COMMERCIAL PRODUCT SPECIFICATIONS

PACKAGED HEAT PUMP
LHT
EnlightTM Rooftop Units High Efficiency - 60 Hz
Bulletin No. 210986 August 2023
Supersedes May 2023

ASHRAE 90.1 COMPLIANT

13 to 20 Tons Net Cooling Capacity - 150,000 to 224,000 Btuh Net Heating Capacity - 144,000 to 224,000 Btuh
Optional Electric Heat - 15 to 90 kW

MODEL NUMBER IDENTIFICATION

Brand/Family L = EnlightTM

L H T 240 H 4 M N 1 Y

Voltage Y = 208/230V-3 phase-60Hz G = 460V-3 phase-60Hz J = 575V-3 phase-60Hz

Unit Type H= Heat Pump Unit

Minor Design Sequence 1 = 1st Revision

Major Design Sequence T = 1st Generation
Nominal Cooling Capacity - Tons 156 = 13 Tons 180= 15 Tons 240 = 20 Tons

Factory Installed Electric Heat N = No Heat E = 15 kW Electric Heat J = 30 kW Electric Heat K = 45 kW Electric Heat L = 60 kW Electric Heat P = 90 kW Electric Heat
Blower Type M = MSAV® Multi-Stage Air Volume, Belt Drive

Cooling Efficiency H = High Efficiency

Refrigerant Type 4 = R-410A

FEATURE HIGHLIGHTS
EnlightTM rooftop units featuring the Lennox® CORE Control System create a bright future through a highly energy-efficient and environmentally sustainable design. Comprehensive configurations meet a wide range of applications, making it the most flexible product line Lennox has to offer.

1. Scroll Compressors 2. Check/Thermal Expansion Valves 3. Filter/Driers 4. Reversing Valves 5. Copper Tube Outdoor Coil 6. Outdoor Coil Fan Motors 7. Heavy Gauge Steel Cabinet 8. Hinged Access Panels 9. MSAV® Multi-Stage Air Volume
Blower 10. Disconnect Switch (option) 11. Electric Heat (option) 12. Air Filters 13. Lennox CORE®Control System 14. Economizer (option) 15. Barometric Relief Dampers (option) 16. Power Exhaust (option)

H

CQ

OM P
J

N 8.8.8.8

B L
K

D
E I

G F

CONTENTS
Approvals And Warranty .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3 Blower Data .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  24 Control System .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  7 Cooling/Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Electrical Accessories - Disconnects .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  30 Electrical/Electric Heat Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 27 Electric Heat Capacities .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  31 Features And Benefits .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3 Model Number Identification .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1 Optional Conventional Temperature Control Systems  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  11 Options / Accessories .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  16 Outdoor Sound Data  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  32 Sequence Of Operation  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 13 Specifications .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  20 Unit Clearances .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  32 Weight Data .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  33
- Accessories .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  35 - Options / Accessories .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 33 - Unit .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  33

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 2

APPROVALS AND WARRANTY

APPROVALS · AHRI Standard 340/360 certified · ETL and CSA listed · CSA certified energy ratings · Unit and components ETL, NEC and CEC bonded for grounding to meet safety standards for servicing · All models are ASHRAE 90.1 energy efficiency compliant and meet or exceed requirements of Section 6.8 · All models meet DOE 2023 energy efficiency standards · All models meet California Code of Regulations, Title 24 and ASHRAE 90.1 Section 6.4.3.10 requirements for staged
airflow · All units are ENERGY STAR® certified · ISO 9001 Registered Manufacturing Quality System
WARRANTY · Compressors - Limited five years · Lennox CORE® Unit Controller - Limited three years · Variable Frequency Drive (VFD) - Limited five years · High Performance Economizers (optional) - Limited five years · All other covered components - Limited one year

FEATURES AND BENEFITS

COOLING/HEATING SYSTEM

High Pressure Switches

· Designed to maximize sensible and latent cooling performance at design conditions
· Mechanical cooling operates from 0°F to 125°F

· Protects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation

· Mechanical heating operates at ambient temperatures above -15°F
NOTE - Optional Electric Heat operates at ambient

Low Pressure Switches
· Protects the compressors from low pressure conditions such as low refrigerant charge, or low/no airflow

temperatures below -4°F and operates in conjunction with mechanical heating down to -15°F.

Indoor Coil Freeze Protection
· Protects the indoor coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant

R-410A Refrigerant · Non-chlorine based

charge
F Coil Construction

· Ozone friendly

· Copper tube construction

B Compressor System
· Scroll compressor on all models for high performance,

· Enhanced rippled-edge aluminum fins · Flared shoulder tubing connections

reliability, and quiet operation

· Silver soldered construction

· Resiliently mounted on rubber grommets for quiet operation
Compressor Crankcase Heaters · Protects against refrigerant migration that can occur
during low ambient operation

· Factory leak tested
Indoor Coil · Cross-row circuiting · Rifled copper tubing

C Check/Thermal Expansion Valves
· Ensures optimal performance throughout the application

Outdoor Coil · Two independent slanted coils for easy cleaning

range

Antimicrobial Condensate Drain Pan

· Removable element head
D Filter/Driers
· High capacity filter/drier protects the system from dirt and moisture
E Reversing Valve
· 4-way interchange reversing valve rapidly changes

· Composite pan, sloped to meet drainage requirements per ASHRAE 62.1
· Anti-Microbial additive prevents growth of mold and mildew, which improves indoor air quality and reduces drain line blockage
· Side or bottom drain connections

the direction of refrigerant flow resulting in quick

changeover from cooling to heating and vice versa

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 3

FEATURES AND BENEFITS
COOLING / HEATING SYSTEM (continued)
G Outdoor Coil Fan Motors
· All models have PSC motors · Thermal overload protected · Totally enclosed · Permanently lubricated ball bearings · Shaft up · Wire basket mount
Outdoor Coil Fan · PVC coated fan guards furnished
Required Selections
Cooling Capacity · Specify nominal cooling capacity
Options/Accessories
Field Installed Condensate Drain Trap · Available in copper or PVC
Factory or Field Installed Drain Pan Overflow Switch · Monitors condensate level in drain pan · Shuts down unit if drain becomes clogged
CABINET
H Construction
· Heavy-gauge steel panels · Full perimeter heavy-gauge galvanized steel base rail · Base rails have rigging holes · Three sides of the base rail have fork slots · Raised edges around duct and power entry openings in
the bottom of the unit for water protection
Airflow Choice · Units are shipped in downflow (vertical) configuration NOTE - Units can be field converted to horizontal air flow
with optional Horizontal Return Air Panel Kit and Horizontal Roof Curb.
Power Entry · Electrical lines can be routed through the unit base or
through horizontal access knock-outs
Exterior Panels · Constructed of heavy-gauge, galvanized steel · Textured pre-paint with polyurethane finish · Cyclic salt fog and UV exposure up to 1,680 hours per
ASTM D5894

Insulation · Fully insulated with non-hygroscopic fiberglass
insulation (conditioned areas) · Unit base is fully insulated · Base insulation serves as an air seal to the roof curb,
eliminating the need to add a seal during installation
I Hinged Access Panels
· Filter section · Heating/blower section · Compressor/controls section · Panel seals and quarter-turn latching handles provide a
tight air and water seal
Required Selections
Airflow Configuration · Specify downflow or horizontal
Options/Accessories
Factory Installed
Corrosion Protection · Completely flexible immersed coating · Electrodeposited dry film process
(AST ElectroFin E-Coat) · ASTM B117 / DIN 53167 Salt Spray - 15,000+ hours · ASTM G85 Annex A3 SWAAT Modified Salt Spray - 3,000
hours · VA Master Construction Specification Division 23 for
High Humidity Installations · CID AA-52474A (GSA) · Indoor Corrosion Protection:
· Coated coil · Painted blower housing · Painted base · Outdoor Corrosion Protection: · Coated coil · Painted outdoor base
Factory or Field Installed Combination Coil/Hail Guards · Heavy gauge steel frame · Painted to match cabinet · Expanded metal mesh protects outdoor coil
Field Installed Horizontal Return Air Panel Kit · Required for horizontal applications with Horizontal Roof
Curb · Contains panel with return air opening for field
replacement of existing unit panel and panel to cover bottom return air opening in unit · See dimension drawings

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 4

FEATURES AND BENEFITS
BLOWER
A wide selection of supply air blower options are available to meet a variety of airflow requirements.
Motor · Overload protected
· Ball bearings
NOTE - All blower motors 5 hp and above meet minimum energy efficiency standards in accordance with the Energy Independence and Security Act (EISA). of 2007
J Supply Air Blower
· Forward curved blades
· Double inlet
· Blower wheel is statically and dynamically balanced
· Ball bearings
· Adjustable pulley (allows speed change)
· Blower assembly slides out of unit for servicing
· Grease fittings furnished
· MSAV® Multi-Stage Air Volume stages the amount of airflow according to compressor stages, heating demand, ventilation demand or smoke alarm
· MSAV® Multi-Stage Air Volume utilizes a Variable Frequency Drive (VFD) to stage the supply blower airflow
· VFD alters the frequency and voltage of the power supply to the blower to control blower speed
· The amount of airflow for each stage can be set according to a parameter in the Lennox® CORE Unit Controller
· Unit is shipped from the factory with preset airflow
· LHT180H models with MSAV® Multi-Stage Air Volume can be ordered with or without an Electronic Bypass Control
· If equipped with the bypass control the MSAV® MultiStage Air Volume features manual (default) or automatic electronic bypass control of the VFD
· In case of a VFD malfunction, a VFD alarm is generated by the Lennox® CORE Unit controller
· VFD can be manually bypassed to continue unit operation at full blower speed or the unit controller can be set to automatically switch to full blower speed if a VFD alarm is generated
· VFD has an operational range of ­40 to 125°F outdoor air ambient temperature
· Lower operating costs are obtained when the blower is operated on lower speeds

Required Selections
NOTE - Units equipped a Variable Frequency Drive (VFD) are designed to operate on balanced, three-phase power. Operating units on unbalanced three-phase power will reduce the reliability of all electrical components in the unit. Unbalanced power is a result of the power delivery system supplied by the local utility company. Factory-installed inverters are sized to drive blower motors with an equivalent current rating using balanced threephase power. If unbalanced three-phase power is supplied, the installer must replace the existing factory-installed inverter with an inverter that has a higher current rating to allow for the imbalance. Refer to the installation instructions for additional information and replacement information.
Ordering Information · Specify motor horsepower and drive kit number when
base unit is ordered
Options/Accessories
Field Installed
Blower Belt Auto-Tensioner · Provides proper tension to belt drive blower belt without
the need for regular adjustments
· Maintains airflow and proper performance
ELECTRICAL
NOTE - All units include terminal block and fuse block in power entry junction box for single power entry application.
SmartWireTM System · Keyed and color-coded wiring connectors prevent
miswiring
· Wire coloring scheme is standardized across all models
· Each connection is intuitively labeled to make troubleshooting and servicing quick and easy
Electrical Plugs · Positive connection electrical plugs connect common
accessories or maintenance parts for easy removal or installation
Phase/Voltage Detection · Monitors power supply to ensure correct phase at unit
start-up
· If phase is incorrect, the unit will not start and an alarm code reports to the unit controller
· Prevents unit start-up if the unit is the incorrect phase; unit start-ups in the wrong phase could lead to issues such as compressors functioning in reverse
· Monitors power supply voltage to ensure proper voltage
· If voltage is not correct (over/under voltage conditions) the unit will not start and an alarm code reports to the unit controller

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 5

FEATURES AND BENEFITS
ELECTRICAL(continued)
Required Selections
Voltage Choice · Specify when ordering base unit
Options/Accessories
Factory Installed
Circuit Breakers · HACR type · Overload and short circuit protection · Factory wired and mounted in the power entry panel · Current sensitive and temperature activated · Manual reset
Short-Circuit Current Rating (SCCR) · Higher short-circuit protection up to 100kA NOTE - Disconnect Switch not available with higher SCCR
option. SCCR option only available with factory installed electric heat.
Factory or Field Installed
K Disconnect Switch
· Accessible outside of unit · Spring loaded weatherproof cover furnished
L Electric Heat
· Helix wound nichrome elements · Individual element limit controls · Wiring harness · Unit fuse block · See Options/Accessories tables for ordering information
GFI Service Outlets (2) · 115V ground fault circuit interrupter (GFCI) type options:
· Factory installed, powered and wired · Factory installed, non-powered, field wired · Field installed, non-powered, field wired
Field Installed GFI Weatherproof Cover · Single-gang cover · Heavy-duty UV-resistant polycarbonate case
construction · Hinged base cover with gasket
INDOOR AIR QUALITY
M Air Filters
· Disposable 2 inch MERV 4 filters furnished as standard
Options/Accessories
Factory or Field Installed Healthy Climate® High Efficiency Air Filters · Disposable MERV 8 or MERV 13 (Minimum Efficiency
Reporting Value based on ASHRAE 52.2) efficiency 2-inch pleated filters

