT OPENING 82-5/8 (2099) 86-1/8 (2188) 21 (533) 17 (432) 16 (406) 1-3/4 (44) 8-1/4 (210) 61-1/2 (1562) SUPPLY OPENING 8-1/4 (210) 102-1/8 (2594) 61-1/2 (1562) RETURN OPENING 98-1/2 (2502) 14 (356) FACTORY INSTALLED PERIMETER WOOD NAILER STRIP BOTTOM CURB ASSEMBLY NOTE - Maximum slope pitch is 3/4 in. per 1 foot (19 mm per 305 mm) in any one direction. TYPICAL FLASHING DETAIL FOR ROOF CURB BASE BOTTOM PACKAGED UNIT FIBERGLASS INSULATION (Furnished) NAILER STRIP (Furnished) ROOF CURB (Extends around entire perimeter of unit) RIGID INSULATION (Field Supplied) COUNTER FLASHING (Field Supplied) CANT STRIP (Field Supplied) ROOFING MATERIAL DETAIL ROOF CURB 1-3/4 (44) 1/2 (13) 14 (356) FACTORY INSTALLED PERIMETER WOOD NAILER STRIP 1-3/4 (44) EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 37 DIMENSIONS ACCESSORIES ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS 69-1/4 (1759) RETURN TRANSITION RETURN AIR OPENING A B 4-1/2 (114) B SUPPLY AIR A OPENINGS SUPPLY TRANSITION SUPPORT ANGLE (Furnished with Transitions) 54 (1372) 3/4 (19) Typ. 26-1/2 (673) 8 (203) TRANSITION DETAIL 69-1/4 (1759) 2 A (51) B 1-1/2 (38) Typ. TOP VIEW TRANSITION OPENING SIZES Model Number A inch mm B inch mm C1DIFF33C-1 18 457 36 914 C1DIFF34C-1 24 610 48 1219 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 38 DIMENSIONS ACCESSORIES HORIZONTAL ROOF CURBS - Requires Optional Horizontal Return Air Panel Kit Frame Opening 1-13/16 (46) 1-13/16 (46) 82-5/8 (2099) 86-1/4 (2191) 102-1/8 (2594) 98-1/2 (2502) Frame Opening 1-13/16 (46) 1 26 (660) 2 37 (940) 1 (25) 2 (51) SECTION A-A 98-1/2 (2502) 1-13/16 (46) NOTE - 26 in. (660 mm) height Curb is designed for horizontal discharge when unit is mounted on a slab. 37 in. (940 mm) height Curb is designed for A A horizontal discharge when unit is mounted on a rooftop. PANEL TO COVER RETURN AIR OPENING IN BOTTOM OF UNIT (Furnished With Optional Horizontal Return Air Panel Kit) 54 (1372) SUPPLY AIR TURNING VANE (Furnished) NOTE - Roof deck may be omitted within confines of curb. SIDE VIEW (Packaged Unit) 1-13/16 (46) 1 26 (660) 2 37 (940) TOP VIEW 102-1/8 (2594) 75 CURB SUPPLY (1905) AIR OPENING WITH 1-1/2 IN. (38 MM) FLANGE 102-1/2 (2604) FRONT VIEW 1,2 8-1/4 (210) 86-1/4 (2191) 5-1/2 (140) 14 (356) 1 6-1/2 (165) 2 17-1/2 (445) 1 Slab Applications SUPPLY AIR TURNING VANE (Furnished) 86-5/8 (2200) SIDE VIEW 2 Rooftop Applications SUPPLY DUCT PANELS (Furnished) HORIZONTAL SUPPLY AND RETURN AIR OPENINGS WITH HORIZONTAL ROOF CURB OPTIONAL RETURN AIR PANEL KIT (Required for Horizontal Applications) 54-1/4 (1378) ¹ 76-1/4 (1937) ² 87-1/4 (2216) 60-1/2 (1537) 15 (381) HORIZONTAL RETURN AIR OPENING 2 (51) 12-3/8 (314) ¹ 26 (660) 2 37 (940) 30-3/8 (772) 75 (1905) HORIZONTAL SUPPLY AIR OPENING NOTE - Top of Roof Curb extends 4 inch (102 mm) inside bottom of unit base. See Typical flashing detail. HORIZONTAL ROOF CURB (Required For Horizontal Applications) 1 Slab Applications 2 Rooftop Applications 14 (356) 8-1/4 (210) 1 6-1/2 (165) 2 17-1/2 (445 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 39 DIMENSIONS COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS STEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER E F G G H 2 (51) N B M J D K C A L E F G G H 2 (51) B ACCESSORIES J D K C A Model Number A in. mm B in. mm C in. mm D in. mm E in. mm F in. mm G in. mm H in. mm J in. mm K in. mm L in. mm M in. mm N in. mm Duct Size in. mm RTD11-185S 47-5/8 1210 47-5/8 1210 24-5/8 625 45-1/2 1156 45-1/2 1156 4-1/2 114 18 457 2-1/2 64 36 914 4-3/4 121 45-1/2 1156 45-1/2 1156 10-1/8 257 18 x 36 457 x 914 RTD11-275S 59-5/8 1514 59-5/8 1514 30-5/8 778 57-1/2 1461 57-1/2 1461 4-1/2 114 24 610 2-1/2 64 48 1219 4-3/4 121 57-1/2 1461 57-1/2 1461 11-1/8 283 24 x 48 610 x 1219 Model Number A in. mm B in. mm C in. mm D in. mm E in. mm F in. mm G in. mm H in. mm J in. mm K in. mm Duct Size in. mm FD11-185S 47-5/8 1210 47-5/8 1210 29-1/4 743 45 1143 45 1143 4-1/2 114 18 457 2-1/4 57 36 914 4-1/2 114 18 x 36 457 x 914 FD11-275S 59-5/8 1514 59-5/8 1514 35-1/4 895 57 1148 57 1448 4-1/2 114 24 610 2-1/4 57 48 1219 4-1/2 114 24 x 48 610 x 1219 EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 40 REVISIONS Sections Weight Data Description of Change Updated Roof Curb weights. Visit us at www.Lennox.com For the latest technical information, www.LennoxCommercial.com Contact us at 1-800-4-LENNOX NOTE - Due to Lennox' ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2023 Lennox Industries, Inc.