Field Installed Healthy Climate® High Efficiency MERV 16 Air Filters · Disposable MERV 16 (Minimum Efficiency Reporting
Value based on ASHRAE 52.2) efficiency 2-inch pleated filters
Healthy Climate® UVC Germicidal Light Kit
· Germicidal lamps emit ultra-violet (UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds
· UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan)
· Destroys the organism or controls its ability to reproduce · Field installed in the blower/evaporator coil section · Magnetic safety interlock terminates power when
access panels are removed · All necessary hardware for installation is included · Lamps operate on 110/230V-1ph power supply NOTE - Step-down transformer may be ordered separately
for 460V and 575V units. · Approved by ETL
Needlepoint Bipolar Ionization (NPBI) Kit · NPBI technology integrates with system controls for
effective air treatment · Ionization has been shown to effectively reduce harmful
pathogens, pollutants and odors NOTE - Please visit www.sciencedirect.com for additional
information. · Brush-type ionizer introduces a high concentration of
both positive and negative ions into the airstream · The bipolar ions are then dispersed into the occupied
space through the duct system proactively reducing the airborne contaminants · Ions travel within the building air stream and attach to particles, pathogens, and gas molecules, making them larger and easier to capture in the filtration system · UL 2998 certified for zero ozone emission
Indoor Air Quality (CO2) Sensors · Monitors CO2 levels, reports to the Lennox CORE®
Unit Controller which adjusts economizer dampers as needed
Replacement Filter Media Kit With Frame · Replaces existing pleated filter media · Includes washable metal mesh screen and metal frame
with clip for holding replaceable non-pleated filter

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 6

CONTROL SYSTEM LENNOX® CORE CONTROL SYSTEM
N The Lennox® CORE Control System is designed to
accelerate equipment install and service. Standard with all EnlightTM rooftop units, control system integrates key technologies that lower installation costs, drive system efficiency, and protect your investments. The Lennox® CORE Unit Controller is a microprocessorbased controller that provides flexible control of all unit functions.
CORE Mobile Service App · Guided Setup with progress indicators, detailed help, and
exportable summaries to manage simple, trouble-free setup, reducing commissioning times · Enhanced Test Functionality provides real-time sensor readings, trending, and reports that enable easy troubleshooting · Ability to set and configure parameters of the CORE Control System to manage sequence of operation · Economizer test function ensures economizer is operating correctly
Additional Features: · Built-In 7-Segment Display shows Unit Status and active
alarms for easy troubleshooting · Buttons for test and clearing delays · SmartWireTM System with keyed and removable screw
terminals ensure correct field wiring · Built-in BACnet MS/TP and IP allow open integration to
building management systems. · Two-port Ethernet Switch enables daisy chaining for
BACnet IP and automatic firmware updates NOTE - Unit Internet Connection required. · Profile setup copies key settings between units with the
same configuration to reduce setup time · USB port allows a technician to download and transfer
unit information to help verify service was performed · USB software updates on the Lennox® CORE Unit
Controller enhance functionality without the need to change components · Unit Controller Software
Configurable Built-In Functions · Discharge Air Cooling Control · Up to three distinct Cooling Airflows in Thermostat
Mode · Programmable independent heating, ventilation and
cooling blower speeds

· Discharge Air Heating Control · Economizer Control Options (See Economizer / Exhaust
Air / Outdoor Air sections) · Exhaust Fan Control Modes for fresh air damper position · Configurable Morning Warm-up · Night Setback Mode · Fresh Air Tempering for Improved Ventilation · Demand Control Ventilation · Low Ambient Controls for operation down to 0°F · Two Defrost Control Methods (demand and timed - heat
pumps only) Component Protection / Unit Safeguards: · Compressor Time-Off Delay · Adjustable Blower On/Off Delay · Return Air Temperature Limit Control · Safety Switch Input allows Controller to respond to a
external safety switch trip · Service Relay Output · Thermostat Bounce Delay · Smoke Alarm Mode has four choices (unit off, positive
pressure, negative pressure, purge) · "Strike Three" Protection · Minimum Compressor Run Time Control Methods / Interfaces: · DDC and 24V Thermostat · BACnet MS/TP and IP · LONTalk (Factory and Field Option) · Lennox S-BUS · Compatibility with Lennox Wireless Room Sensors · Zone Temperature Sensor Input · Dehumidistat and Humidity Sensor Inputs · Indoor Air Quality Inputs (2) · Built-in Control Parameter Defaults · Permanent Diagnostic Code Storage · Field Adjustable Control Parameters (Over 200 settings) · Multiple Configurable Digital Inputs · LED Indicators · PC Interface connects the Lennox® CORE Unit Controller
to a PC with the Lennox Unit Controller Software NOTE - Lennox® CORE Control System features vary with
the type of rooftop unit in which the control is installed.
EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 7

CONTROL SYSTEM

OPTIONS / ACCESSORIES

LENNOX® CORE CONTROL SYSTEM (continued)

ECONOMIZER

Controls Options

· Economizer operation is set and controlled by the

Factory or Field Installed
Blower Proving Switch · Monitors blower operation, shuts down unit if blower
fails

Lennox® CORE unit controller
· Simple plug-in connections from Economizer to unit controller for easy installation
· All EnlightTM rooftop units are equipped with factory installed CEC Title 24 approved sensors for outside,

Dirty Filter Switch

return and discharge air temperature monitoring

· Senses static pressure increase and issues alarm if necessary

NOTE - Optional sensors may be used instead of unit sensors to determine whether outdoor air is suitable

Fresh Air Tempering

for free cooling. See Options/Accessories table.

· Used in applications with high outside air requirements

Factory or Field Installed

· Controller energizes the first stage heat as needed to O High Performance Economizer

maintain a minimum supply air temperature for comfort,

· Approved for California Title 24 building standards

regardless of the thermostat demand

· Low leakage dampers are Air Movement and Control

· When ordered as a factory option, sensor ships with the

Association International (AMCA) Class 1A Certified -

unit for field installation

Maximum 3 CFM per sq. ft. leakage at 1 in. w.g.

Smoke Detector · Photoelectric type
· Installed in supply air section, return air section or both sections
· Available with power board and single sensor (supply or return) or power board and two sensors (supply and return)
· Power board located in unit control compartment
Interoperability via BACnet® or LonTalk® Protocols · Communication compatible with third-party automation
systems that support the BACnet Application Specific Controller device profile, LonMark® Space Comfort Controller functional profile, or LonMark Discharge Air Controller functional profile
Commercial Control Systems
Field Installed
Thermostats · Control system and thermostat options, see page 11

· ASHRAE 90.1 and IECC compliant
· Downflow or Horizontal with Outdoor Air Hood
· Outdoor Air Hood with mist elimination is included when Economizer is factory installed and is furnished with Economizer when ordered for field installation
NOTE - Downflow or horizontal economizer applications require optional Downflow or Horizontal Barometric Relief Dampers with Exhaust Hood.
· Linked damper action
· High torque 24-volt fully-modulating spring return damper motor
· Return air and outdoor air dampers
· Plug-in connections to unit
NOTE - High Performance Economizers are not approved for use with enthalpy controls in Title 24 applications.
NOTE - The Free Cooling setpoint for Title 24 applications must be set based on the Climate Zone where the system is installed. See Section 140.4 "Prescriptive Requirements for Space Conditioning Systems" of the California Energy Commission's 2019 Building Energy Efficiency Standards.
NOTE - Refer to Installation Instructions for complete setup information.

Differential Sensible Control · Factory setting
· Uses outdoor air and return air sensors that are furnished with the unit
· The Lennox® CORE unit controller compares outdoor air temperature with return air
· When the outdoor air is below the configured setpoint and cooler than return air, the controller activates the Economizer

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 8

OPTIONS / ACCESSORIES

ECONOMIZER (continued)

EXHAUST

Factory or Field Installed NOTE - Differential Sensible Control can be configured
in the field to provide Offset Differential Sensible Control or Single Sensible Control.

Factory or Field Installed
P Downflow Barometric Relief Dampers
· Allow relief of excess air

NOTE - In Offset Differential Sensible Control mode, the Economizer is enabled if the temperature

· Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle

differential (offset) between outdoor air and return air reaches the configured setpoint. In Single Sensible Control mode, the Economizer is enabled when outdoor air temperature falls below the configured setpoint.

· Exhaust hood is factory installed when dampers are factory installed with Economizer
· Exhaust hood is furnished with dampers when ordered for field installation

Global Control · Unit controller communicates with a DDC system with

· Bird screen furnished
Q Power Exhaust Fans

one global sensor (enthalpy or sensible)

· Install internal to unit for downflow applications only

· Determines whether outside air is suitable for free

with Economizer option

cooling on all units connected to the control system

· Provides exhaust air pressure relief

· Sensor must be field provided

· Interlocked to run when supply air blower is operating

Single Enthalpy Control (Not for Title 24)
· Outdoor air enthalpy sensor enables Economizer if the outdoor enthalpy is less than the setpoint of the control

· Fans run when outdoor air dampers are 50% open (adjustable)
· Motor is overload protected

Differential Enthalpy Control (Not for Title 24) · Order two Single Enthalpy Controls

· Dual propeller type fans are 20 in. diameter · Five blades

· One is field installed in the return air section

· Two 1/3 hp motors

· One is installed in the outdoor air section

· SCCR rated

· Allows the Economizer control to select between outdoor air or return air, whichever has lower enthalpy
Field Installed
Outdoor Air CFM Control · Maintains constant outdoor air volume levels on the
supply air fan and varying unit airflows
· Velocity sensor located in the rooftop unit outdoor air section, the Lennox® CORE unit controller changes the Economizer position to help minimize the effect of supply fan speed changes on outdoor air volume levels
· Setpoint for outdoor air volume is established by field testing
NOTE - Not available with Demand Control Ventilation (CO2 Sensor) or Building Pressure Control.
Building Pressure Control · Maintains constant building pressure level
· Includes a static pressure transducer and outdoor static pressure assembly

NOTE - Requires Economizer with furnished Outdoor Air Hood and Downflow Barometric Relief Dampers.
NOTE - All models are equipped with 2-stage power exhaust fans. Power exhaust operates in 1st stage (one fan) up to 70% of supply air blower speed. Both exhaust fans operate in 2nd stage when supply air blower speed is above 70% (adjustable) of full speed.
Field Installed
Horizontal Barometric Relief Dampers · For use when unit is configured for horizontal
applications requiring an Economizer
· Allows relief of excess air
· Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle
· Field installed in return air duct
· Bird screen and hood furnished

· Using differential pressure information between the outdoor air and the building air, the Lennox® CORE unit controller changes the Economizer position to help maintain a constant building pressure
NOTE - Not available with Demand Control Ventilation (CO2 Sensor) or Outdoor Air CFM Control.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 9

OPTIONS / ACCESSORIES
OUTDOOR AIR OPTIONS
Factory or Field Installed Outdoor Air Damper · Downflow or Horizontal · Linked mechanical dampers · 0 to 25% (fixed) outdoor air adjustable · Installs in unit · Includes outdoor air hood · Motorized model features fully modulating spring return
damper motor with plug-in connection · Manual model features parallel blade, gear-driven
dampers with adjustable fixed position NOTE - Manual Outdoor Air Damper is a field installed
option only. NOTE - Outdoor Air Hood is included when damper is
factory installed and is furnished with damper when ordered for field installation.
ROOF CURBS
Field Installed · Nailer strip furnished (downflow only) · Mates to unit · US National Roofing Contractors Approved · Shipped knocked down
Downflow Hybrid Roof Curbs · Interlocking tabs fasten corners together · No tools required for assembly · Can also be fastened together with furnished hardware · Available in 8, 14, 18, and 24 inch heights
Adjustable Pitch Curb · Fully adjustable pitch curbs (3/4 in. per foot in any
direction) provide a level platform for rooftop units allowing flexible installations on roofs with uneven or sloped angles · Interlocking tabs fasten corners together · No tools required for assembly · Hardware is furnished to connect upper curb with lower curb · Available in 14 inch height

Horizontal · Meet National Roofing Code requirements · Converts unit from downflow to horizontal (side) air flow · Return air is on unit · Supply air is on curb · See dimension drawings · Available in 26, 30, 37, and 41 inch heights NOTE - Requires Horizontal Return Air Panel Kit. NOTE - Optional Insulation Kit is available to help prevent
sweating.
Adaptor Curbs (not shown) · Curbs are regionally sourced · Dimensions vary based upon the source NOTE - Contact your local sales representative for a
detailed cut sheet with applicable dimensions.
CEILING DIFFUSERS
Field Installed Ceiling Diffusers (Flush or Step-Down) · White powder coat finish on diffuser face and grilles · Insulated UL listed duct liner · Diffuser box has collars for duct connection · Step-down diffusers have double deflection blades · Flush diffusers have fixed blades · Provisions for suspending · Internally sealed to prevent recirculation · Removable return air grille · Adapts to T-bar ceiling grids or plaster ceilings
Transitions (Supply and Return) · Used with diffusers · Installs in roof curb · Galvanized steel construction · Flanges furnished for duct connection to diffusers · Fully insulated

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 10

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS

CS8500 Commercial 7-Day Programmable Thermostat

CS3000 Commercial 5-2 Day Programmable Thermostat

MAINT

· Fully Communicating Sensor · Full Color Touchscreen Interface · Variable Speed System Control (On Compatible Units) · Up To 4 Heat / 4 Cool · Built-In Sensors For Temperature, Humidity And
Optional CO2 · Remote Sensor Options For Occupancy, Temperature · BACnet Capable Options · 5-2 or 7-Day Scheduling · Smooth Setback Recovery · Heat/Cool Auto-Changeover · Four-Wire Installation · FDD, ASHRAE, IECC Compliant CS7500 Commercial 7-Day Programmable Thermostat

Commercial
· Conventional Multi-Stage Thermostat · Intuitive Display · Push-Button Operation · Up To 2 Heat / 2 Cool · Built-In Temperature Sensor · Remote Temperature Sensing · Up to 5-2 Day Scheduling · Smooth Setback Recovery · Heat/Cool Auto-changeover Wireless/Wired Temperature/Humidity Room Sensor (LCS-5030)

· Premium Universal Thermostat · Full Color Touchscreen Interface · Up To 4 Heat / 3 Cool · Built-In Sensors For Temperature and Humidity · Remote Sensors Options For Temperature, Discharge
Air, Outdoor Air · 5-2 or 7-Day Scheduling · Smooth Setback Recovery · Heat/Cool Auto-Changeover · FDD, ASHRAE, IECC Compliant

· Simple Push-Button Override · Variable Speed System Control (On Compatible Units) · Up To 4 Heat / 4 Cool · AA Battery / 24VAC Powered · BluetoothTM Mesh Operation · SBUS Wired Operation · Automatic Sensor Averaging · Locking Hex Screw Wireless Repeater for LCS-5030

· Extends Effective Range of Wireless Sensor (LCS-5030) · 24VAC Only · Locking Hex Screw NOTE - Wireless only.
EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 11

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS
Wired Temperature/Humidity Room Sensor (Non-Communicating)

· Terminal blocks for wiring connections · Five-wire sensor connection · Off-white plastic enclosure · Non-adjustable · Relative humidity range: 0 -100% · +/- 3% Accuracy

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS

Description

CS8500 Commercial 7 Day Programmable Thermostat

CS8500 7-Day Thermostat

No CO2 Sensing

With CO2 Sensing

Sensors/Accessories

¹ Remote non-adjustable wall-mount 10k

¹ Remote non-adjustable wall-mount 11k

Sysbus Network Cable (Yellow) for CS8500 and LCS-5030 Wired Room Sensor

Twisted pair 100% shielded communication cable, Red and Black 22 AWG, yellow jacket, rated at 75°C, 300V, Plenum rated Insulation - Low smoke PVC, NEC, CMP

500 ft. box 1000 ft. box 2500 ft. roll

CS7500 Commercial 7-Day Programmable Thermostat

CS7500 7-Day Thermostat

Sensors/Accessories

² Remote non-adjustable wall-mount 20k

² Remote non-adjustable wall-mount 10k

Remote non-adjustable discharge air (duct mount)

Outdoor temperature sensor

CS3000 Commercial 5-2 Day Programmable Thermostat

CS3000 5-2 Day Thermostat

Sensors/Accessories

Remote non-adjustable wall mount 10k averaging

Thermostat wall mounting plate

Universal Thermostat Guard with Lock (clear)

Inside Dimensions (H x W x D) 5-7/8 x 8-3/8 x 3 in.

Temperature/Humidity Room Sensors

LCS-5030 Wireless/Wired Temperature/Humidity Room Sensor

Wireless Repeater for LCS-5030

A335MT13AE1 Wired Temperature/Humidity Room Sensor (Non-Communicating)

1 Up to nine of the same type remote temperature sensors can be connected in parallel.
2 Remote wall-mount sensors can be applied in any of the following combinations: One Sensor - (1) 47W36, Two Sensors - (2) 47W37, Three Sensors - (2) 47W36 and (1) 47W37 Four Sensors - (4) 47W36, Five Sensors - (3) 47W36 and (2) 47W37

Catalog No.
24K55 24K53 47W37 94L61
27M19 94L63 68M25
24K41 47W36 47W37 19L22 X2658
11Y05 47W37 X2659
39P21
21L07 21L09 21W06

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 12

SEQUENCE OF OPERATION

M S AV ® M U LT I - S TA G E A I R VO LU M E

Objective: Outline the unit functions as a result of room thermostat or zone sensor demands. Given: When economizer is present, it will function as an integral part of the unit cooling system. When not present, unit will function as if economizer is present but outdoor ambient is high and sensed as not suitable. UNIT OPERATION WITH 2-STAGE THERMOSTAT (2 COOL AND 2 HEAT STAGES, Y1, Y2, W1, W2) Supply Air Blower Speed
Unit has following supply air blower speed setting:  Ventilation speed  Cooling Speed - Low  Cooling Speed - High  Heating speed  Smoke speed (Used only in smoke removal option - not discussed)
¹ Unit Features An Economizer And Outdoor Air Is Suitable
Cooling - Thermostat Mode (Y1, Y2) Y1 Demand: All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting). Y2 Demand: All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55°F supply air temperature. If economizer stays at maximum open for 3 minutes, compressor 1 is energized while supply air blower stays on high cooling speed providing maximum cooling capacity.
¹ O utdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection.
Unit Does Not Feature An Economizer Or Outdoor Air Is Not Suitable
Y1 Demand: Compressor 1 operates, and supply air blower operates at low cooling speed. Y2 Demand: All compressors operate and supply air blower operates at high cooling speed.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 13

SEQUENCE OF OPERATION

M S AV ® M U LT I - S TA G E A I R VO LU M E

UNIT OPERATION WITH 3-STAGE THERMOSTAT OR ZONE SENSOR (3 COOL AND 2 HEAT STAGES, Y1, Y2, Y3 AND W1, W2) Supply Air Blower Speed
Unit has following supply air blower speed setting:  Ventilation speed  Cooling Speed - Low  Cooling Speed - Medium  Cooling Speed - High  Heating speed  Smoke speed (Used only in smoke removal option - not discussed)
¹ Unit Features An Economizer And Outdoor Air Is Suitable
Cooling - Thermostat or Zone Sensor Mode (Y1, Y2, Y3) Y1 Demand: All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting). Y2 Demand: All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55°F supply air temperature. If economizer stays at maximum open for 3 minutes, compressor 1 is energized while supply air blower stays on high cooling speed providing maximum cooling capacity. After compressors are energized the economizer stays at maximum open. Y3 Demand: Compressors 1 and 2 are energized while supply air blower stays on high cooling speed.
¹ O utdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection.
Unit Does Not Feature An Economizer or Outdoor Air Is Not Suitable
Y1 Demand: Compressor 1 operates at part load and supply air blower operates at low cooling speed. Y2 Demand: Compressor 1 operates at part load with compressor 2 ON, and supply air blower operates at medium cooling speed. Y3 Demand: All compressors operate and supply air blower operates at high cooling speed. Defrost Mode
Coil Sensors (RT48 - Circuit 1 and RT49 - Circuit 2) and Ambient Sensor (RT17) provides input to the Lennox® CORE Unit Controller to initiate a defrost cycle if needed. Coil sensors are located on a return bend for each circuit on the front of the outdoor coil. Ambient sensor is located on the inside of the corner mullion on the back of the outdoor coil section. If a coil sensor measures a temperature below 35°F during mechanical heating mode, defrost logic is enabled. The system will constantly monitor coil and ambient temperatures and will initiate a defrost cycle if the controller determines that the target temperature difference between the coil and ambient temperature has been satisfied, or when the accumulated run time with coil temperature below 35°F reaches 6 hours. Defrost will not be activated on more than one circuit at the time. If the ambient sensor fails, or the circuit is in uncalibrated state, the controller will switch to time/temperature defrost operation. Electric heat is energized during a defrost cycle to maintain discharge air temperature.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 14

SEQUENCE OF OPERATION

M S AV ® M U LT I - S TA G E A I R VO LU M E

Heating Mode: Thermostat or Zone Sensor W1 Demand: A first-stage heating demand (W1) will energize compressors 1 and 2 and the outdoor fans.
NOTE ­ L1 & L2 reversing valves are de-energized in the heating mode. Units With Optional Electric Heat: An increased heating demand (W2) will energize electric heat. Electric heat is also energized during the defrost cycle (W1) to maintain discharge air temperature.
Modulating Outdoor Air Damper
The minimum damper position for "occupied low blower" and "occupied high blower" is adjusted during unit setup to provide minimum fresh air requirements per ASHRAE 62.1 at the corresponding supply air blower speeds.
 When supply air blower is off or the unit is in unoccupied mode, the outdoor air damper is closed.  When unit is in occupied mode and supply air blower is operating at a speed below the "midpoint" blower
speed, the outdoor air damper is at minimum "low blower" position.  When unit is in occupied mode and supply air blower is operating at a speed equal to or above the
"midpoint" blower speed, the outdoor air damper is at minimum "high blower" position. NOTE - The "midpoint" blower speed is an average of the minimum and maximum blower speed (minimum speed +
maximum speed divided by 2). Power Exhaust Operation
NOTE - POWER EXHAUST OPERATION IS THE SAME FOR ALL CONTROL OPTIONS MSAV® models are equipped with 2-stage power exhaust fans. Power exhaust fans operate when economizer outdoor air dampers are 50% open (adjustable). Power exhaust operates in 1st stage (one fan) up to 70% of supply air blower speed. 2nd stage power exhaust fans (both fans) operate when supply air blower speed is above 70% (adjustable) of full speed.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 15

OPTIONS / ACCESSORIES

Item Description

Catalog Number

COOLING SYSTEM

Condensate Drain Trap Drain Pan Overflow Switch

PVC Copper

BLOWER - SUPPLY AIR

Blower Option Motors

MSAV® Multi-Stage Air Volume option (With VFD Bypass Control) MSAV® Multi-Stage Air Volume option (Without VFD Bypass Control)
Belt Drive - 3 hp

Belt Drive - 5 hp Belt Drive - 7.5 hp

Drive Kits
See Blower Data Tables for usage and selection

Belt Drive - 10 hp Kit #1 535-725 rpm Kit #2 710-965 rpm Kit #3 685-856 rpm Kit #4 850-1045 rpm Kit #5 945-1185 rpm Kit #6 850-1045 rpm Kit #7 945-1185 rpm Kit #8 1045-1285 rpm Kit #10 1045-1285 rpm Kit #11 1135-1365 rpm

Blower Belt Auto-Tensioner

22H54 76W27 21Z07
Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory 24B80

CABINET Combination Coil/Hail Guards Corrosion Protection

23U71 Factory

CONTROLS

Blower Proving Switch

Commercial Controls

CPC Einstein Integration

LonTalk® Module

Novar® LSE

Dirty Filter Switch

Fresh Air Tempering

Smoke Detector - Supply or Return (Power board and one sensor)

Smoke Detector - Supply and Return (Power board and two sensors)

NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed.

21Z10 Factory 54W27 Factory 53W68 21Z08 22H56 22H57

Unit Model No

156

180

240

X

X

X

X

X

X

OX

OX

OX

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

X

X

X

OX

OX

OX

O

O

O

OX

OX

OX

O

O

O

OX

OX

OX

O

O

O

OX

OX

OX

OX

OX

OX

OX

OX

OX

OX

OX

OX

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 16

OPTIONS / ACCESSORIES

Item Description

Catalog Number

Unit Model No

156

180

240

INDOOR AIR QUALITY

Air Filters Healthy Climate® High Efficiency Air Filters 24 x 24 x 2 (Order 6 per unit)
Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media)

MERV 8 54W67 OX

OX

OX

MERV 13 52W40 OX

OX

OX

MERV 16 21U42

X

X

X

44N61

X

X

X

Indoor Air Quality (CO2) Sensors

Sensor - Wall-mount, off-white plastic cover with LCD display

77N39

X

X

X

Sensor - Wall-mount, off-white plastic cover, no display

23V86

X

X

X

Sensor - Black plastic case with LCD display, rated for plenum mounting

87N52

X

X

X

Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting

87N54

X

X

X

CO2 Sensor Duct Mounting Kit - for downflow applications

85L43

X

X

X

Aspiration Box - for duct mounting non-plenum rated CO2 sensors (77N39)

90N43

X

X

X

Needlepoint Bipolar Ionization (NPBI)

Needlepoint Bipolar Ionization (NPBI) Kit

21U37

X

X

21U38

X

UVC Germicidal Light Kit

1 Healthy Climate® UVC Light Kit (110/230v-1ph)

21A94

X

X

X

Step-Down Transformers

460V primary, 230V secondary 10H20

X

X

X

575V primary, 230V secondary 10H21

X

X

X

ELECTRICAL

Voltage 60 Hz

208/230V - 3 phase Factory

O

O

O

460V - 3 phase Factory

O

O

O

575V - 3 phase Factory

O

O

O

Disconnect Switch (see Electric Heat Tables for usage,
HACR Circuit Breakers

80 amp 54W85 OX

OX

OX

150 amp 54W86 OX

OX

OX

250 amp 54W87 OX

OX

OX

Factory

O

O

O

² Short-Circuit Current Rating (SCCR) of 100kA (includes Phase/Voltage Detection)

Factory

O

O

O

GFI Service Outlets

15 amp non-powered, field-wired (208/230V, 460V, 575V) 74M70 OX

OX

OX

15 amp factory-wired and powered (208/230V, 460V) Factory

O

O

O

³ 20 amp non-powered, field-wired (208/230V, 460V, 575V) 67E01

X

X

X

³ 20 amp non-powered, field-wired (575V) Factory

O

O

O

Weatherproof Cover for GFI

10C89

X

X

X

1 Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s).
2 Disconnect Switch not available with SCCR option. SCCR option is only available with factory installed electric heat or no electric. SCCR option is not available if the MOCP of the configured unit is greater than 200A.
3 Canada requires a minimum 20 amp circuit. Select 20 amp, non-powered, field wired GFI.

NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 17

OPTIONS / ACCESSORIES

Item Description

Catalog Number

Unit Model No

156

180

240

ELECTRIC HEAT

15 kW 30 kW 45 kW 60 kW

208/230V-3ph 22H66 OX

OX

OX

460V-3ph 22H67 OX

OX

OX

575V-3ph 22V35 OX

OX

OX

208/230V-3ph 22H70 OX

OX

OX

460V-3ph 22H71 OX

OX

OX

575V-3ph 22V37

OX

OX

OX

208/230V-3ph 22H74 OX

OX

OX

460V-3ph 22H75 OX

OX

OX

575V-3ph 22V39

OX

OX

OX

208/230V-3ph 22H78 OX

OX

OX

460V-3ph 22H79 OX

OX

OX

575V-3ph 22V41

OX

OX

OX

90 kW

208/230V-3ph 22H80

OX

460V-3ph 22H81

OX

575V-3ph 22V42

OX

ECONOMIZER

High Performance Economizer (Approved for California Title 24 Building Standards / AMCA Class 1A Certified)

High Performance Economizer Downflow or Horizontal - Includes Outdoor Air Hood. Order Downflow or Horizontal Barometric Relief Dampers separately.

E1ECON17C-2 22J18

OX

OX

OX

Economizer Controls Differential Enthalpy (Not for Title 24)

Order 2 21Z09 OX

OX

OX

Sensible Control

Sensor is Furnished Factory

O

O

O

Single Enthalpy (Not for Title 24)

21Z09 OX

OX

OX

Global Control

Sensor Field Provided Factory

O

O

O

Building Pressure Control Outdoor Air CFM Control Barometric Relief Dampers With Exhaust Hood Downflow Barometric Relief Dampers

13J77

X

X

X

13J76

X

X

X

54W78 OX

OX

OX

Horizontal Barometric Relief Dampers OUTDOOR AIR

16K99

X

X

X

Outdoor Air Dampers With Outdoor Air Hood Motorized

22J27

OX

OX

OX

Manual
NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed.

13U05

X

X

X

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 18

OPTIONS / ACCESSORIES

Item Description

Catalog Number

Unit Model No

156

180

240

¹ POWER EXHAUST (DOWNFLOW APPLICATIONS ONLY)

Standard Static, SCCR Rated

208/230V 22H90 OX

OX

OX

460V 22H91 OX

OX

OX

575V 22V34 OX

OX

OX

ROOF CURBS

Hybrid Roof Curbs, Downflow 8 in. height 14 in. height 18 in. height 24 in. height Adjustable Pitch Curb 14 in. height Standard Roof Curbs, Horizontal - Requires Horizontal Return Air Panel Kit 26 in. height - slab applications 37 in. height - rooftop applications Insulation Kit For Standard Horizontal Roof Curbs For 26 in. Curb For 37 in. Curb Horizontal Return Air Panel Kit Required for Horizontal Applications with Roof Curb

11F58

X

X

X

11F59

X

X

X

11F60

X

X

X

11F61

X

X

X

43W26

X

X

X

11T89

X

X

X

11T96

X

X

X

73K32

X

X

X

73K34

X

X

X

87M00

X

X

X

CEILING DIFFUSERS

Step-Down - Order one

RTD11-185S 13K63

X

X

RTD11-275S 13K64

X

Flush - Order one

FD11-185S 13K58

X

X

FD11-275S 13K59

X

Transitions (Supply and Return) - Order one

C1DIFF33C-1 12X68

X

X

C1DIFF34C-1 12X70

X

1 Field installed Power Exhaust requires Economizer with Outdoor Air Hood and Downflow Barometric Relief Dampers with Exhaust Hood. Must be ordered separately.

NOTE - Catalog numbers shown are for ordering field installed accessories. OX = Configure To Order (Factory Installed) or Field Installed. O = Configure To Order (Factory Installed). X = Field Installed.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 19

SPECIFICATIONS

General Data

Nominal Tonnage

13 Ton

15 Ton

20 Ton

Model Number

LHT156H4M

LHT180H4M

LHT240H4M

Efficiency Type

High

High

High

Blower Type

MSAV®

MSAV®

MSAV®

Multi-Stage Air Volume Multi-Stage Air Volume Multi-Stage Air Volume

Cooling

Gross Cooling Capacity - Btuh

154,000

181,000

232,000

Performance

1 Net Cooling Capacity - Btuh

150,000

176,000

224,000

1 AHRI Rated Air Flow - cfm

4500

5500

7000

Total Unit Power - kW

12.3

15.8

20.1

1 IEER (Btuh/Watt)

15.7

15.5

15.5

1 EER (Btuh/Watt)

12.1

11.1

11.1

Refrigerant

Refrigerant Type

R-410A

R-410A

R-410A

Charge

Circuit 1

21 lbs. 0 oz.

22 lbs. 12 oz.

22 lbs. 8 oz.

Circuit 2

21 lbs. 0 oz.

21 lbs. 12 oz.

21 lbs. 8 oz.

Heating

1 Total High Heat Capacity - Btuh

144,000

174,000

224,000

Performance

Total Unit Power - kW

12.4

15.0

19.3

1 C.O.P.

3.40

3.40

3.40

1 Total Low Heat Capacity - Btuh

80,000

96,000

128,000

Total Unit Power (kW)

11.1

13.4

17.9

1 C.O.P.

2.10

2.10

2.10

Electric Heat (kW) Available - See page 18

15, 30, 45, 60 kW

15, 30, 45, 60 kW

15, 30, 45, 60, 90 kW

Compressor Type (number)

Scroll (2)

Scroll (2)

Scroll (2)

Outdoor Coils

Net face area (total) - sq. ft.

55.1

55.1

55.1

Number of rows

2

2

2

Fins per inch

20

20

20

Outdoor Coil

Motor - (No.) horsepower

(6) 1/3

(6) 1/3

(6) 1/3

Fans

Motor rpm

1075

1075

1075

Total Motor watts

2150

2150

2150

Diameter - (No.) in.

(6) 24

(6) 24

(6) 24

Number of blades

3

3

3

Total Air volume - cfm

16,300

16,300

16,300

Indoor Coils

Net face area (total) - sq. ft.

21.4

21.4

21.4

Tube diameter - in.

3/8

3/8

3/8

Number of rows

4

4

4

Fins per inch

14

14

14

Drain connection - No. and size

(1) 1in. FPT

(1) 1in. FPT

(1) 1in. FPT

Expansion device type

Balance Port Thermostatic Expansion Valve (removable element head)

2 Indoor

Nominal motor output

3 hp, 5 hp

3 hp, 5 hp, 7.5 hp

5 hp, 7.5 hp, 10 hp

Blower

Max. usable motor output (US)

3.45 hp, 5.75 hp

3.45 hp, 5.75 hp, 8.62 hp 5.75 hp, 8.62 hp, 11.5 hp

and Drive Selection

Motor - Drive kit number

3 hp
Kit 1 535-725 rpm Kit 2 710-965 rpm

3 hp
Kit 1 535-725 rpm Kit 2 710-965 rpm

5 hp
Kit 3 685-856 rpm Kit 4 850-1045 rpm

5 hp

5 hp

Kit 5 945-1185 rpm

Kit 3 - 685-856 rpm

Kit 3 - 685-856 rpm

7.5 hp

Kit 4 850-1045 rpm

Kit 4 850-1045 rpm

Kit 6 850-1045 rpm

Kit 5 945-1185 rpm

Kit 5 945-1185 rpm

Kit 7 945-1185 rpm

7.5 hp

Kit 8 1045-1285 rpm

Kit 6 850-1045 rpm

10 hp

Kit 7 945-1185 rpm

Kit 7 945-1185 rpm

Kit 8 1045-1285 rpm

Kit 10 1045-1285 rpm

Kit 11 1135-1365 rpm

Blower wheel nominal D x W - in.

(2) 15 x 15 in.

(2) 15 x 15 in.

(2) 15 x 15

Filters

Type of filter

MERV 4, Disposable

Number and size - in.

(6) 24 x 24 x 2

Electrical characteristics

208/230V, 460V or 575V - 60 hertz - 3 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.

1 AHRI Certified to AHRI Standard 340/360:
Cooling Ratings - 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air. High Temperature Heating Ratings - 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air. Low Temperature Heating Ratings - 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air.

2 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

NOTE ­ Motor service factor limit - 1.0.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 20

COOLING/HEATING RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

13 TON - COOLING LHT156H4M (1 COMPRESSOR - PART LOAD)

Entering Wet Bulb Tem-

Total Air Volume

perature cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

1800 58.6 1.96 .77 .94 1.00 55.8 2.26 .79 .96 1.00 52.6 2.62 .81 .99 1.00

63°F 2250 61.8 1.93 .84 1.00 1.00 58.8 2.23 .86 1.00 1.00 55.8 2.59 .89 1.00 1.00

2700 65.2 1.89 .91 1.00 1.00 62.2 2.20 .94 1.00 1.00 58.9 2.57 .97 1.00 1.00

1800 62.8 1.92 .59 .74 .90 59.5 2.22 .59 .76 .92 56.0 2.59 .60 .78 .95

67°F 2250 65.5 1.89 .63 .81 .99 62.2 2.20 .64 .83 1.00 58.6 2.57 .65 .86 1.00

2700 67.5 1.87 .67 .88 1.00 64.1 2.18 .68 .91 1.00 60.2 2.55 .70 .94 1.00

1800 67.2 1.87 .41 .57 .72 64.0 2.18 .41 .58 .73 60.4 2.55 .41 .58 .74

71°F 2250 70.6 2.14 .42 .61 .79 66.6 2.16 .42 .62 .81 62.7 2.53 .43 .63 .83

2700 71.8 1.82 .44 .65 .86 68.1 2.15 .45 .67 .88 64.5 2.51 .46 .68 .91

Total Cool Cap. kBtuh 49.1 52.8 55.7 52.6 54.9 56.6 56.7 59.0 60.6

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

3.03 .83 1.00 1.00

3.00 .92 1.00 1.00

2.98 1.00 1.00 1.00

3.01 .61 .80 .98

2.98 .67 .89 1.00

2.97 .72 .98 1.00

2.97 .41 .59 .77

2.95 .44 .65 .86

2.93 .46 .71 .95

13 TON - COOLING LHT156H4M (2 COMPRESSORS - PART LOAD / FULL LOAD)

Entering Wet Bulb Tem-

Total Air Volume

perature cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

3000 124.4 7.04 .69 .82 .94 117.1 7.96 .70 .84 .95 109.5 9.37 .71 .86 .97

63°F 3750 132.1 7.07 .74 .89 .99 124.3 7.99 .76 .91 1.00 116.4 9.39 .78 .93 1.00

4500 138.5 7.09 .79 .94 1.00 131.3 8.02 .81 .95 1.00 120.8 9.41 .83 .98 1.00

3000 133.4 7.07 .54 .67 .79 125.8 7.99 .54 .68 .81 118.0 9.39 .55 .69 .82

67°F 3750 141.0 7.11 .58 .72 .86 133.0 8.03 .58 .73 .88 122.3 9.43 .59 .76 .90

4500 147.2 7.14 .60 .77 .92 138.3 8.05 .61 .79 .93 129.9 9.10 .62 .81 .95

3000 142.5 7.10 .41 .53 .64 135.1 8.03 .41 .53 .65 126.1 9.06 .40 .53 .66

71°F 3750 150.6 7.13 .42 .56 .69 142.3 8.05 .42 .56 .71 131.0 9.54 .42 .58 .73

4500 154.2 7.54 .43 .59 .75 148.1 8.08 .43 .60 .76 140.0 9.54 .44 .61 .78

Total Cool Cap. kBtuh 98.7 107.9 114.2 109.3 115.8 116.9 117.4 125.0 130.3

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

10.72 .73 .90 .99

11.97 .80 .95 1.00

11.96 .86 1.00 1.00

11.97 .55 .70 .85

11.97 .59 .77 .92

11.19 .63 .85 .97

11.95 .40 .54 .68

11.17 .42 .58 .74

11.19 .43 .62 .81

13 TON - COOLING LHT156H4M (2 COMPRESSORS - FULL LOAD)

Entering Wet Bulb Tem-

Total Air Volume

perature cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

4160 150.1 8.13 .73 .88 1.00 141.2 9.14 .75 .90 1.00 132.0 10.28 .76 .93 1.00

63°F 5200 157.4 8.20 .79 .96 1.00 148.8 9.20 .81 .99 1.00 140.0 10.34 .84 1.00 1.00

6240 164.7 8.26 .85 1.00 1.00 157.0 9.73 .88 1.00 1.00 147.8 10.41 .90 1.00 1.00

4160 160.1 8.22 .57 .71 .85 151.2 9.23 .57 .72 .87 141.5 10.36 .58 .74 .89

67°F 5200 167.2 8.28 .61 .77 .93 156.2 10.15 .61 .79 .95 147.8 10.41 .62 .81 .98

6240 172.7 8.34 .65 .83 .99 166.1 10.18 .65 .85 1.00 149.7 10.89 .68 .89 1.00

4160 169.9 8.31 .42 .55 .68 160.4 10.17 .42 .56 .70 148.9 10.88 .42 .57 .72

71°F 5200 177.9 8.38 .43 .59 .75 171.6 9.84 .44 .60 .77 159.6 10.92 .44 .61 .78

6240 186.0 8.86 .45 .63 .81 175.0 9.50 .45 .64 .82 164.4 10.96 .46 .66 .85

Total Cool Cap. kBtuh 122.7 131.3 137.0 131.8 135.0 143.3 142.3 148.8 149.7

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

11.57 .79 .96 1.00

13.31 .86 1.00 1.00

13.98 .94 1.00 1.00

13.31 .59 .76 .93

13.99 .64 .84 1.00

13.99 .69 .91 1.00

13.99 .42 .58 .73

14.01 .44 .63 .82

12.76 .46 .69 .90

13 TON - HEATING LHT156H4M

Indoor Coil Air Volume
70°F Dry Bulb cfm
4160 5200 6240

65°F

Total

Comp.

Heating

Motor

Capacity

Input

kBtuh

kW

190.6

10.10

196.3

9.32

200.3

8.82

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Heating

Motor

Heating

Motor

Heating

Capacity

Input

Capacity

Input

Capacity

kBtuh

kW

kBtuh

kW

kBtuh

136.1

8.83

94.7

7.92

61.7

139.6

8.27

96.6

7.53

63.1

142.3

7.92

98.4

7.30

64.5

Comp. Motor Input
kW 7.09
6.86
6.73

-15°F

Total

Comp.

Heating

Motor

Capacity

Input

kBtuh

kW

37.5

6.62

38.6

6.56

39.7

6.55

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 21

COOLING/HEATING RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

15 TON - COOLING LHT180H4M (1 COMPRESSOR - PART LOAD)

Entering Wet Bulb Tem-
perature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

2000 64.3 2.43 0.76 0.94 1 60.6 2.67 0.77 0.98 1 56.8 2.96 0.79 1 1 52.9 3.32 0.81 1

1

63°F 2400 67.1 2.46 0.82 1 1 63.6 2.69 0.83 1

1 60.1 2.98 0.86 1 1 56 3.33 0.89 1

1

2800 70.3 2.49 0.88 1 1 66.8 2.71 0.91 1

1 63.2 2.99 0.95 1 1 58.7 3.34 0.99 1

1

2000 68.9 2.47 0.57 0.73 0.9 65 2.7 0.57 0.74 0.93 60.9 2.98 0.58 0.76 0.96 56.3 3.33 0.58 0.78 1

67°F 2400 71.2 2.49 0.61 0.79 1 67.3 2.71 0.61 0.81 1 63.1 2.99 0.62 0.83 1 58.4 3.34 0.63 0.86 1

2800 73.1 2.51 0.64 0.85 1 69.2 2.72 0.65 0.88 1

65

3 0.67 0.91 1 59.9 3.34 0.68 0.96 1

2000 73.8 2.52 0.4 0.56 0.71 69.9 2.73 0.39 0.56 0.72 65.7 3 0.39 0.56 0.73 60.8 3.34 0.38 0.57 0.75

71°F 2400 76.1 2.54 0.41 0.59 0.77 72.2 2.75 0.41 0.6 0.78 67.9 3.02 0.41 0.61 0.81 62.7 3.35 0.41 0.62 0.84

2800 77.9 2.56 0.43 0.63 0.83 73.8 2.76 0.43 0.64 0.85 69 3.02 0.43 0.66 0.88 64.1 3.36 0.43 0.68 0.93

15 TON - COOLING LHT180H4M (2 COMPRESSORS - PART LOAD / FULL LOAD)

Entering Wet Bulb Tem-
perature

Total Air Volume
cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

3300 138 8.46 0.67 0.81 0.92 129.3 9.47 0.68 0.82 0.94 119.4 10.93 0.69 0.84 0.95 109.6 11.93 0.7 0.86 0.97

63°F 4000 146.3 8.54 0.72 0.87 0.97 136.9 9.52 0.73 0.89 0.99 126.8 10.99 0.74 0.9 1 116.6 11.97 0.76 0.92 1

4800 154.2 8.62 0.77 0.92 1 143.9 9.58 0.79 0.94 1 133.6 11.05 0.81 0.96 1 123 12.39 0.83 0.97 1

3300 149 8.56 0.52 0.65 0.77 139.5 9.54 0.52 0.66 0.79 127.3 10.66 0.52 0.67 0.81 117.8 11.98 0.52 0.68 0.83

67°F 4000 157.2 8.64 0.55 0.69 0.84 146.8 9.61 0.55 0.71 0.85 136 10.73 0.55 0.72 0.87 124.5 12.03 0.56 0.74 0.89

4800 164.1 8.72 0.58 0.75 0.9 152.9 9.67 0.59 0.76 0.91 141.8 10.78 0.59 0.78 0.93 129.6 12.45 0.6 0.81 0.95

3300 160.1 8.66 0.39 0.51 0.63 149.6 9.63 0.38 0.51 0.63 139.4 10.75 0.37 0.51 0.64 127.6 12.43 0.36 0.51 0.66

71°F 4000 167.5 8.74 0.4 0.54 0.67 157.3 9.7 0.4 0.54 0.68 146.4 10.81 0.39 0.54 0.7 132.1 12.49 0.38 0.55 0.72

4800 174.8 8.82 0.42 0.57 0.72 164.2 9.77 0.41 0.58 0.74 152.6 10.87 0.41 0.58 0.76 140.6 12.15 0.4 0.59 0.79

15 TON - COOLING LHT180H4M (2 COMPRESSORS - FULL LOAD)

Outdoor Air Temperature Entering Outdoor Coil

Entering Wet Bulb Tem-

Total Air Volume

perature

Total Cool Cap.

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

105°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

Total Cool Cap.

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

4800 176.1 10.46 0.72 0.87 1 165 11.67 0.73 0.89 1 153 13.07 0.74 0.91 1 140.1 15.42 0.77 0.94 1

63°F 6000 185.8 10.55 0.78 0.95 1 174 11.75 0.79 0.97 1 161.8 13.16 0.82 0.99 1 150.7 15.45 0.84 1

1

7200 193.4 10.62 0.84 1 1 182.4 11.83 0.86 1

1 170.9 13.22 0.88 1 1 156.5 15.46 0.91 1

1

4800 188.5 10.58 0.56 0.7 0.83 177.3 11.78 0.56 0.71 0.85 164.5 13.17 0.56 0.72 0.88 152.9 15.45 0.57 0.74 0.91

67°F 6000 197.8 10.66 0.59 0.76 0.91 185.7 11.87 0.6 0.77 0.94 172.5 13.24 0.61 0.79 0.97 155.8 15.46 0.62 0.83 1

7200 204.2 10.74 0.63 0.82 0.98 192.1 11.92 0.64 0.84 1 175 13.84 0.65 0.87 1 165.4 15.48 0.66 0.89 1

4800 201.2 10.71 0.41 0.54 0.67 189.3 11.89 0.41 0.55 0.68 176.3 13.27 0.4 0.55 0.7 164.4 15.47 0.4 0.56 0.71

71°F 6000 210.5 10.8 0.43 0.58 0.73 198.4 12 0.43 0.59 0.75 183.5 13.87 0.42 0.6 0.78 172.9 15.53 0.42 0.61 0.79

7200 217.1 10.97 0.44 0.62 0.79 204.7 12.07 0.44 0.63 0.82 193.3 13.93 0.44 0.64 0.83 177.6 15.58 0.44 0.66 0.87

15 TON - HEATING LHT180H4M

Indoor Coil Air Volume
70°F Dry Bulb cfm
4800 6000 7200

65°F

Total

Comp.

Heating

Motor

Capacity

Input

kBtuh

kW

232.5

12.63

240.4

11.67

247.5

11.08

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Heating

Motor

Heating

Motor

Heating

Capacity

Input

Capacity

Input

Capacity

kBtuh

kW

kBtuh

kW

kBtuh

165.3

11.38

112.0

10.27

74.7

170.7

10.68

115.5

9.76

77.1

175.1

10.22

118.8

9.45

79.9

Comp. Motor Input
kW 9.51
9.17
8.95

-15°F

Total

Comp.

Heating

Motor

Capacity

Input

kBtuh

kW

45.8

8.73

47.7

8.58

49.9

8.51

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 22

COOLING/HEATING RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

20 TON - COOLING LHT240H4M (1 COMPRESSOR - PART LOAD)

Entering Wet Bulb Tem-

Total Air Volume

perature cfm

Total Cool Cap.
kBtuh

65°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

75°F

85°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

3200 92.2 3.35 0.82 1

1 86.6 3.91 0.84 1

1 80.4 4.54 0.86 1 1

63°F 4000 98 3.33 0.9 1

1 92.4 3.88 0.93 1

1

86 4.52 0.96 1 1

4800 102.7 3.32 0.98 1

1 96.6 3.87 1

1

1 90.2 4.5 1 1 1

3200 98.3 3.33 0.61 0.8 0.98 92.3 3.88 0.61 0.81 0.99 85.1 4.53 0.62 0.84 1

67°F 4000 102.1 3.32 0.66 0.88 1 95.5 3.87 0.66 0.9 1 88.9 4.51 0.68 0.93 1

4800 105 3.32 0.71 0.96 1 98.6 3.87 0.73 0.98 1 91.4 4.5 0.75 1 1

3200 105.1 3.32 0.41 0.6 0.77 98.7 3.87 0.41 0.6 0.78 91.5 4.5 0.4 0.61 0.81

71°F 4000 108.7 3.31 0.44 0.66 0.86 102.1 3.86 0.43 0.66 0.88 94.8 4.48 0.43 0.68 0.91

4800 111.5 3.31 0.46 0.71 0.94 104.6 3.85 0.46 0.73 0.97 97.1 4.47 0.46 0.75 0.99

Total Cool Cap. kBtuh 73.9 79.4 83.7 77.8 81.4 84.2 84.3 87.3 89.6

95°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

5.26 0.89 1

1

5.23 0.99 1

1

5.21 1

1

1

5.24 0.62 0.86 1

5.22 0.7 0.97 1

5.21 0.77 1

1

5.21 0.39 0.62 0.84

5.2 0.42 0.69 0.95

5.19 0.46 0.77 1

20 TON - COOLING LHT240H4M (2 COMPRESSORS - PART LOAD / FULL LOAD)

Entering Wet Bulb Tem-

Total Air Volume

perature cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

4800 182.4 11.6 0.7 0.85 0.96 165.7 13.2 0.7 0.87 0.97 151.9 14.91 0.72 0.89 0.99

63°F 6000 194.3 11.61 0.76 0.92 1 182.6 13.23 0.77 0.93 1 162.7 14.94 0.79 0.95 1

7200 202.9 11.63 0.81 0.97 1 188.4 13.26 0.84 0.98 1 172.8 14.97 0.86 1 1

4800 197.2 11.62 0.54 0.67 0.81 181.3 13.21 0.53 0.68 0.83 164.8 14.95 0.53 0.69 0.85

67°F 6000 208.2 11.63 0.57 0.74 0.89 192.1 13.24 0.57 0.75 0.91 174.6 14.99 0.58 0.77 0.93

7200 217.1 11.65 0.61 0.79 0.95 200.2 13.26 0.62 0.81 0.96 182.2 15.01 0.62 0.84 0.98

4800 212.2 11.63 0.39 0.52 0.65 195.7 13.24 0.38 0.52 0.66 179.8 14.99 0.37 0.52 0.67

71°F 6000 223.8 11.66 0.41 0.56 0.71 207.2 13.26 0.4 0.57 0.73 189.6 15.03 0.39 0.57 0.75

7200 232 11.67 0.43 0.6 0.77 214.7 13.28 0.42 0.61 0.79 196.7 15.05 0.41 0.62 0.82

Total Cool Cap. kBtuh 135.8 146.7 156 148.3 157.1 162.9 162.3 170.4 176.7

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

16.9 0.73 0.91 1

16.92 0.82 0.97 1

16.94 0.89 1

1

16.94 0.52 0.71 0.88

16.98 0.58 0.79 0.95

16.99 0.63 0.87 1

16.97 0.35 0.52 0.69

17 0.38 0.58 0.77

17.02 0.4 0.63 0.85

20 TON - COOLING LHT240H4M (2 COMPRESSORS - FULL LOAD)

Entering Wet Bulb Tem-

Total Air Volume

perature cfm

Total Cool Cap.
kBtuh

85°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

Total Cool Cap.
kBtuh

Outdoor Air Temperature Entering Outdoor Coil

95°F

105°F

Comp. Sensible To Total Total Comp. Sensible To Total

Motor

Ratio (S/T)

Cool Motor

Ratio (S/T)

Input

Dry Bulb

Cap. Input

Dry Bulb

kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

6400 229.1 14.17 0.73 0.88 1 212.2 15.82 0.73 0.9 1 195.8 17.66 0.75 0.93 1

63°F 8000 241.1 14.3 0.79 0.96 1 223.9 15.94 0.81 0.99 1 207.6 17.78 0.83 1 1

9600 253 14.41 0.85 1

1 236.1 16.07 0.87 1

1 220.6 17.93 0.9 1 1

6400 245.8 14.34 0.56 0.7 0.85 228.6 15.99 0.55 0.71 0.87 210.9 17.83 0.55 0.73 0.89

67°F 8000 259 14.47 0.59 0.77 0.93 240 16.11 0.6 0.78 0.96 221.3 17.94 0.6 0.81 0.98

9600 266.6 14.55 0.63 0.83 0.99 249 16.2 0.64 0.85 1 229.2 18.03 0.65 0.88 1

6400 262.7 14.51 0.41 0.54 0.68 245.3 16.16 0.4 0.55 0.69 227.2 18 0.39 0.55 0.7

71°F 8000 276.4 14.64 0.42 0.59 0.74 257.4 16.29 0.42 0.59 0.76 237.7 18.11 0.41 0.6 0.78

9600 284.9 14.72 0.44 0.63 0.81 264.8 16.36 0.44 0.64 0.83 245.5 18.19 0.43 0.65 0.86

Total Cool Cap. kBtuh 178.9 190.5 202.9 192.7 201.9 208.7 208.2 217.1 224.5

115°F

Comp. Sensible To Total

Motor

Ratio (S/T)

Input

Dry Bulb

kW 75°F 80°F 85°F

19.73 0.77 0.96 1

19.86 0.85 1

1

20 0.93 1

1

19.89 0.56 0.74 0.92

19.99 0.61 0.83 1

20.07 0.66 0.91 1

20.06 0.38 0.55 0.72

20.16 0.4 0.61 0.81

20.24 0.43 0.66 0.89

20 TON - HEATING LHT240H4M

Indoor Coil Air Volume
70°F Dry Bulb cfm
6400 8000 9600

65°F

Total

Comp.

Heating

Motor

Capacity

Input

kBtuh

kW

290.0

16.08

297.6

14.90

308.2

14.16

Air Temperature Entering Outdoor Coil

45°F

25°F

5°F

Total

Comp.

Total

Comp.

Total

Heating

Motor

Heating

Motor

Heating

Capacity

Input

Capacity

Input

Capacity

kBtuh

kW

kBtuh

kW

kBtuh

210.2

14.43

146.5

12.97

99.7

214.6

13.58

149.5

12.39

102.0

223.5

13.09

156.1

12.02

107.7

Comp. Motor Input
kW 11.98
11.62
11.42

-15°F

Total

Comp.

Heating

Motor

Capacity

Input

kBtuh

kW

64.5

11.46

66.3

11.36

71.5

11.32

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 23

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 24

BLOWER DATA

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE

FOR ALL UNITS ADD:

1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (electric heat, Economizer, etc.) 3 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.)

Then determine from blower table blower motor output and drive required. See page 25 for wet coil, option/accessory air resistance data, and factory installed drive kit specifications. See page 26 for minimum air volume required for use with optional electric heat.

Air Volume cfm

0.20

RPM

BHP

TOTAL STATIC PRESSURE - Inches Water Gauge (Pa)

0.40

0.60

0.80

1.00

1.20

1.40

1.60

1.80

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2750

385 0.30 505 0.50 600 0.70 680 0.90 755 1.10 820 1.30 - - - - - - - - - - - - - - - - - -

3000

395 0.35 515 0.55 610 0.75 685 1.00 760 1.20 825 1.45 885 1.70 - - - - - - - - - - - -

3250

405 0.40 520 0.60 615 0.85 695 1.10 765 1.30 830 1.60 890 1.85 950 2.10 - - - - - -

3500

415 0.45 530 0.70 620 0.95 700 1.20 775 1.45 840 1.70 900 2.00 955 2.25 1005 2.55

3750

425 0.50 540 0.75 630 1.05 710 1.30 780 1.60 845 1.85 905 2.15 960 2.45 1010 2.70

4000

435 0.55 545 0.85 635 1.10 715 1.40 785 1.70 850 2.00 910 2.30 965 2.60 1020 2.90

4250

445 0.60 555 0.90 645 1.25 725 1.55 795 1.85 855 2.15 915 2.45 970 2.80 1025 3.10

4500 4750 5000 5250 5500 5750 6000 6250 6500

455 0.70 565 1.00 655 1.35 730 1.65 800 2.00 865 2.35 925 2.65 980 3.00 1030 3.30 470 0.75 575 1.10 660 1.45 740 1.80 810 2.15 870 2.50 930 2.85 985 3.20 1040 3.55 480 0.85 585 1.25 670 1.60 750 1.95 815 2.30 880 2.70 940 3.05 995 3.40 1045 3.80 495 0.95 595 1.35 680 1.70 755 2.10 825 2.50 890 2.90 945 3.25 1000 3.65 1050 4.00 505 1.05 605 1.45 690 1.85 765 2.25 835 2.65 895 3.05 955 3.45 1010 3.85 1060 4.25 520 1.15 615 1.60 700 2.00 775 2.45 840 2.85 905 3.25 960 3.65 1015 4.10 1065 4.50 530 1.30 630 1.75 710 2.15 785 2.60 850 3.05 910 3.45 970 3.90 1025 4.35 1075 4.80 545 1.40 640 1.90 720 2.35 795 2.80 860 3.25 920 3.70 975 4.15 1030 4.60 1080 5.05 560 1.55 650 2.05 730 2.50 805 3.00 870 3.45 930 3.95 985 4.40 1040 4.85 1090 5.35

6750

570 1.70 665 2.20 745 2.70 815 3.20 880 3.70 940 4.20 995 4.65 1045 5.10 1095 5.60

7000

585 1.85 675 2.35 755 2.90 825 3.40 890 3.95 950 4.45 1005 4.95 1055 5.40 1105 5.95

7250

600 2.00 690 2.60 765 3.10 835 3.65 900 4.15 955 4.65 1015 5.25 1065 5.75 1115 6.25

7500

615 2.20 700 2.75 775 3.30 845 3.85 910 4.45 965 4.95 1020 5.50 1075 6.05 1125 6.60

7750

630 2.40 715 3.00 790 3.55 855 4.10 920 4.70 975 5.25 1030 5.80 1080 6.35 1130 6.90

8000

640 2.55 725 3.20 800 3.80 865 4.35 930 4.95 985 5.50 1040 6.10 1090 6.70 1140 7.25

8250

655 2.80 740 3.40 810 4.00 880 4.65 940 5.25 995 5.85 1050 6.45 1100 7.05 1150 7.65

8500

670 3.00 750 3.65 825 4.30 890 4.90 950 5.55 1005 6.15 1060 6.80 1110 7.40 1160 8.05

8750 9000 9250 9500 9750 10,000 10,250 10,500 10,750

685 3.25 765 3.90 835 4.55 900 5.20 960 5.85 1015 6.45 1070 7.15 1120 7.75 1165 8.35 700 3.50 780 4.20 850 4.85 910 5.50 970 6.15 1025 6.80 1080 7.50 1130 8.15 1175 8.75 715 3.75 790 4.45 860 5.15 925 5.85 985 6.55 1040 7.20 1090 7.85 1140 8.55 1185 9.20 730 4.00 805 4.75 875 5.45 935 6.15 995 6.90 1050 7.60 1100 8.25 1150 8.95 1195 9.60 745 4.30 820 5.05 885 5.75 950 6.55 1005 7.20 1060 7.95 1110 8.65 1160 9.40 1205 10.05 760 4.60 835 5.40 900 6.15 960 6.85 1015 7.60 1070 8.35 1120 9.05 1170 9.80 1215 10.50 775 4.90 845 5.65 910 6.45 970 7.20 1030 8.00 1080 8.75 1135 9.55 1180 10.25 1225 11.00 790 5.20 860 6.00 925 6.85 985 7.65 1040 8.40 1095 9.20 1145 10.00 1190 10.70 1235 11.45 805 5.55 875 6.40 940 7.25 1000 8.05 1055 8.85 1105 9.65 1155 10.45 1200 11.20 - - - - - -

11,000 820 5.90 890 6.80 950 7.60 1010 8.45 1065 9.30 1115 10.05 1165 10.90 - - - - - - - - - - - -

2.00 RPM BHP --- ---
--- ---
--- ----- --1060 3.00 1070 3.25 1075 3.45 1080 3.65 1085 3.90 1095 4.15 1100 4.40 1110 4.70 1115 4.95 1120 5.20 1130 5.50 1140 5.85 1145 6.10 1155 6.45 1160 6.75 1170 7.15 1180 7.50 1185 7.85 1195 8.25 1205 8.65 1215 9.05 1220 9.40 1230 9.85 1240 10.30 1250 10.80 1260 11.25 --- ----- ----- ----- ---

2.20 RPM BHP --- ---
--- ---
--- ----- --1110 3.30 1115 3.55 1120 3.75 1130 4.05 1135 4.25 1140 4.50 1150 4.80 1155 5.10 1160 5.35 1170 5.65 1175 5.95 1185 6.30 1190 6.60 1200 6.95 1205 7.30 1215 7.65 1225 8.05 1230 8.40 1240 8.85 1250 9.25 1255 9.65 1265 10.10 1275 10.55 1285 11.05 1295 11.50 --- ----- ----- ----- ----- ---

2.40 RPM BHP --- ---
--- ---
--- ----- ----- --1160 3.85 1165 4.10 1175 4.35 1180 4.65 1185 4.90 1195 5.20 1200 5.50 1205 5.80 1215 6.10 1220 6.45 1225 6.75 1235 7.10 1240 7.45 1250 7.85 1260 8.25 1265 8.60 1275 9.00 1280 9.40 1290 9.85 1300 10.30 1310 10.80 1315 11.20 --- ----- ----- ----- ----- ----- ----- ---

2.60 RPM BHP --- ---
--- ---
--- ----- ----- --1205 4.15 1210 4.45 1215 4.70 1225 5.00 1230 5.30 1235 5.60 1240 5.90 1250 6.25 1255 6.55 1265 6.90 1270 7.25 1275 7.60 1285 8.00 1290 8.35 1300 8.75 1305 9.15 1315 9.60 1325 10.05 1330 10.45 1340 10.90 1350 11.40 --- ----- ----- ----- ----- ----- ----- ----- ---

BLOWER DATA

FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS

Nominal hp

Maximum hp

Drive Kit Number

RPM Range

3

3.45

1

535 - 725

3

3.45

2

710 - 965

5

5.75

3

685 - 856

5

5.75

4

850 - 1045

5

5.75

5

945 - 1185

7.5

8.63

6

850 - 1045

7.5

8.63

7

945 - 1185

7.5

8.63

8

1045 - 1285

10

11.50

7

945 - 1185

10

11.50

10

1045 - 1285

10

11.50

11

1135 - 1365

NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
NOTE ­ Motor service factor limit - 1.0.

FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE

Air Volume cfm

Wet Indoor Coil
in. w.g.

Electric Heat
in. w.g.

Economizer in. w.g.

MERV 8

Filters MERV 13

3250

.03

- - -

- - -

.01

.04

3500

.03

- - -

- - -

.01

.04

3750

.03

- - -

- - -

.01

.04

4000

.04

- - -

- - -

.01

.04

4250

.04

- - -

- - -

.01

.05

4500

.05

- - -

- - -

.01

.05

4750

.05

- - -

- - -

.02

.05

5000

.05

- - -

- - -

.02

.06

5250

.06

- - -

- - -

.02

.06

5500

.07

- - -

- - -

.02

.06

5750

.07

- - -

- - -

.02

.07

6000

.08

.01

- - -

.03

.07

6250

.08

.01

.01

.03

.07

6500

.09

.01

.02

.03

.08

6750

.10

.01

.03

.03

.08

7000

.10

.01

.04

.04

.08

7250

.11

.01

.05

.04

.09

7500

.12

.01

.06

.04

.09

8000

.13

.02

.09

.05

.10

8500

.15

.02

.11

.05

.10

9000

.16

.04

.14

.06

.11

9500

.18

.05

.16

.07

.12

10,000

.20

.06

.19

.07

.12

10,500

.22

.09

.22

.08

.13

11,000

.24

.11

.25

.09

.14

MERV 16 0.07 0.08 0.08 0.09 0.10 0.10 0.11 0.12 0.12 0.13 0.14 0.14 0.15 0.16 0.17 0.17 0.18 0.19 0.21 0.22 0.24 0.25 0.27 0.29 0.30

Horizontal Roof Curb
in. w.g. .04 .05 .05 .06 .07 .07 .08 .08 .09 .10 .11 .11 .12 .13 .14 .15 .16 .17 .19 .21 .24 .26 .29 .31 .34

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 25

BLOWER DATA

MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT

Electric Heat kW

Minimum cfm

15

6000

30

6000

45

6000

60

6000

90

6000

POWER EXHAUST FAN PERFORMANCE

Return Air System Static

Air Volume Exhausted

Pressure

in. w.g.

cfm

0.00

8630

0.05

8210

0.10

7725

0.15

7110

0.20

6470

0.25

5790

0.30

5060

0.35

4300

0.40

3510

0.45

2690

0.50

1840

CEILING DIFFUSER AIR RESISTANCE - in. w.g.

Air Volume
cfm

Step-Down Diffuser

RTD11-185S

RTD11-275S

2

Ends

Open

1

Side/2 Ends Open

All Ends & Sides Open

2

Ends

Open

1

Side/2 Ends Open

All Ends & Sides Open

5000

.51

.44

.39

- - -

- - -

- - -

5200

.56

.48

.42

- - -

- - -

- - -

5400

.61

.52

.45

- - -

- - -

- - -

5600

.66

.56

.48

- - -

- - -

- - -

5800

.71

.59

.51

- - -

- - -

- - -

6000

.76

.63

.55

.36

.31

.27

6200

.80

.68

.59

- - -

- - -

- - -

6400

.86

.72

.63

- - -

- - -

- - -

6500

- - -

- - -

- - -

.42

.36

.31

6600

.92

.77

.67

- - -

- - -

- - -

6800

.99

.83

.72

- - -

- - -

- - -

7000

1.03

.87

.76

.49

.41

.36

7200

1.09

.92

.80

- - -

- - -

- - -

7400

1.15

.97

.84

- - -

- - -

- - -

7500

- - -

- - -

- - -

.51

.46

.41

7600

1.20

1.02

.88

- - -

- - -

- - -

8000

- - -

- - -

- - -

.59

.49

.43

8500

- - -

- - -

- - -

.69

.58

.50

9000

- - -

- - -

- - -

.79

.67

.58

9500

- - -

- - -

- - -

.89

.75

.65

10,000

- - -

- - -

- - -

1.00

.84

.73

10,500

- - -

- - -

- - -

1.10

.92

.80

11,000

- - -

- - -

- - -

1.21

1.01

.88

Flush Diffuser

FD11-185S FD11-275S

.27

- - -

.30

- - -

.33

- - -

.36

- - -

.39

- - -

.42

.29

.46

- - -

.50

- - -

- - -

.34

.54

- - -

.58

- - -

.62

.40

.66

- - -

.70

- - -

- - -

.45

.74

- - -

- - -

.50

- - -

.57

- - -

.66

- - -

.74

- - -

.81

- - -

.89

- - -

.96

CEILING DIFFUSER AIR THROW DATA - ft.

Model No.

Air Volume cfm

1 Effective Throw Range - ft.

RTD11-185S Step-Down

FD11-185S Flush

5600

39 - 49

28 - 37

5800

42 - 51

29 - 38

156, 180

6000 6200

44 - 54 45 - 55

40 - 50 42 - 51

6400

46 - 55

43 - 52

6600

47 - 56

45 - 56

1 Throw is the horizontal or vertical distance an airstream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 26

Model No.
240

Air Volume cfm
7200 7400 7600 7800 8000 8200 8400 8600 8800

1 Effective Throw Range - ft.

RTD11-275S Step-Down

FD11-275S Flush

33 - 38

26 - 35

35 - 40

28 - 37

36 - 41

29 - 38

38 - 43

40 - 50

39 - 44

42 - 51

41 - 46

43 - 52

43 - 49

44 - 54

44 - 50

46 - 57

47 - 55

48 - 59

ELECTRICAL/ELECTRIC HEAT DATA

Model No.

1 Voltage - 60Hz

Compressor 1 (Non-Inverter)

Rated Load Amps Locked Rotor Amps

Compressor 2 (Non-Inverter)

Rated Load Amps Locked Rotor Amps

Outdoor Fan Motors (6)

Full Load Amps (6 Non-ECM) Total

Power Exhaust (2) 0.33 HP

Full Load Amps Total

Service Outlet 115V GFI (amps)

Indoor Blower Motor

Horsepower Full Load Amps

2 Maximum Overcurrent Protection (MOCP)

Unit Only
With (2) 0.33 HP Power Exhaust

3 Minimum Circuit Ampacity (MCA)

Unit Only
With (2) 0.33 HP Power Exhaust

208/230V - 3 Ph 17.6 136 22.4 149 2.4

LHT156H4 460V - 3 Ph 8.5 66.1 10.6 75 1.3

14.4

2.4

4.8

15

3

5

7.8

1.3

2.6

15

3

5

10.6

16.7

4.8

7.6

90

90

40

45

90

100

45

50

71

77

35

38

76

82

37

40

ELECTRIC HEAT DATA

Electric Heat Voltage 208V 240V 208V 240V

2 Maximum

Unit+ 15 kW 4 110

125

125

125

Overcurrent

Electric Heat 30 kW 4 150

175

175

175

Protection (MOCP)

45 kW 4 200

225

4 200

225

60 kW 4 200

225

225

225

3 Minimum Circuit Ampacity (MCA)

Unit+ 15 kW 110

116

116

122

Electric Heat 30 kW 149

161

155

167

45 kW 188

206

194

213

60 kW 196

215

202

222

2 Maximum

Unit+ 15 kW 125

125

4 125

150

Overcurrent

Electric Heat 30 kW 175

175

175

175

Protection (MOCP) and (2) 0.33 HP

Power Exhaust 45 kW 4 200

225

4 200

225

60 kW 225

225

4 225

250

3 Minimum

Unit+ 15 kW 115

121

121

127

Circuit

Electric Heat 30 kW 154

166

160

172

Ampacity (MCA) and (2) 0.33 HP

Power Exhaust 45 kW 193

211

199

217

60 kW 201

220

207

226

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.

480V 60 80 110 110 57 80 103 107 60 90 110 110 60 83 105 110

480V 60 90 110 110 60 83 105 110 70 90 110 125 63 85 108 112

575V - 3 Ph 6.3 55.3 7.7 54 1

6

1

2

20

3

5

3.9

6.1

30

35

35

35

26

29

28

31

600V 45 70 80 90 44 62 80 84 50 70 90 90 46 64 82 86

600V 50 70 90 90 47 65 83 86 50 70 90 90 49 67 85 88

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 27

ELECTRICAL/ELECTRIC HEAT DATA

15 TON

Model No.

1 Voltage - 60Hz

Compressor 1 (Non-Inverter)

Rated Load Amps Locked Rotor Amps

Compressor 2 (Non-Inverter)

Rated Load Amps Locked Rotor Amps

Outdoor Fan Motors (6)

Full Load Amps (6 Non-ECM) Total

Power Exhaust (2) 0.33 HP

Full Load Amps Total

Service Outlet 115V GFI (amps)

Indoor Blower Motor

Horsepower Full Load Amps

2 Maximum Overcurrent Protection (MOCP)

Unit Only
With (2) 0.33 HP Power Exhaust

3 Minimum Circuit Ampacity (MCA)

Unit Only
With (2) 0.33 HP Power Exhaust

208/230V - 3 Ph 25.3 184 25 164 2.4

LHT180H4 460V - 3 Ph 9.6 84 12.2 100 1.3

14.4

7.8

2.4

1.3

4.8

2.6

15

15

3

5

7.5

3 5 7.5

10.6

16.7

24.2

4.8 7.6 11

100

110

110

45 50 50

110

110

125

50 50 50

575V - 3 Ph 8.4 60 9 78 1 6 1 2 20
3 5 7.5
3.9 6.1 9 35 40 40 40 40 45

82

88

96

38 41 44 30 32 35

87

93

101

41 43 47 32 34 37

ELECTRIC HEAT DATA

Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480 600V 600V 600V

2 Maximum Overcurrent Protection (MOCP)

Unit+ 15 kW 4 125 150 150 150 150 150 70 70 70 50 50 60 Electric Heat 30 kW 175 175 4 175 200 4 175 200 90 90 90 70 70 80
45 kW 4 200 225 225 225 4 225 250 110 110 125 90 90 90

60 kW 4 225 250 4 225 250 4 225 250 110 125 125 90 90 100

3 Minimum Circuit Ampacity (MCA)

Unit+ 15 kW 121 127 127 133 135 141 61 63 67 48 50 53 Electric Heat 30 kW 160 172 166 178 174 186 83 86 89 66 68 71
45 kW 199 217 205 224 213 231 106 108 112 84 86 89

60 kW 207 226 213 233 221 240 110 113 116 88 90 93

2 Maximum Overcurrent Protection (MOCP)

Unit+ Electric Heat and (2) 0.33 HP Power Exhaust

15 kW 150 150 150 150 150 150 70 70 70 50 60 60 30 kW 4 175 200 4 175 200 200 200 90 90 100 70 70 80 45 kW 225 225 4 225 250 4 225 250 110 125 125 90 90 100 60 kW 4 225 250 4 225 250 250 250 125 125 125 90 100 100

3 Minimum Circuit Ampacity (MCA)

Unit+ 15 kW 126 132 132 138 140 146 63 66 69 50 52 55 Electric Heat 30 kW 165 177 171 183 179 191 86 88 92 68 70 73 and (2) 0.33 HP Power Exhaust 45 kW 204 222 210 228 218 236 108 111 114 86 88 91
60 kW 212 231 218 237 226 245 113 116 119 90 92 95

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 28

ELECTRICAL/ELECTRIC HEAT DATA

20 TON

Model No.

1 Voltage - 60Hz

Compressor 1 (Non-Inverter)

Rated Load Amps Locked Rotor Amps

Compressor 2 (Non-Inverter)

Rated Load Amps Locked Rotor Amps

Outdoor Fan Motors (6)

Full Load Amps (6 Non-ECM) Total

Power Exhaust (2) 0.33 HP

Full Load Amps Total

Service Outlet 115V GFI (amps)

Indoor Blower Motor

Horsepower Full Load Amps

2 Maximum Overcurrent Protection (MOCP)

Unit Only
With (2) 0.33 HP Power Exhaust

3 Minimum Circuit Ampacity (MCA)

Unit Only
With (2) 0.33 HP Power Exhaust

LHT240H4

208/230V - 3 Ph

460V - 3 Ph

32.6

14.8

240

130

31.1

13

255

123

2.4

1.3

14.4

7.8

2.4

1.3

4.8

2.6

15

15

5

7.5

10

5 7.5 10

16.7

24.2

30.8

7.6 11 14

125

125

125

60 60 60

125

125

150

60 60 70

575V - 3 Ph 11.1 93.7 11 93.7 1 6 1 2 20
5 7.5 10 6.1 9 11 45 50 50 50 50 50

103

111

118

47 51 54 37 40 42

108

116

122

50 53 56 39 42 44

ELECTRIC HEAT DATA

Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

2 Maximum Overcurrent Protection (MOCP)

Unit+ Electric Heat

15 kW 150 150 4 150 175 175 175 70 80 80 60 60 60 30 kW 200 200 4 200 225 4 200 225 100 100 100 80 80 80 45 kW 4 225 250 250 250 4 250 4 300 125 125 125 100 100 100

60 kW 250 250 4 250 4 300 4 250 4 300 125 125 150 100 100 110

90 kW 4 300 4 350 4 300 4 350 350 4 350 175 175 175 125 150 150

3 Minimum Circuit Ampacity (MCA)

Unit+ 15 kW 143 149 150 156 157 163 70 73 76 56 58 60 Electric Heat 30 kW 182 194 189 201 196 208 93 96 99 74 76 78
45 kW 221 239 228 246 235 253 115 118 121 92 95 97

60 kW 229 248 236 255 243 262 120 123 126 95 98 100

90 kW 291 320 299 327 305 334 156 159 162 124 127 129

2 Maximum Overcurrent Protection (MOCP)

Unit+ Electric Heat and (2) 0.33 HP Power Exhaust

15 kW 4 150 175 175 175 175 175 80 80 80 60 60 70 30 kW 200 200 4 200 225 225 225 100 100 110 80 80 80 45 kW 250 250 4 250 4 300 4 250 4 300 125 125 125 100 100 100 60 kW 4 250 4 300 4 250 4 300 4 250 4 300 125 150 150 100 110 110

90 kW 4 300 4 350 350 4 350 350 4 350 175 175 175 150 150 150

3 Minimum Circuit Ampacity (MCA)

Unit+ Electric Heat and (2) 0.33 HP Power Exhaust

15 kW 147 153 155 161 161 167 73 76 79 58 60 62 30 kW 186 198 194 206 201 213 95 99 102 76 78 80 45 kW 226 244 233 251 240 258 118 121 124 94 97 99 60 kW 233 253 241 260 247 267 122 126 129 97 100 102

90 kW 296 325 303 332 310 339 158 162 165 126 129 131

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. 1 Extremes of operating range are plus and minus 10% of line voltage. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Factory installed circuit breaker not available.

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 29

ELECTRICAL ACCESSORIES - DISCONNECTS

13 TON | LHT156H4

Motor Horsepower

3

5

3

5

3

5

Electric Heat Voltage 208V 240V 208V 240V 480V 480V 600V 600V

Unit Only

54W85 54W85 54W86 54W86 54W85 54W85 54W85 54W85

+ Power Exhaust

54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85

+ Electric Heat 15 kW

54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 30 kW

54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85

+ Electric Heat 45 kW

54W87 54W86 54W87 54W86 54W85 54W85 54W85 54W85

+ Electric Heat 60 kW

54W87 54W87 54W87 54W87 54W86 54W86 54W85 54W85

+ Power Exhaust + Elec. Heat 15 kW 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 30 kW 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 45 kW 54W87 54W86 54W87 54W86 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 60 kW 54W87 54W87 54W87 54W87 54W86 54W86 54W85 54W85

15 TON | LHT180H4

Motor Horsepower

3

5

7.5

3

5

7.5

3

5

7.5

Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

Unit Only

54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust

54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 15 kW

54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 30 kW

54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 45 kW

54W87 54W86 54W87 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 60 kW

54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 15 kW 54W85 54W85 54W85 54W85 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 30 kW 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 45 kW 54W87 54W86 54W87 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 60 kW 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85

20 TON | LHT240H4

Motor Horsepower

5

7.5

10

5

7.5 10

5

7.5 10

Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

Unit Only

54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust

54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 15 kW

54W85 54W85 54W85 54W85 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 30 kW

54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 45 kW

54W87 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85

+ Electric Heat 60 kW

54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85

+ Electric Heat 90 kW

¹ NA ¹ NA ¹ NA ¹ NA ¹ NA ¹ NA 54W86 54W86 54W86 54W86 54W86 54W86

+ Power Exhaust + Elec. Heat 15 kW 54W85 54W85 54W86 54W85 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 30 kW 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 45 kW 54W87 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W86 54W85 54W85 54W85

+ Power Exhaust + Elec. Heat 60 kW 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W86

+ Power Exhaust + Elec. Heat 90 kW ¹ NA ¹ NA
Disconnects - 5 4W85 - 80A 54W86 - 150A 54W87 - 250A
1 Disconnect must be field furnished.
EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 30

¹ NA

¹ NA

¹ NA

¹ NA 54W86 54W86 54W86 54W86 54W86 54W86

ELECTRIC HEAT CAPACITIES

15 kW

30 kW

45 kW

60 kW

90 kW

Volts

Input kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of

Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages

208 11.3 38,600 1 22.5 76,800 1 33.8 115,300 2 45.0 153,600 2 67.6 230,700 2

220 12.6 43,000 1 25.2 86,000 1 37.8 129,000 2 50.4 172,000 2 75.6 258,000 2

230 13.8 47,100 1 27.5 93,900 1 41.3 141,000 2 55.1 188,000 2 82.7 282,200 2

240 15.0 51,200 1 30.0 102,400 1 45.0 153,600 2 60.0 204,800 2 90.0 307,100 2

440 12.6 43,000 1 25.2 86,000 1 37.8 129,000 2 50.4 172,000 2 75.6 258,000 2

460 13.8 47,100 1 27.5 93,900 1 41.3 141,000 2 55.1 188,000 2 82.7 282,200 2

480 15.0 51,200 1 30.0 102,400 1 45.0 153,600 2 60.0 204,800 2 90.0 307,100 2

550 12.6 43,000 1 25.2 86,000 1 37.8 129,000 2 50.4 172,000 2 75.6 258,000 2

575 13.8 47,100 1 27.5 93,900 1 41.3 141,000 2 55.1 188,000 2 82.7 282,200 2

600 15.0 51,200 1 30.0 102,400 1 45.0 153,600 2 60.0 204,800 2 90.0 307,100 2

FIELD WIRING NOTES · For use with copper wiring only · Field wiring not furnished · All wiring must conform to NEC or CEC and local electrical codes · For specific wiring information, please refer to the installation instructions

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 31

UNIT CLEARANCES Unit With Economizer

C
OUTDOOR AIR HOOD

D

B

Note: 210-240-300 sizes shown
A

1 Unit Clearance

A

B

in. mm in. mm in.

Service Clearance

60 1524 36 914 36

Minimum Operation Clearance

45 1143 36 914 36

NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1 S ervice Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation.

C mm 934 914

D in. mm 66 1676 41 1041

Top Clearance
Unobstructed

OUTDOOR SOUND DATA

Unit Model Number

Octave Band Sound Power Levels dBA, re 10-12 Watts - Center Frequency - Hz

125

250

500

1000

2000

4000

8000

156, 180, 240

79

84

88

89

85

82

73

Note - The octave sound power data does not include tonal corrections.
1 Sound Rating Number according to AHRI Standard 370-2001 (includes pure tone penalty). Sound Rating Number is the overall A-Weighted Sound Power Level (LwA), dBA (100 Hz to 10,000 Hz).

1 Sound Rating Number (dBA)
94

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 32

WEIGHT DATA

UNIT

Model Number

Net

lbs.

kg

Shipping

lbs.

kg

156 Base Unit

2198

997

2398

1088

156 Max. Unit

2488

1129

2688

1219

180 Base Unit

2226

1010

2426

1100

180 Max. Unit

2516

1141

2716

1232

240 Base Unit

2268

1029

2468

1119

240 Max. Unit

2558

1160

2758

1251

NOTE - Max. Unit is the unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories EXTERNAL to unit.

WEIGHT DATA
ECONOMIZER / OUTDOOR AIR / EXHAUST Economizer Economizer Dampers (with Outdoor Air Hood) Barometric Relief Dampers (downflow) Barometric Relief Dampers (horizontal) Outdoor Air Dampers with Hood (downflow) Motorized Manual Power Exhaust ELECTRIC HEAT 15 kW 30 kW 45 kW 60 kW 90 kW COIL/HAIL GUARDS All models ROOF CURBS Hybrid Roof Curbs, Downflow 8 in. height 14 in. height 18 in. height 24 in. height Adjustable Pitch Curb, Downflow 14 in. height Horizontal, Standard 26 in. height 37 in. height CEILING DIFFUSERS Step-Down
Flush
Transitions

RTD11-185S RTD11-275S
FD11-185S FD11-275S C1DIFF33C-1 C1DIFF34C-1

OPTIONS / ACCESSORIES

Shipping Weight

lbs.

kg

167

76

30

14

20

9

39

18

22

10

62

28

59

27

59

27

76

34

76

34

84

38

36

16

136

62

169

77

191

87

224

102

224

102

168

76

238

108

168

76

238

108

80

36

75

34

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 33

DIMENSIONS

CORNER WEIGHTS

CENTER OF GRAVITY

Model No.

AA

BB

CC

DD

EE

FF

lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm

LHT156 Base Unit

411 187 485 220 705 321 598 272 58-3/8 1481 37-1/8 943

LHT156 Max. Unit

509 231 575 261 745 338 659 300 57-1/8 1452 39-3/4 1010

LHT180 Base Unit

412 187 486 221 719 327 610 277 58-3/8 1482 36-3/4 934

LHT180 Max. Unit

511 232 577 262 758 345 671 305 57-1/8 1452 39-3/8 1000

LHT240 Base Unit

415 189 488 222 738 336 628 285 58-1/4 1479 36-1/4 921

LHT240 Max. Unit

513 233 578 263 777 353 690 314 57 1450 38-7/8 987

Base Unit - The unit with NO INTERNAL OPTIONS.
Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit.

AA

BB

4-1/4 (108)

28-3/8 (721)

12-3/8 (314)

15 (381)

60-1/2 (1537) BOTTOM RETURN
AIR OPENING

ALTERNATE (THRU THE BASE)

BOTTOM SUPPLY 18 (457) AIR OPENINGS

CONDENSATE DRAIN LOCATION

1-5/8 in. (41 mm) Diameter

5-5/8 (143)

12-3/8 (314)

4-1/2 (114) 28 (711)

28 (711)

20 (508)

20 (508)

EE

CENTER OF
GRAVITY FF

4 (102)

DD

CC

4 (102)

BOTTOM POWER ENTRY 5 X 8 inches (127 X 203 mm)

TOP VIEW

90-1/8 (2289)

OPTIONAL DISCONNECT (Factory Installed)

132-5/8

OPTIONAL

(3369)

115 VOLT OUTLET

(Factory Installed Inside Unit)

CONDENSATE DRAIN
5-3/8 (137)

54-1/4 (1378) 51 (1295)

28-3/4 (730)

SIDE ELECTRICAL INLETS
91-1/8 (2315) BASE
END VIEW

3-1/4 (83)

LIFTING HOLES (For Rigging
Front and Back)

FORKLIFT SLOTS (Front and Left Side Only) 107-3/4 (2737)
BASE
SIDE VIEW

25-3/8 (645)

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 34

DIMENSIONS

OUTDOOR AIR HOOD (Furnished with Economizer or
Outdoor Air Damper)

OUTDOOR AIR HOOD DETAIL
16 (406)

EXHAUST AIR HOOD (Furnished with Optional
Downflow Barometric Relief Dampers, Field Installed)

ACCESSORIES

OPTIONAL HORIZONTAL BAROMETRIC RELIEF DAMPERS WITH HOOD (Field installed in horizontal return air duct adjacent to unit)

31-5/8 (803) 1 29-1/2 (749)

6-1/2 (165)

14-1/2 (368)
1 13 (330)

FRONT VIEW NOTE - Two furnished per order no. 1 NOTE - Opening size required in return air duct.

SIDE VIEW

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 35

DIMENSIONS
HYBRID ROOF CURBS - DOUBLE DUCT OPENING

ACCESSORIES

86-1/8 (2188)

82-5/8

21

(2099) (533)

17 (432)

16 (406)

8-1/4 (210)

61-1/2 (1562)
RETURN OPENING

102 (2591)

61-1/2 (1562)

SUPPLY OPENING

81-1/2 (2070)
98-1/2 (2502)

8 (203) 14 (356) 18 (457) 24 (610)

NOTE - Roof deck may be omitted within confines of curb.

TYPICAL FLASHING DETAIL FOR ROOF CURB

BASE BOTTOM

PACKAGED UNIT

FIBERGLASS INSULATION
(Furnished)
NAILER STRIP (Furnished)
ROOF CURB (Extends around entire
perimeter of unit)
RIGID INSULATION (Field Supplied)

COUNTER FLASHING (Field Supplied)
CANT STRIP (Field Supplied)
ROOFING MATERIAL

DETAIL ROOF CURB
1-3/4 (44)
1/2 (13)

8 (203) 14 (356) 18 (457) 24 (610)

FACTORY INSTALLED PERIMETER WOOD NAILER STRIP

1-3/4 (44)

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 36

DIMENSIONS

ACCESSORIES

ADJUSTABLE PITCH CURB - DOUBLE DUCT OPENING

82-5/8 (2099)

86-1/8 (2188)
21 (533)

17 (432)

16 (406)

1-3/4 (44)

8-1/4 (210)

61-1/2 (1562)

SUPPLY OPENING

8-1/4 (210)

102-1/8 (2594)

61-1/2 (1562)
RETURN OPENING

98-1/2 (2502)

14 (356)

FACTORY INSTALLED PERIMETER WOOD NAILER STRIP

BOTTOM CURB ASSEMBLY

NOTE - Maximum slope pitch is 3/4 in. per 1 foot (19 mm per 305 mm) in any one direction.

TYPICAL FLASHING DETAIL FOR ROOF CURB

BASE BOTTOM

PACKAGED UNIT

FIBERGLASS INSULATION
(Furnished)
NAILER STRIP (Furnished)
ROOF CURB (Extends around entire
perimeter of unit)
RIGID INSULATION (Field Supplied)

COUNTER FLASHING (Field Supplied)
CANT STRIP (Field Supplied)
ROOFING MATERIAL

DETAIL ROOF CURB
1-3/4 (44)
1/2 (13)

14 (356)

FACTORY INSTALLED PERIMETER WOOD NAILER STRIP

1-3/4 (44)

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 37

DIMENSIONS

ACCESSORIES

ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS

69-1/4 (1759)

RETURN TRANSITION

RETURN AIR

OPENING

A

B

4-1/2 (114)

B SUPPLY AIR A OPENINGS

SUPPLY TRANSITION

SUPPORT ANGLE
(Furnished with Transitions)
54 (1372)

3/4 (19)

Typ.

26-1/2 (673)
8 (203)

TRANSITION DETAIL
69-1/4 (1759)

2

A

(51)

B

1-1/2 (38)

Typ.

TOP VIEW

TRANSITION OPENING SIZES

Model Number

A inch mm

B inch mm

C1DIFF33C-1 18

457

36

914

C1DIFF34C-1 24

610

48

1219

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 38

DIMENSIONS

ACCESSORIES

HORIZONTAL ROOF CURBS - Requires Optional Horizontal Return Air Panel Kit

Frame Opening

1-13/16 (46) 1-13/16
(46)
82-5/8 (2099) 86-1/4 (2191)

102-1/8 (2594)

98-1/2 (2502)

Frame Opening

1-13/16 (46) 1 26 (660) 2 37 (940)

1 (25)

2 (51) SECTION A-A

98-1/2 (2502)

1-13/16 (46)

NOTE - 26 in. (660 mm) height Curb is designed for

horizontal discharge when unit is mounted on a slab.

37 in. (940 mm) height Curb is designed for

A

A

horizontal discharge when unit is mounted on a rooftop.

PANEL TO COVER RETURN AIR OPENING IN BOTTOM OF UNIT (Furnished With Optional Horizontal Return Air Panel Kit)

54 (1372)

SUPPLY AIR TURNING VANE
(Furnished)

NOTE - Roof deck may be omitted within confines of curb.

SIDE VIEW (Packaged Unit)

1-13/16 (46)
1 26 (660) 2 37 (940)

TOP VIEW
102-1/8 (2594)

75

CURB SUPPLY

(1905)

AIR OPENING

WITH 1-1/2 IN. (38 MM) FLANGE

102-1/2 (2604)
FRONT VIEW

1,2 8-1/4 (210)

86-1/4 (2191)

5-1/2 (140) 14 (356)
1 6-1/2 (165) 2 17-1/2 (445)
1 Slab Applications

SUPPLY AIR TURNING VANE
(Furnished)
86-5/8 (2200)
SIDE VIEW 2 Rooftop Applications

SUPPLY DUCT
PANELS (Furnished)

HORIZONTAL SUPPLY AND RETURN AIR OPENINGS WITH HORIZONTAL ROOF CURB

OPTIONAL RETURN AIR PANEL KIT (Required for Horizontal Applications)

54-1/4 (1378)
¹ 76-1/4 (1937) ² 87-1/4 (2216)

60-1/2 (1537) 15 (381) HORIZONTAL RETURN
AIR OPENING 2 (51)

12-3/8 (314)

¹ 26 (660) 2 37 (940)

30-3/8 (772)

75 (1905) HORIZONTAL SUPPLY AIR OPENING

 NOTE - Top of Roof Curb extends 4 inch (102 mm) inside bottom of unit base. See Typical flashing detail.

HORIZONTAL ROOF CURB (Required For Horizontal Applications)
1 Slab Applications 2 Rooftop Applications

14 (356)

8-1/4 (210)

1 6-1/2 (165) 2 17-1/2 (445

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 39

DIMENSIONS

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS

STEP-DOWN CEILING DIFFUSER

FLUSH CEILING DIFFUSER

E

F G

G

H

2 (51)
N B
M

J

D

K C

A L

E

F G

G

H

2 (51) B

ACCESSORIES

J

D

K C

A

Model Number

A

in.

mm

B

in.

mm

C

in.

mm

D

in.

mm

E

in.

mm

F

in.

mm

G

in.

mm

H

in.

mm

J

in.

mm

K

in.

mm

L

in.

mm

M

in.

mm

N

in.

mm

Duct Size in.

mm

RTD11-185S 47-5/8 1210 47-5/8 1210 24-5/8 625 45-1/2 1156 45-1/2 1156 4-1/2 114 18 457 2-1/2 64 36 914 4-3/4 121 45-1/2 1156 45-1/2 1156 10-1/8 257 18 x 36
457 x 914

RTD11-275S 59-5/8 1514 59-5/8 1514 30-5/8 778 57-1/2 1461 57-1/2 1461 4-1/2 114 24 610 2-1/2 64 48 1219 4-3/4 121 57-1/2 1461 57-1/2 1461 11-1/8 283 24 x 48
610 x 1219

Model Number

A

in.

mm

B

in.

mm

C

in.

mm

D

in.

mm

E

in.

mm

F

in.

mm

G

in.

mm

H

in.

mm

J

in.

mm

K

in.

mm

Duct Size in.

mm

FD11-185S 47-5/8 1210 47-5/8 1210 29-1/4 743 45 1143 45 1143 4-1/2 114 18 457 2-1/4 57 36 914 4-1/2 114 18 x 36
457 x 914

FD11-275S 59-5/8 1514 59-5/8 1514 35-1/4 895 57 1148 57 1448 4-1/2 114 24 610 2-1/4 57 48 1219 4-1/2 114 24 x 48
610 x 1219

EnlightTM Packaged Heat Pump 13 to 20 Ton / Page 40

REVISIONS
Sections Weight Data

Description of Change Updated Roof Curb weights.

Visit us at www.Lennox.com For the latest technical information, www.LennoxCommercial.com Contact us at 1-800-4-LENNOX

NOTE - Due to Lennox' ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.

Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.

Installation and service must be performed by a qualified installer and servicing agency.

©2023 Lennox Industries, Inc.

